Abb acs150 руководство по эксплуатации

ABB ACS150 User Manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

ACS150

User’s Manual

ACS150 Drives (0.37…4 kW, 0.5…5 hp)

loading

Related Manuals for ABB ACS150

Summary of Contents for ABB ACS150

  • Page 1
    ACS150 User’s Manual ACS150 Drives (0.37…4 kW, 0.5…5 hp)
  • Page 2
    OPTION MANUALS (delivered with optional equipment and available in Internet) MUL1-R1 Installation instructions for ACS150 and ACS350 3AFE68642868 (EN) MFDT-01 FlashDrop User’s Manual 3AFE68591074 (EN) MAINTENANCE MANUALS (available in Internet) Guide for Capacitor Reforming in ACS50, ACS55, ACS150, ACS350, ACS550 and ACH550 3AFE68735190 (English)
  • Page 3
    The notice concerns ACS150 user’s manual Code: 3AUA0000069902 Rev A Code Revision Language Valid: From 2010-05-07 for ACS150 drives with drive firmware version 1.35A or later, until the release of Rev 3AFE68576032 English C of the manual. You can check the firmware version of…
  • Page 4
    (EN page 65) below. If you use other than the default connections presented below, see chapter Electrical installation, section I/O terminals in ACS150 user’s manual (3AFE68576032 [EN]). Note: Parameter 2108 START INHIBIT must remain in the default setting 0 (OFF).
  • Page 5: Reference

    Default I/O connections I/O connection Signal cable shield (screen) Process actual value: 4…20 mA Analog input circuit common +10V Reference voltage: +10 VDC, max. 10 mA 1…10 kohm +24V Auxiliary voltage output: +24 VDC, max. 200 mA Alternative connection Auxiliary voltage output common for AI1.

  • Page 6: Ref2 Select

    Default parameter values with PID Control macro (EN page 65) Index Name/Selection PID CONTROL 1001 EXT1 COMMANDS 1 = DI1 1002 EXT2 COMMANDS 20 = DI5 1003 DIRECTION 1 = FORWARD 1102 EXT1/EXT2 SEL 2 = DI2 1103 REF1 SELECT 2 = POT 1106 REF2 SELECT…

  • Page 7: Table Of Contents

    New parameters and parameter values (EN page 72) Parameters Index Name/Selection Description 11 REFERENCE Panel reference type, external control location selection and external reference sources and limits SELECT 1106 REF2 SELECT Selects the signal source for external reference REF2. 2 = POT PID1OUT New value.

  • Page 8
    Parameters Index Name/Selection Description 40 PROCESS PID SET 1 Process PID (PID1) control parameter set 1. 4001 GAIN Defines the gain for the process PID controller. High gain may cause speed oscillation. 0.1…100.0 Gain. When value is set to 0.1, the PID controller output changes one-tenth as much as the error value.
  • Page 9
    Parameters Index Name/Selection Description 0.0…10.0 s Filter time constant. If parameter value is set to zero, the derivative filter is disabled. 4005 ERROR VALUE INV Selects the relationship between the feedback signal and drive speed (drive 0 = NO output frequency). Normal: A decrease in feedback signal increases drive speed (drive output frequency).
  • Page 10
    Parameters Index Name/Selection Description DI3U,4D(NC) Digital input DI3: Reference increase. Digital input DI4: Reference decrease. The program stores the active reference (not reset by a stop command). When this selection becomes active (in change from EXT1 to EXT2), the reference initializes to the value used when this control location (and this selection) was active the last time.
  • Page 11
    Parameters Index Name/Selection Description MIN(ACT1,2) Selects the smaller of ACT1 and ACT2 MAX(ACT1,2) Selects the higher of ACT1 and ACT2 sqrt(ACT1-2) Square root of the subtraction of ACT1 and ACT2 sqA1+sqA2 Addition of the square root of ACT1 and the square root of ACT2 sqrt(ACT1) Square root of ACT1.
  • Page 12
    Parameters Index Name/Selection Description -1000…1000% Value in percent 4020 ACT2 MINIMUM See parameter 4018 ACT1 MINIMUM. -1000…1000% See parameter 4018. 4021 ACT2 MAXIMUM See parameter 4019 ACT1 MAXIMUM. 100% -1000…1000% See parameter 4019. 4022 SLEEP SELECTION Activates the sleep function and selects the source for the activation input. 0 = NOT SEL NOT SEL No sleep function selected…
  • Page 13
    Wake-up delay 99 START-UP DATA Language selection. Definition of motor set-up data. 9902 APPLIC MACRO Selects the application macro. See chapter Application macros in ACS150 1 = ABB user’s manual (3AFE68576032 [EN]). STANDARD PID CONTROL New value. PID control. For application in which the drive controls a process value.
  • Page 14
    Quick configuration of process control 9902 APPLIC MACRO 4018 ACT1 4010 Process MINUMUM POINT SEL 4019 ACT1 MAXIMUM 4019 ACT1 4016 ACT1 MAXIMUM INPUT 4018 ACT1 MINUMUM PID output 4014 4021 ACT2 MAXIMUM 4017 ACT2 INPUT 4020 ACT2 MINUMUM 4001 GAIN 4002 INTEGRATION TIME…
  • Page 15
    SET POINT SEL to 19 (INTERNAL). 2. Set 4011 INTERNAL SETPNT to 5.0 («bar» is not displayed on the drive control panel) as an example. For detailed parameter descriptions, see the related parameters in ACS150 user’s manual (3AFE68576032 [EN]). Update notice…
  • Page 16
    4022 4026 1) 1 = Activate sleeping 0 = Deactivate sleeping %refActive: The % reference (EXT REF2) is in use. See parameter 1102 EXT1/EXT2 SEL in ACS150 user’s manual (3AFE68576032 [EN]). PIDCtrlActive: Parameter 9902 APPLIC MACRO = PID CONTROL. See ACS150 user’s manual (3AFE68576032 [EN]).
  • Page 17
    consequence, the PID process controller decreases the motor speed. However, due to natural losses in the pipes and the low efficiency of the centrifugal pump at low speeds, the motor does not stop but keeps rotating. The sleep function detects the slow rotation, and stops the unnecessary pumping after the sleep delay has passed.
  • Page 18
    NEW USER MACRO (USER PARAMETER SET) FUNCTIONALITY (EN page 57) Macro Suitable applications User The user can save the customised standard macro, i.e. the parameter settings, including group 99 START-UP DATA, into the permanent memory, and recall the data at a later time. For example, three user macros can be used when switching between three different motors is required.
  • Page 19
    Description 99 START-UP DATA Language selection. Definition of motor set-up data. 9902 APPLIC MACRO Selects the application macro. See chapter Application macros in ACS150 1 = ABB user’s manual (3AFE68576032 [EN]). STANDARD USER S1 LOAD New value. User 1 macro loaded into use. Before loading, check that the saved parameter settings and the motor model are suitable for the application.
  • Page 20
    NEW MOTOR CONTROL FUNCTIONALITY: Noise smoothing, DC stabilizer and ON (LOAD) switching frequency control option New parameters and parameter values (EN page 72) Parameters Index Name/Selection Description 26 MOTOR CONTROL Motor control variables 2607 SWITCH FREQ CTRL Activates the switching frequency control. When active, the selection of 1 = ON parameter 2606 SWITCHING FREQ is limited when the drive internal temperature increases.
  • Page 21
    DISABLE. EXTERNAL External brake chopper control. Note: The drive is compatible only with ABB ACS-BRK-X brake units. Note: Ensure the brake unit is installed and the overvoltage control is switched off by setting parameter 2005 OVERVOLT CTRL to selection DISABLE.
  • Page 22: Acs150 Drive Manuals

    Update notice…

  • Page 23
    ACS150 Drives 0.37…4 kW 0.5…5 hp User’s Manual 3AFE68576032 Rev B EFFECTIVE: 12.9.2007 © 2007 ABB Oy. All Rights Reserved.
  • Page 25: Safety

    Safety What this chapter contains The chapter contains the safety instructions which you must follow when installing, operating and servicing the drive. If ignored, physical injury or death may follow, or damage may occur to the drive, motor or driven equipment. Read the safety instructions before you work on the drive.

  • Page 26: Operation And Start-Up

    • The drive is not field repairable. Never attempt to repair a malfunctioning drive; contact your local ABB representative or Authorized Service Center for replacement. • Make sure that dust from drilling does not enter the drive during the installation.

  • Page 27
    Providing feedback on ABB Drives manuals ……..
  • Page 28
    Planning electrical installation What this chapter contains …………23 Motor selection .
  • Page 29
    ABB Standard macro ……..
  • Page 30: Relay Output 1

    Actual signals …………..70 01 OPERATING DATA .

  • Page 31
    Current and power …………113 Symbols .
  • Page 32
    Table of contents…
  • Page 33: About The Manual

    Product and service inquiries Address any inquiries about the product to your local ABB representative, quoting the type code and serial number of the unit in question. A listing of ABB sales, support and service contacts can be found by navigating to www.abb.com/drives…

  • Page 34: Installation And Commissioning Flowchart

    Installation and commissioning flowchart Task Identify the frame size of your drive: R0…R2. Technical data: Ratings on page Plan the installation: select the cables, etc. Planning electrical installation on page Check the ambient conditions, ratings and required Technical data on page cooling air flow.

  • Page 35: Hardware Description

    The chapter describes the construction and type code information in short. Overview The ACS150 is a wall or cabinet mountable drive for controlling AC motors. The construction of frame sizes R0…R2 varies to some extent. Without plates (R0 and R1)

  • Page 36: Overview: Connections And Switch

    Overview: Connections and switch The diagram shows the connections and switch of the ACS150. FlashDrop connection EMC filter grounding screw Varistor grounding screw Potentiometer AI type selection V / mA Relay output Analog input 250 VAC / 30 VDC 0(2)…+10 VDC or 0(4)…+20 mA…

  • Page 37: Type Code

    The type code contains information on the specifications and configuration of the drive. You find the type code on the type designation label attached to the drive. The first digits from the left express the basic configuration, for example ACS150-03E- 08A8-4. The explanations of the type code selections are described below.

  • Page 38
    Hardware description…
  • Page 39: Mechanical Installation

    Mechanical installation What this chapter contains The chapter describes the mechanical installation procedure of the drive. Unpacking the drive The drive (1) is delivered in a package that also contains the following items (frame size R0 shown in the figure): •…

  • Page 40: Delivery Check

    Before installation The ACS150 may be installed on the wall or in a cabinet. Check the enclosure requirements for the need to use the NEMA 1 option in wall installations (see chapter Technical data).

  • Page 41: Free Space Around The Drive

    Free space around the drive The required free space for cooling above and below the drive is 75 mm (3 in.). No free space is required on the sides of the drive, so they can be mounted side by side. Mounting the drive Mount the drive Note: Make sure that dust from drilling does not enter the drive during the…

  • Page 42: Fasten Clamping Plates

    Fasten clamping plates 1. Fasten the clamping plate to the plate at the bottom of the drive with the provided screws. 2. Fasten the I/O clamping plate to the clamping plate with the provided screws. Mechanical installation…

  • Page 43: Planning Electrical Installation

    Note: The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations.

  • Page 44: Thermal Overload And Short-Circuit Protection

    2) Circuit breakers which have been tested by ABB with the ACS150 can be used. Fuses must be used with other circuit breakers. Contact your local ABB representative for the approved breaker types and supply network characteristics.

  • Page 45: Thermal Overload Protection Of The Motor

    Thermal overload protection of the motor According to regulations, the motor must be protected against thermal overload and the current must be switched off when overload is detected. The drive includes a motor thermal protection function that protects the motor and switches off the current when necessary.

  • Page 46: Selecting The Power Cables

    Selecting the power cables General rules Dimension the input power and motor cables according to local regulations. • The cable must be able to carry the drive load current. See chapter Technical data for the rated currents. ° • The cable must be rated for at least 70 C maximum permissible temperature of the conductor in continuous use.

  • Page 47: Motor Cable Shield

    Motor cable shield To function as a protective conductor, the shield must have the same cross-sectional area as the phase conductors when they are made of the same metal. To effectively suppress radiated and conducted radio-frequency emissions, the shield conductivity must be at least 1/10 of the phase conductor conductivity. The requirements are easily met with a copper or aluminium shield.

  • Page 48: Protecting The Relay Output Contact And Attenuating Disturbances In Case Of Inductive Loads

    Residual current device (RCD) compatibility ACS150-01x drives are suitable to be used with residual current devices of Type A, ACS150-03x drives with residual current devices of Type B. For ACS150-03x drives, other measures for protection in case of direct or indirect contact, such as separation from the environment by double or reinforced insulation or isolation from the supply system by a transformer, can also be applied.

  • Page 49: Relay Cable

    Never mix 24 VDC and 115/230 VAC signals in the same cable. Relay cable The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL) has been tested and approved by ABB. Routing the cables Route the motor cable away from other cable routes. Motor cables of several drives can be run in parallel installed next to each other.

  • Page 50: Control Cable Ducts

    A diagram of the cable routing is shown below. Motor cable Drive min. 300 mm (12 in.) Power cable Input power cable Motor cable 90 ° min. 200 mm (8 in.) min. 500 mm (20 in.) Control cables Control cable ducts 24 V 230 V 24 V 230 V…

  • Page 51: Electrical Installation

    Protective Earth conductor using a measuring voltage of 500 V DC. The insulation resistance of an ABB motor must exceed 10 Mohm (reference value at 25 °C or 77 °F). For the insulation resistance of other motors, please consult the W1 PE manufacturer’s instructions.

  • Page 52: Connecting The Power Cables

    Connecting the power cables Connection diagram Drive INPUT OUTPUT V1 W1 V2 W2 BRK- BRK+ For alternatives, see section Supply Optional brake disconnecting device resistor on page 23. Motor Ground the other end of the PE conductor at the distribution board. Use a separate grounding cable if the conductivity of the cable shield is insufficient (smaller than the conductivity of the phase conductor) and there is no symmetrically constructed grounding conductor in the cable (see section Selecting the…

  • Page 53: Procedure

    1. On IT (ungrounded) systems and corner grounded TN systems, disconnect the internal EMC filter by removing the screw at EMC. For 3-phase U-type drives (with type code ACS150-03U-), the screw at EMC is already removed at the factory and replaced by a plastic screw.

  • Page 54: Connecting The Control Cables

    Connecting the control cables I/O terminals The figure below shows the I/O connectors. X1A: SCR X1B: (RO)COM AI(1) (RO)NC (RO)NO +10 V +24 V DCOM DI5 digital or frequency input The default connection of the control signals depends on the application macro in use, which is selected with parameter 9902.

  • Page 55: Procedure

    Procedure 1. Analog signal (if connected): Strip the outer insulation of the analog signal cable 360 degrees and ground the bare shield under the clamp. 2. Connect the conductors to the appropriate terminals. 3. Connect the grounding conductor of the used pair in the analog signal cable to the SCR terminal.

  • Page 56
    Electrical installation…
  • Page 57: Installation Checklist

    Installation checklist Checklist Check the mechanical and electrical installation of the drive before start-up. Go through the checklist below together with another person. Read chapter Safety the first pages of this manual before you work on the drive. Check MECHANICAL INSTALLATION The ambient operating conditions are allowed.

  • Page 58
    Installation checklist…
  • Page 59: Start-Up And Control With I/O

    ENTRY OF START-UP DATA Select the application macro (parameter 9902). 9902 The default value 1 (ABB STANDARD) is suitable in most cases. The general parameter setting procedure in the Short Parameter mode is described below. You find more detailed instructions on setting parameters on page 53.

  • Page 60
    7. Save the parameter value by pressing Enter the motor data from the motor nameplate: Note: Set the motor data to exactly the same value as on the motor nameplate. ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl. F…
  • Page 61: Select

    Set constant speeds (drive output frequencies) 1, 2 and 3 1202 (parameters 1202, 1203 and 1204). 1203 1204 Set the minimum value (%) corresponding to the minimum 1301 signal for AI(1) (parameter 1301). Set the maximum limit for the drive output frequency 2008 (parameter 2008).

  • Page 62
    ACCELERATION/DECELERATION TIMES Set the acceleration time 1 (parameter 2202). 2202 Set the deceleration time 1 (parameter 2203). 2203 FINAL CHECK The start-up is now completed. Check that there are no faults or alarms shown in the display. The drive is now ready for use. Start-up and control with I/O…
  • Page 63: How To Control The Drive Through The I/O Interface

    Ensure that the control connections are wired according to the ABB Standard macro page 59. connection diagram given for the ABB Standard macro. Ensure that the drive is in remote control. Press key to switch In remote control, the panel display shows text REM.

  • Page 64
    Start-up and control with I/O…
  • Page 65: Control Panel

    The chapter describes the control panel keys and display fields. It also instructs in using the panel in control, monitoring and changing the settings. Integrated Control Panel The ACS150 works with the Integrated Control Panel, which provides basic tools for manual entry of parameter values. Control panel…

  • Page 66: Overview

    Overview The following table summarizes the key functions and displays on the Integrated Control Panel. No. Use LCD display – Divided into five areas: a. Upper left – Control location: LOC: drive control is local, that is, from the control panel REM: drive control is remote, such as the drive I/O.

  • Page 67: Operation

    The ACS150 includes an integrated potentiometer located at the front of the drive. It is used for setting the frequency reference. The Integrated Control Panel has six panel modes: Output, Reference, Short Parameter, Long Parameter, Changed Parameters and Fault.

  • Page 68: How To Do Common Tasks

    How to do common tasks The table below lists common tasks, the mode in which you can perform them and the page number where the steps to do the task are described in detail. Task Mode Page How to switch between local and remote control How to start and stop the drive How to change the direction of the motor rotation How to set the frequency reference…

  • Page 69: How To Start, Stop And Switch Between Local And Remote Control

    How to start, stop and switch between local and remote control You can start, stop and switch between local and remote control in any mode. To be able to start or stop the drive, the drive must be in local control. Step Action Display…

  • Page 70: How To Set The Frequency Reference

    How to set the frequency reference You can set the local frequency reference with the integrated potentiometer in any mode when the drive is in local control if parameter 1109 LOC REF SOURCE has the default value 0 (POT). If parameter 1109 LOC REF SOURCE has been changed to 1 (KEYPAD), so that you can use keys…

  • Page 71: Output Mode

    Output mode In the Output mode, you can: • monitor actual values of up to three group 01 OPERATING DATA signals, one signal at a time • start, stop, change direction, switch between local and remote control and set the frequency reference.

  • Page 72: Reference Mode

    Reference mode In the Reference mode, you can: • view and set the frequency reference • start, stop, change direction and switch between local and remote control. How to view and set the frequency reference You can set the local frequency reference with the integrated potentiometer in any mode when the drive is in local control if parameter 1109 LOC REF SOURCE has…

  • Page 73: Parameter Modes

    Parameter modes There are two parameter modes: Short Parameter mode and Long Parameter mode. Both function identically, except that the Short Parameter mode shows only the minimum number of parameters typically required to set up the drive (see section Parameters in the Short Parameter mode on page 66).

  • Page 74: How To Select The Monitored Signals

    Step Action Display Use keys to select the parameter value. When you have changed the parameter value, starts flashing. 1203 • To save the displayed parameter value, press • To cancel the new value and keep the original, press How to select the monitored signals Step Action Display…

  • Page 75: Changed Parameters Mode

    Changed Parameters mode In the Changed Parameters mode, you can: • view a list of all parameters that have been changed from the macro default values • change these parameters • start, stop, change direction, switch between local and remote control and set the frequency reference.

  • Page 76
    Control panel…
  • Page 77: Application Macros

    Application macros are preprogrammed parameter sets. While starting up the drive, the user selects the macro best suited for the purpose with parameter 9902 APPLIC MACRO. The ACS150 has five application macros. The table below contains a summary of the macros and describes suitable applications. Macro Suitable applications ABB Standard Ordinary speed control applications where no, one, two or three constant speeds are used.

  • Page 78: Summary Of I/O Connections Of Application Macros

    Summary of I/O connections of application macros The following table gives the summary of the default I/O connections of all application macros. Macro Input/output Motor ABB Standard 3-wire Alternate Hand/Auto Potentiometer Frequency Frequency Frequency Frequency ref. reference reference reference (Auto)

  • Page 79: Abb Standard Macro

    ABB Standard macro This is the default macro. It provides a general purpose I/O configuration with three constant speeds. Parameter values are the default values given in chapter Actual signals and parameters, starting from page 65. If you use other than the default connections presented below, see section terminals on page 34.

  • Page 80: 3-Wire Macro

    3-wire macro This macro is used when the drive is controlled using momentary push-buttons. It provides three constant speeds. To enable the macro, set the value of parameter 9902 to 2 (3-WIRE). For the parameter default values, see section Default parameter values with different macros on page 65.

  • Page 81: Alternate Macro

    Alternate macro This macro provides an I/O configuration adapted to a sequence of DI control signals used when alternating the rotation direction of the drive. To enable the macro, set the value of parameter 9902 to 3 (ALTERNATE). For the parameter default values, see section Default parameter values with different macros on page 65.

  • Page 82: Motor Potentiometer Macro

    Motor Potentiometer macro This macro provides a cost-effective interface for PLCs that vary the speed of the drive using only digital signals. To enable the macro, set the value of parameter 9902 to 4 (MOTOR POT). For the parameter default values, see section Default parameter values with different macros on page 65.

  • Page 83: Hand/Auto Macro

    Hand/Auto macro This macro can be used when switching between two external control devices is needed. To enable the macro, set the value of parameter 9902 to 5 (HAND/AUTO). For the parameter default values, see section Default parameter values with different macros on page 65.

  • Page 84
    Application macros…
  • Page 85: Actual Signals And Parameters

    5 = DI5 0 = NOT SEL 5 = DI5 0 = NOT SEL 0 = NOT SEL 9902 APPLIC MACRO 1 = ABB STANDARD 2 = 3-WIRE 3 = ALTERNATE 4 = MOTOR POT 5 = HAND/AUTO Actual signals and parameters…

  • Page 86: Parameters In The Short Parameter Mode

    Selects the application macro or activates FlashDrop parameter values. See 1 = ABB chapter Application macros. STANDARD 1 = ABB STANDARD Standard macro for constant speed applications 2 = 3-WIRE 3-wire macro for constant speed applications 3 = ALTERNATE Alternate macro for start forward and start reverse applications…

  • Page 87: Fault History

    Parameters in the Short Parameter mode Name/Value Description 9907 MOTOR NOM FREQ Defines the nominal motor frequency, i.e the frequency at which the output Eur: 50 / voltage equals the motor nominal voltage: US: 60 Field weakening point = Nom. frequency · Supply voltage / Mot nom. voltage 10.0…500.0 Hz Frequency 04 FAULT HISTORY…

  • Page 88: Analog Inputs

    Parameters in the Short Parameter mode Name/Value Description 13 ANALOG INPUTS Analog input signal minimum 1301 MINIMUM AI1 Defines the minimum % value that corresponds to minimum mA/(V) signal for analog input AI1. 0…20 mA 0…100% 4…20 mA 20…100% When analog input AI1 is selected as the source for external reference REF1, the value corresponds to the minimum reference value, i.e.

  • Page 89
    Parameters in the Short Parameter mode Name/Value Description 2203 DECELER TIME 1 Defines the deceleration time 1 i.e. the time required for the speed to change from the value defined by parameter 2008 MAXIMUM FREQ to zero. — If the speed reference decreases slower than the set deceleration rate, the motor speed will follow the reference signal.
  • Page 90: Actual Signals

    Actual signals The following table includes the descriptions of all actual signal. Actual signals Name/Value Description 01 OPERATING DATA Basic signals for monitoring the drive (read-only). For actual signal supervision, see parameter group SUPERVISION. For selection of an actual signal to be displayed on the control panel, see parameter group 34 PANEL DISPLAY.

  • Page 91: Fault History

    Actual signals Name/Value Description 04 FAULT HISTORY Fault history (read-only) 0401 LAST FAULT Fault code of the latest fault. See chapter Fault tracing for the codes. 0 = fault history is clear (on panel display = NO RECORD). 0402 FAULT TIME 1 Day on which the latest fault occurred.

  • Page 92: Parameters In The Long Parameter Mode

    Parameters in the Long Parameter mode The following table includes the complete descriptions of all parameters that are visible only in the Long Parameter mode. See section Parameter modes on page for how to select the parameter mode. Parameters in the Long Parameter mode Index Name/Selection Description 10 START/STOP/DIR…

  • Page 93: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 1 = FORWARD Fixed to forward 2 = REVERSE Fixed to reverse 3 = REQUEST Direction of rotation control allowed 1010 JOGGING SEL Defines the signal that activates the jogging function. The jogging function is 0 = NOT SEL typically used to control a cyclical movement of a machine section.

  • Page 94: Reference Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3 = DI3 See selection DI1. 4 = DI4 See selection DI1. 5 = DI5 See selection DI1. 0 = NOT SEL Not selected -1 = DI1(INV) Inverted digital input DI1. 1 = jogging inactive, 0 = jogging active. -2 = DI2(INV) See selection DI1(INV).

  • Page 95: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3 = AI1/JOYST Analog input AI1 as joystick. The minimum input signal runs the motor at the maximum reference in the reverse direction, the maximum input at the maximum reference in the forward direction. Minimum and maximum references are defined by parameters 1104 REF1 MIN and…

  • Page 96: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 1104 REF1 MIN Defines the minimum value for external reference REF1. Corresponds to the minimum setting of the used source signal. 0.0…500.0 Hz Minimum value. Example: Analog input AI1 is selected as the reference source (value of parameter 1103 REF1 SELECT is AI1).

  • Page 97: Constant Speeds

    Parameters in the Long Parameter mode Index Name/Selection Description 12 CONSTANT SPEEDS Constant speed selection and values. It is possible to define seven positive constant speeds. Constant speeds are selected with digital inputs. Constant speed activation overrides the external speed reference. Constant speed selections are ignored if drive is in local control mode.

  • Page 98: Select

    Parameters in the Long Parameter mode Index Name/Selection Description -5 = DI5(INV) Speed defined by parameter 1202 CONST SPEED 1 is activated through inverted digital input DI5. 0 = active, 1 = inactive. -7 = DI1,2 (INV) Constant speed selection through inverted digital inputs DI1 and DI2. 1 = DI active, 0 = DI inactive.

  • Page 99: Analog Inputs

    Parameters in the Long Parameter mode Index Name/Selection Description 13 ANALOG INPUTS Analog input signal processing 1301 MINIMUM AI1 Defines the minimum %-value that corresponds to minimum mA/(V) signal for analog input AI1. When used as a reference, the value corresponds to the reference minimum setting.

  • Page 100: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 7 = STARTED The drive has received a start command. Relay is energized even if Run Enable signal is off. Relay is de-energized when drive receives a stop command or a fault occurs. 8 = SUPRV 1 OVER Status according to supervision parameters 3201…3203.

  • Page 101: System Controls

    Parameters in the Long Parameter mode Index Name/Selection Description 16 SYSTEM Run Enable, parameter lock etc. CONTROLS 1601 RUN ENABLE Selects a source for the external Run Enable signal. 0 = NOT SEL 0 = NOT SEL Allows the drive to start without an external Run Enable signal. 1 = DI1 External signal required through digital input DI1.

  • Page 102: Freq Input

    Parameters in the Long Parameter mode Index Name/Selection Description -3 = DI3(INV) See selection DI1(INV). -4 = DI4(INV) See selection DI1(INV). -5 = DI5(INV) See selection DI1(INV). 1606 LOCAL LOCK Disables entering local control mode or selects the source for the local 0 = NOT SEL control mode lock signal.

  • Page 103: Limits

    Parameters in the Long Parameter mode Index Name/Selection Description 0…16000 Hz Minimum frequency 1802 FREQ INPUT MAX Defines the maximum input value when DI5 is used as a frequency input. 1000 0…16000 Hz Maximum frequency 1803 FILTER FREQ IN Defines the filter time constant for frequency input, i.e the time within 63% of a step change is reached.

  • Page 104: Start/Stop

    Parameters in the Long Parameter mode Index Name/Selection Description 21 START/STOP Start and stop modes of the motor 2101 START FUNCTION Selects the motor starting method. 1 = AUTO 1 = AUTO Frequency reference ramps immediately from 0 Hz. 2 = DC MAGN The drive pre-magnetises the motor with DC current before the start.

  • Page 105: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 2106 DC CURR REF Defines the DC braking current. See parameter 2104 DC HOLD CTL. 0…100% Value in percent of the motor nominal current (parameter 9906 MOTOR NOM CURR) 2107 DC BRAKE TIME Defines the DC braking time.

  • Page 106: Accel/Decel

    Parameters in the Long Parameter mode Index Name/Selection Description 2112 ZERO SPEED DELAY Defines the delay for the Zero Speed Delay function. The function is useful in applications where a smooth and quick restarting is essential. During the delay the drive knows accurately the rotor position. No Zero Speed Delay With Zero Speed Delay Speed…

  • Page 107: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 2202 ACCELER TIME 1 Defines the acceleration time 1 i.e. the time required for the speed to change from zero to the speed defined by parameter 2008 MAXIMUM FREQ. — If the speed reference increases faster than the set acceleration rate, the motor speed will follow the acceleration rate.

  • Page 108: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 2205 ACCELER TIME 2 Defines the acceleration time 2 i.e. the time required for the speed to change from zero to the speed defined by parameter 2008 MAXIMUM FREQ. See parameter 2202 ACCELER TIME 1.

  • Page 109: Critical Speeds

    Parameters in the Long Parameter mode Index Name/Selection Description 25 CRITICAL SPEEDS Speed bands within which the drive is not allowed to operate. A Critical Speeds function is available for applications where it is necessary to avoid certain motor speeds or speed bands because of e.g. mechanical resonance problems.

  • Page 110: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 1 = ON Active 2603 IR COMP VOLT Defines the output voltage boost at zero speed (IR compensation). The Type function is useful in applications with high break-away torque. To prevent dependent overheating, set IR compensation voltage as low as possible.

  • Page 111: Fault Functions

    Parameters in the Long Parameter mode Index Name/Selection Description 2608 SLIP COMP RATIO Defines the slip gain for the motor slip compensation control. 100% means full slip compensation, 0% means no slip compensation. Other values can be used if a static speed error is detected despite of the full slip compensation. Example: 35 Hz constant speed reference is given to the drive.

  • Page 112: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3005 MOT THERM PROT Selects how the drive reacts when motor overtemperature is detected. 1 = FAULT The drive calculates the temperature of the motor on the basis of the following assumptions: 1) The motor is in the ambient temperature of 30°C when power is applied to the drive.

  • Page 113: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3008 ZERO SPEED LOAD Defines the load curve together with parameters 3007 MOT LOAD CURVE 3009 BREAK POINT FREQ. 25.…150% Allowed continuous motor load at zero speed in percent of the nominal motor current 3009 BREAK POINT FREQ…

  • Page 114: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3012 STALL TIME Defines the time for the stall function. See parameter 3010 STALL FUNCTION. 10…400 s Time 3013 UNDERLOAD FUNC Selects how the drive reacts to underload. The protection wakes up if 0 = NOT SEL — the motor torque falls below the curve selected by parameter 3015…

  • Page 115: Automatic Reset

    Parameters in the Long Parameter mode Index Name/Selection Description 2 = ALARM The drive generates alarm INPUT PHASE LOSS (code: A2026) when the DC ripple exceeds 14% of the nominal DC voltage. 3017 EARTH FAULT Selects how the drive reacts when an earth (ground) fault is detected in the 1 = ENABLE motor or the motor cable.

  • Page 116: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 0 = DISABLE Inactive 1 = ENABLE Active 3105 AR OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link 0 = DISABLE overvoltage fault. Automatically resets the fault (DC OVERVOLT, code: F0002) after the delay set by parameter 3103 DELAY TIME.

  • Page 117: Supervision

    Parameters in the Long Parameter mode Index Name/Selection Description 32 SUPERVISION Signal supervision. The drive monitors whether certain user selectable variables are within the user-defined limits. The user may set limits for speed, current etc. Supervision status can be monitored with relay output. See parameter group 14 RELAY OUTPUTS.

  • Page 118: Information

    E.g. 1.30b 3302 LP VERSION Displays the version of the loading package. Type dependent 0x2001…0x20FF 0x2021 = ACS150-0x (Eur GML) (hex) 3303 TEST DATE Displays the test date. 00.00 Date value in format YY.WW (year, week) Actual signals and parameters…

  • Page 119: Panel Display

    Parameters in the Long Parameter mode Index Name/Selection Description 3304 DRIVE RATING Displays the drive current and voltage ratings. 0x0000 0x0000…0xFFFF Value in format XXXY: (hex) XXX = Nominal current of the drive in Amperes. An “A” indicates decimal point. For example if XXX is 8A8, nominal current is 8.8 A. Y = Nominal voltage of the drive: 2 = 200…240 V 4 = 380…480 V…

  • Page 120: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3404 OUTPUT1 DSP Defines the format for the displayed signal selected by parameter 3401 9 = DIRECT FORM SIGNAL1 PARAM. 0 = +/-0 Signed/Unsigned value. Unit is selected by parameter 3405 OUTPUT 1 UNIT.

  • Page 121: Select

    Parameters in the Long Parameter mode Index Name/Selection Description 3408 SIGNAL2 PARAM Selects the second signal to be displayed on the control panel in display mode. See parameter 3401 SIGNAL1 PARAM. 0, 102…162 Parameter index in group 01 OPERATING DATA. E.g. 102 = 0101 SPEED.

  • Page 122: Start-Up Data

    Selects the application macro or activates FlashDrop parameter values. See 1 = ABB chapter Application macros. STANDARD 1 = ABB STANDARD Standard macro for constant speed applications 2 = 3-WIRE 3-wire macro for constant speed applications 3 = ALTERNATE Alternate macro for start forward and start reverse applications…

  • Page 123: Speed

    Parameters in the Long Parameter mode Index Name/Selection Description 9908 MOTOR NOM SPEED Defines the nominal motor speed. Must be equal to the value on the motor Type rating plate. dependent 50…30000 rpm Speed 9909 MOTOR NOM Defines the nominal motor power. Must equal the value on the motor rating POWER plate.

  • Page 124
    Actual signals and parameters…
  • Page 125: Fault Tracing

    An alarm or fault message on the panel display indicates abnormal drive status. Using the information given in this chapter most alarm and fault causes can be identified and corrected. If not, contact an ABB representative. How to reset The drive can be reset either by pressing the keypad key on the control panel, through digital input, or by switching the supply voltage off for a while.

  • Page 126: Alarm Messages Generated By The Drive

    Alarm messages generated by the drive CODE ALARM CAUSE WHAT TO DO OVERCURRENT Output current limit controller is Check motor load. A2001 active. (programmable Check acceleration time (2202 and 2205). fault function 1610) Check motor and motor cable (including phasing). Check ambient conditions.

  • Page 127
    Stop drive and change parameter value. A5023 Drive is executing task. Wait until task is completed. A5024 Value is at or below minimum limit. Contact your local ABB representative. A5026 Value is at or above maximum limit. Contact your local ABB representative. A5027 Invalid value Contact your local ABB representative.
  • Page 128: Fault Messages Generated By The Drive

    Fault messages generated by the drive CODE FAULT CAUSE WHAT TO DO OVERCURRENT Output current has exceeded trip Check motor load. F0001 level. Check acceleration time (2202 and 2205). Overcurrent trip limit for drive is Check motor and motor cable (including phasing). 325% of drive nominal current.

  • Page 129
    Check fault function parameter settings. equipment. fault function Check motor power against unit power. 3013…3015) THERM FAIL Drive internal fault. Thermistor Contact your local ABB representative. F0018 used for drive internal temperature measurement is open or short-circuited. CURR MEAS Drive internal fault. Current Contact your local ABB representative.
  • Page 130
    Fault tracing…
  • Page 131: Maintenance

    Fan failure can be predicted by the increasing noise from the fan bearings. If the drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are available from ABB. Do not use other than ABB specified spare parts.

  • Page 132: Fan Replacement (R1 And R2)

    For information on reforming the capacitors, refer to Guide for Capacitor Reforming in ACS50, ACS55, ACS150, ACS350, ACS550 and ACH550 [3AFE68735190 (English)], available on the internet (go to http://www.abb.com…

  • Page 133: Technical Data

    Current and power The current and power ratings are given below. The symbols are described below the table. Type Input Output Frame size ACS150- 2,1min/10min 2max x = E/U 1-phase U = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 0.37 01x-04A7-2 11.4…

  • Page 134: Symbols

    Symbols Input continuous rms input current Output continuous rms current. 50% overload is allowed for one minute every ten minutes. maximum (50% overload) current allowed for one minute every ten minutes 2,1min/10min maximum output current. Available for two seconds at start, otherwise as long as 2max allowed by the drive temperature.

  • Page 135: Cooling Air Flow Requirements

    The total heat dissipation is the sum of the heat dissipation in the main and control circuits. Type Heat dissipation Air flow ACS150- Main circuit Control circuit x = E/U Rated I…

  • Page 136: Power Cable Sizes And Fuses

    Power cable sizes and fuses Cable dimensioning for rated currents (I ) is shown in the table below together with the corresponding fuse types for short-circuit protection of the input power cable. The rated fuse currents given in the table are the maxima for the mentioned fuse types.

  • Page 137
    Note: Larger fuses must not be used. Type Fuses Size of CU conductor in cablings UL Class Supply Motor Brake ACS350- T (600 V) (U1, V1, W1) (U2, V2, W2) (BRK+ and BRK-) x = E/U 1-phase U = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 0.75 01x-04A7-2…
  • Page 138: Power Cables: Terminal Sizes, Maximum Cable Diameters And Tightening Torques

    Power cables: terminal sizes, maximum cable diameters and tightening torques Input power, motor cable and brake resistor terminal sizes, accepted cable diameters and tightening torques are given below. Frame U1, V1, V2, W2, BRK+ and BRK- size cable Terminal size Tightening Clamp capacity Tightening…

  • Page 139: Input Power Connection

    Input power connection Voltage (U 200/208/220/230/240 VAC 1-phase for 200 VAC drives 200/208/220/230/240 VAC 3-phase for 200 VAC drives 380/400/415/440/460/480 VAC 3-phase for 400 VAC drives Regular 10% variation from converter nominal voltage is allowed as default. Short-circuit capacity Maximum allowed prospective short-circuit current at the input power connection as defined in IEC 60439-1 is 100 kA.

  • Page 140: Control Connections

    The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1 and (IEC 61800-5-1, IEC 60439-1, UL 508C. For correct fuse selection, contact your local ABB representative. Rated UL 508C) conditional short-circuit current as defined in IEC 60439-1 and the Short-circuit test current by UL 508C is 100 kA.

  • Page 141: Ambient Conditions

    The DC capacitors contain electrolyte, which is classified as hazardous waste within the EU. They must be removed and handled according to local regulations. For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor. Technical data…

  • Page 142: Ce Marking

    Applicable standards The drive complies with the following standards: • IEC/EN 61800-5-1 (2003) Electrical, thermal and functional safety requirements for adjustable frequency a.c. power drives • IEC/EN 60204-1 (1997) + Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Amendment A1 (1999) Provisions for compliance: The final assembler of the machine is responsible for installing — an emergency-stop device…

  • Page 143: Ul Marking

    UL marking See the type designation label for the valid markings of your drive. UL checklist Input power connection – See section Input power connection on page 119. Disconnecting device (disconnecting means) – See section Supply disconnecting device page 23. Ambient conditions –…

  • Page 144: Compliance With The Iec/En 61800-3 (2004)

    First environment (drives of category C2) 1. The optional EMC filter is selected according to the ABB documentation and installed as specified in the EMC filter manual. 2. The motor and control cables are selected as specified in this manual.

  • Page 145: Brake Resistors

    Brake resistors ACS150 drives have an internal brake chopper as standard equipment. The brake resistor is selected using the table and equations presented in this section. Brake resistor selection 1. Determine the required maximum braking power P for the application. P…

  • Page 146: Resistor Installation And Wiring

    Type BRmax ACS150- 1-phase U = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 0.37 01x-04A7-2 0.75 01x-06A7-2 01x-07A5-2 01x-09A8-2 3-phase U = 200…240 V (200, 208, 220, 230, 240 V) 03x-02A4-2 0.37 03x-03A5-2 0.55 0.75 03x-04A7-2 0.75 03x-06A7-2…

  • Page 147: Mandatory Circuit Protection

    Below is a simple wiring diagram example. L1 L2 L3 Fuses Thermal switch of the resistor ACS150 U1 V1 W1 Parameter set-up To enable resistor braking, switch off the drive’s overvoltage control by setting parameter 2005 to 0 (DISABLE).

  • Page 148
    Technical data…
  • Page 149
    Dimensions Dimensional drawings of the ACS150 are shown below. The dimensions are given in millimeters and [inches]. Dimensions…
  • Page 150: Frame Sizes R0 And R1, Ip20 (Cabinet Installation) / Ul Open

    Frame sizes R0 and R1, IP20 (cabinet installation) / UL open R1 and R0 are identical except for the fan at the top of R1. Dimensions…

  • Page 151: Frame Sizes R0 And R1, Ip20 / Nema 1

    Frame sizes R0 and R1, IP20 / NEMA 1 R1 and R0 are identical except for the fan at the top of R1. Dimensions…

  • Page 152: Frame Size R2, Ip20 (Cabinet Installation) / Ul Open

    Frame size R2, IP20 (cabinet installation) / UL open Dimensions…

  • Page 153: Frame Size R2, Ip20 / Nema 1

    Frame size R2, IP20 / NEMA 1 Dimensions…

  • Page 154
    Dimensions…
  • Page 156
    WA4 4BT UNITED KINGDOM Telephone +44 1925 741111 +44 1925 741212 ABB Oy ABB Inc. ABB Beijing Drive Systems Co. Ltd. AC Drives Automation Technologies No. 1, Block D, A-10 Jiuxianqiao Beilu P.O. Box 184 Drives & Motors Chaoyang District…

This manual is also suitable for:

Acs350

ABB ACS150 User Manual

  1. Manuals
  2. Brands
  3. ABB Manuals
  4. Controller
  5. ACS150 series
  6. User manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

ACS150

User’s Manual

ACS150 Drives (0.37…4 kW, 0.5…5 HP)

QUOTE OR BUY ONLINE

www.inverterdrive.co.uk

loading

Related Manuals for ABB ACS150

Summary of Contents for ABB ACS150

  • Page 1
    ACS150 QUOTE OR BUY ONLINE www.inverterdrive.co.uk User’s Manual ACS150 Drives (0.37…4 kW, 0.5…5 HP)
  • Page 3
    ACS150 Drives 0.37…4 kW 0.5…5 HP User’s Manual 3AFE68576032 Rev A EFFECTIVE: 7.12.2005 © 2005 ABB Oy. All Rights Reserved.
  • Page 5: Safety

    Safety What this chapter contains The chapter contains the safety instructions which you must follow when installing, operating and servicing the drive. If ignored, physical injury or death may follow, or damage may occur to the drive, motor or driven equipment. Read the safety instructions before you work on the drive.

  • Page 6: Operation And Start-Up

    • The drive is not field repairable. Never attempt to repair a malfunctioning drive; contact your local ABB representative or Authorized Service Center for replacement. • Make sure that dust from drilling does not enter the drive during the installation.

  • Page 7: Table Of Contents

    Table of contents Safety What this chapter contains …………5 Use of warning symbols .

  • Page 8
    ABB Standard macro ……..
  • Page 9
    10 START/STOP/DIR …………69 11 REFERENCE SELECT .
  • Page 10
    Efficiency …………..115 Cooling .
  • Page 11: About The Manual

    It contains a flowchart of steps for checking the delivery and installing and commissioning the drive. The flowchart refers to chapters/sections in this manual. Compatibility The manual is compatible with the ACS150 drive firmware version 1.30b or later. See parameter 3301 FW VERSION.

  • Page 12: Installation And Commissioning Flowchart

    Installation and commissioning flowchart Task Identify the frame size of your drive: R0…R2. Technical data: Ratings on page Plan the installation: select the cables, etc. Planning electrical installation on page Check the ambient conditions, ratings and required Technical data on page cooling air flow.

  • Page 13: Hardware Description

    The chapter describes the construction and type code information in short. Overview The ACS150 is a wall or cabinet mountable drive for controlling AC motors. The construction of frame sizes R0…R2 varies to some extent. Without plates (R0 and R1)

  • Page 14: Overview: Connections And Switch

    Overview: Connections and switch The diagram shows the connections and switch of the ACS150. FlashDrop connection EMC filter grounding screw Varistor grounding screw Potentiometer AI type selection V / mA Relay output Analog input 250 VAC / 30 VDC 0(2)…+10 VDC or 0(4)…+20 mA…

  • Page 15: Type Code

    The type code contains information on the specifications and configuration of the drive. You find the type code on the type designation label attached to the drive. The first digits from the left express the basic configuration, for example ACS150-03E- 08A8-4. The explanations of the type code selections are described below.

  • Page 16
    Hardware description…
  • Page 17: Mechanical Installation

    Mechanical installation What this chapter contains The chapter describes the mechanical installation procedure of the drive. Unpacking the drive The drive (1) is delivered in a package that also contains the following items (frame size R0 shown in the figure): •…

  • Page 18: Before Installation

    Before installation The ACS150 may be installed on the wall or in a cabinet. Check the enclosure requirements for the need to use the NEMA 1 option in wall installations (see chapter Technical data).

  • Page 19: Mounting The Drive

    Free space around the drive The required free space for cooling above and below the drive is 75 mm (3 in.). No free space is required on the sides of the drive, so they can be mounted side by side. Mounting the drive Mount the drive Note: Make sure that dust from drilling does not enter the drive during the…

  • Page 20
    Fasten clamping plates 1. Fasten the clamping plate to the plate at the bottom of the drive with the provided screws. 2. Fasten the I/O clamping plate to the clamping plate with the provided screws. Mechanical installation…
  • Page 21: Planning Electrical Installation

    Note: The installation must always be designed and made according to applicable local laws and regulations. ABB does not assume any liability whatsoever for any installation which breaches the local laws and/or other regulations.

  • Page 22: Thermal Overload And Short-Circuit Protection

    Circuit breakers (To be defined) Circuit breakers which have been tested by ABB with the ACS150 can be used. Fuses must be used with other circuit breakers. Contact your local ABB representative for approved breaker types and supply network characteristics.

  • Page 23: Selecting The Power Cables

    Selecting the power cables General rules Dimension the input power and motor cables according to local regulations. • The cable must be able to carry the drive load current. See chapter Technical data for the rated currents. ° • The cable must be rated for at least 70 C maximum permissible temperature of the conductor in continuous use.

  • Page 24
    Motor cable shield To function as a protective conductor, the shield must have the same cross-sectional area as the phase conductors when they are made of the same metal. To effectively suppress radiated and conducted radio-frequency emissions, the shield conductivity must be at least 1/10 of the phase conductor conductivity. The requirements are easily met with a copper or aluminium shield.
  • Page 25: Protecting The Relay Output Contact And Attenuating Disturbances In Case Of Inductive Loads

    Residual current device (RCD) compatibility ACS150-01x drives are suitable to be used with residual current devices of Type A, ACS150-03x drives with residual current devices of Type B. For ACS150-03x drives, other measures for protection in case of direct or indirect contact, such as separation from the environment by double or reinforced insulation or isolation from the supply system by a transformer, can also be applied.

  • Page 26: Routing The Cables

    Never mix 24 VDC and 115/230 VAC signals in the same cable. Relay cable The cable type with braided metallic screen (e.g. ÖLFLEX by LAPPKABEL) has been tested and approved by ABB. Routing the cables Route the motor cable away from other cable routes. Motor cables of several drives can be run in parallel installed next to each other.

  • Page 27
    A diagram of the cable routing is shown below. Motor cable Drive min. 300 mm (12 in.) Power cable Input power cable Motor cable 90 ° min. 200 mm (8 in.) min. 500 mm (20 in.) Control cables Control cable ducts 24 V 230 V 24 V 230 V…
  • Page 28
    Planning electrical installation…
  • Page 29: Electrical Installation

    Electrical installation What this chapter contains The chapter describes the electrical installation procedure of the drive. WARNING! The work described in this chapter may only be carried out by a qualified electrician. Follow the instructions in chapter Safety on page 5. Ignoring the safety instructions can cause injury or death.

  • Page 30: Connecting The Power Cables

    Connecting the power cables Connection diagram Drive INPUT OUTPUT V1 W1 U2 V2 W2 BRK- BRK+ For alternatives, see section Supply Optional brake disconnecting device resistor on page 21. Motor Ground the other end of the PE conductor at the distribution board. Use a separate grounding cable if the conductivity of the cable shield is insufficient (smaller than the conductivity of the phase conductor) and there is no symmetrically constructed grounding conductor in the cable (see section Selecting the…

  • Page 31
    1. On IT (ungrounded) systems and corner grounded TN systems, disconnect the internal EMC filter by removing the screw at EMC. For 3-phase U-type drives (with type code ACS150-03U-), the screw at EMC is already removed at the factory and replaced by a plastic screw.
  • Page 32: Connecting The Control Cables

    Connecting the control cables I/O terminals The figure below shows the I/O connectors. X1A: 1: SCR X1B: 12: (RO)COM 2: AI(1) 13: (RO)NC 3: GND 14: (RO)NO 4: +24 V 1 2 3 4 5 6 7 8 9 10 11 12 13 14 5: GND 6: DCOM…

  • Page 33
    Procedure 1. Analog signal (if connected): Strip the outer insulation of the analog signal cable 360 degrees and ground the bare shield under the clamp. 2. Connect the conductors to the appropriate terminals. 3. Connect the grounding conductor of the used pair in the analog signal cable to the SCR terminal.
  • Page 34
    Electrical installation…
  • Page 35: Installation Checklist

    Installation checklist Checklist Check the mechanical and electrical installation of the drive before start-up. Go through the checklist below together with another person. Read chapter Safety the first pages of this manual before you work on the drive. Check MECHANICAL INSTALLATION The ambient operating conditions are allowed.

  • Page 36
    Installation checklist…
  • Page 37: Start-Up And Control With I/O

    ENTRY OF START-UP DATA Select the application macro (parameter 9902). 9902 The default value 1 (ABB STANDARD) is suitable in most cases. The general parameter setting procedure in the Short Parameter mode is described below. You find more detailed instructions on setting parameters on page 51.

  • Page 38
    7. Save the parameter value by pressing Enter the motor data from the motor nameplate: Note: Set the motor data to exactly the same value as on the motor nameplate. ABB Motors motor M2AA 200 MLA 4 IEC 200 M/L 55 Ins.cl. F…
  • Page 39
    Set constant speeds (drive output frequencies) 1, 2 and 3 1202 (parameters 1202, 1203 and 1204). 1203 1204 Set the minimum value (%) corresponding to the minimum 1301 signal for AI(1) (parameter 1301). Set the maximum limit for the drive output frequency 2008 (parameter 2008).
  • Page 40
    ACCELERATION/DECELERATION TIMES Set the acceleration time 1 (parameter 2202). 2202 Set the deceleration time 1 (parameter 2203). 2203 FINAL CHECK The start-up is now completed. Check that there are no faults or alarms shown in the display. The drive is now ready for use. Start-up and control with I/O…
  • Page 41: How To Control The Drive Through The I/O Interface

    Ensure that the control connections are wired according to the ABB Standard macro page 57. connection diagram given for the ABB Standard macro. Ensure that the drive is in remote control. Press key to switch In remote control, the panel display shows text REM.

  • Page 42
    Start-up and control with I/O…
  • Page 43: Control Panel

    The chapter describes the control panel keys and display fields. It also instructs in using the panel in control, monitoring and changing the settings. Integrated Control Panel The ACS150 works with the Integrated Control Panel, which provides basic tools for manual entry of parameter values. Control panel…

  • Page 44
    Overview The following table summarizes the key functions and displays on the Integrated Control Panel. No. Use LCD display – Divided into five areas: a. Upper left – Control location: LOC: drive control is local, that is, from the control panel REM: drive control is remote, such as the drive I/O.
  • Page 45
    The ACS150 includes an integrated potentiometer located at the front of the drive. It is used for setting the frequency reference. The Integrated Control Panel has six panel modes: Output, Reference, Short Parameter, Long Parameter, Changed Parameters and Fault.
  • Page 46
    How to do common tasks The table below lists common tasks, the mode in which you can perform them and the page number where the steps to do the task are described in detail. Task Mode Page How to switch between local and remote control How to start and stop the drive How to change the direction of the motor rotation How to set the frequency reference…
  • Page 47
    How to start, stop and switch between local and remote control You can start, stop and switch between local and remote control in any mode. To be able to start or stop the drive, the drive must be in local control. Step Action Display…
  • Page 48
    How to set the frequency reference You can set the local frequency reference with the integrated potentiometer in any mode when the drive is in local control if parameter 1109 LOC REF SOURCE has the default value 0 (POT). If parameter 1109 LOC REF SOURCE has been changed to 1 (KEYPAD), so that you can use keys…
  • Page 49
    Output mode In the Output mode, you can: • monitor actual values of up to three group 01 OPERATING DATA signals, one signal at a time • start, stop, change direction, switch between local and remote control and set the frequency reference.
  • Page 50
    Reference mode In the Reference mode, you can: • view and set the frequency reference • start, stop, change direction and switch between local and remote control. How to view and set the frequency reference You can set the local frequency reference with the integrated potentiometer in any mode when the drive is in local control if parameter 1109 LOC REF SOURCE has…
  • Page 51
    Parameter modes There are two parameter modes: Short Parameter mode and Long Parameter mode. Both function identically, except that the Short Parameter mode shows only the minimum number of parameters typically required to set up the drive (see section Parameters and signals in the Short Parameter mode on page 64).
  • Page 52
    Step Action Display Use keys to select the parameter value. When you have changed the parameter value, starts flashing. 1203 • To save the displayed parameter value, press • To cancel the new value and keep the original, press How to select the monitored signals Step Action Display…
  • Page 53
    Changed Parameters mode In the Changed Parameters mode, you can: • view a list of all parameters that have been changed from the macro default values • change these parameters • start, stop, change direction, switch between local and remote control and set the frequency reference.
  • Page 54
    Control panel…
  • Page 55: Application Macros

    Application macros are preprogrammed parameter sets. While starting up the drive, the user selects the macro best suited for the purpose with parameter 9902 APPLIC MACRO. The ACS150 has five application macros. The table below contains a summary of the macros and describes suitable applications. Macro Suitable applications ABB Standard Ordinary speed control applications where no, one, two or three constant speeds are used.

  • Page 56: Summary Of I/O Connections Of Application Macros

    Summary of I/O connections of application macros The following table gives the summary of the default I/O connections of all application macros. Macro Input/output Motor ABB Standard 3-wire Alternate Hand/Auto Potentiometer Frequency Frequency Frequency Frequency ref. reference reference reference (Auto)

  • Page 57: Abb Standard Macro

    ABB Standard macro This is the default macro. It provides a general purpose I/O configuration with three constant speeds. Parameter values are the default values given in chapter Actual signals and parameters, starting from page 63. If you use other than the default connections presented below, see section terminals on page 32.

  • Page 58: 3-Wire Macro

    3-wire macro This macro is used when the drive is controlled using momentary push-buttons. It provides three constant speeds. To enable the macro, set the value of parameter 9902 to 2 (3-WIRE). For the parameter default values, see section Default values with different macros on page 63.

  • Page 59: Alternate Macro

    Alternate macro This macro provides an I/O configuration adapted to a sequence of DI control signals used when alternating the rotation direction of the drive. To enable the macro, set the value of parameter 9902 to 3 (ALTERNATE). For the parameter default values, see section Default values with different macros on page 63.

  • Page 60: Motor Potentiometer Macro

    Motor Potentiometer macro This macro provides a cost-effective interface for PLCs that vary the speed of the drive using only digital signals. To enable the macro, set the value of parameter 9902 to 4 (MOTOR POT). For the parameter default values, see section Default values with different macros on page 63.

  • Page 61: Hand/Auto Macro

    Hand/Auto macro This macro can be used when switching between two external control devices is needed. To enable the macro, set the value of parameter 9902 to 5 (HAND/AUTO). For the parameter default values, see section Default values with different macros on page 63.

  • Page 62
    Application macros…
  • Page 63: Actual Signals And Parameters

    5 = DI5 0 = NOT SEL 5 = DI5 0 = NOT SEL 0 = NOT SEL 9902 APPLIC MACRO 1 = ABB STANDARD 2 = 3-WIRE 3 = ALTERNATE 4 = MOTOR POT 5 = HAND/AUTO Actual signals and parameters…

  • Page 64: Parameters And Signals In The Short Parameter Mode

    Selects the application macro or activates FlashDrop parameter values. See 1 = ABB chapter Application macros. STANDARD 1 = ABB STANDARD Standard macro for constant speed applications 2 = 3-WIRE 3-wire macro for constant speed applications 3 = ALTERNATE Alternate macro for start forward and start reverse applications…

  • Page 65: Fault History

    04 FAULT HISTORY Fault history (read-only) 0401 LAST FAULT Fault code of the latest fault. See chapter Fault tracing for the codes. 0 = fault history is clear (on panel display = NO RECORD). 11 REFERENCE Maximum reference SELECT 1105 REF1 MAX Defines the maximum value for external reference REF1.

  • Page 66: Limits

    20 LIMITS Maximum frequency 2008 MAXIMUM FREQ Defines the maximum limit for the drive output frequency. Eur: 50 / US: 60 2008 Allowed frequency range -(2008) 0.0…500.0 Hz Maximum frequency 21 START/STOP Stop mode of the motor 2102 STOP FUNCTION Selects the motor stop function.

  • Page 67: Parameters And Signals In The Long Parameter Mode

    Parameters and signals in the Long Parameter mode The following table includes the complete parameter and signal list, i.e. parameters and signals used in the Long Parameter mode. Name/Value Description 01 OPERATING DATA Basic signals for monitoring the drive (read-only). For actual signal supervision, see parameter group SUPERVISION.

  • Page 68
    Name/Value Description 0403 FAULT TIME 2 Time at which the latest fault occurred. Format: Time elapsed after power-on in 2 second ticks (minus the whole days stated by signal 0402 FAULT TIME 1). 30 ticks = 60 seconds. E.g. Value 514 equals 17 minutes and 8 seconds (= 514/30). 0404 SPEED AT FLT Motor speed in rpm at the time the latest fault occurred…
  • Page 69: Start/Stop/Dir

    Index Name/Selection Description 10 START/STOP/DIR The sources for external start, stop and direction control 1001 EXT1 COMMANDS Defines the connections and the source for the start, stop and direction 2 = DI1,2 commands for external control location 1 (EXT1). 0 = NOT SEL No start, stop and direction command source 1 = DI1 Start and stop through digital input DI1.

  • Page 70
    Index Name/Selection Description 1010 JOGGING SEL Defines the signal that activates the jogging function. The jogging function is 0 = NOT SEL typically used to control a cyclical movement of a machine section. One push button controls the drive through the whole cycle: When it is on, the drive starts, accelerates to a preset speed at a preset rate.
  • Page 71: Reference Select

    Index Name/Selection Description -1 = DI1(INV) Inverted digital input DI1. 1 = jogging inactive, 0 = jogging active. -2 = DI2(INV) See selection DI1(INV). -3 = DI3(INV) See selection DI1(INV). -4 = DI4(INV) See selection DI1(INV). -5 = DI5(INV) See selection DI1(INV). 11 REFERENCE Panel reference type, local reference source, external control location selection and external reference sources and limits…

  • Page 72
    Index Name/Selection Description 3 = AI1/JOYST Analog input AI1 as joystick. The minimum input signal runs the motor at the maximum reference in the reverse direction, the maximum input at the maximum reference in the forward direction. Minimum and maximum references are defined by parameters 1104 REF1 MIN and…
  • Page 73
    Index Name/Selection Description 1104 REF1 MIN Defines the minimum value for external reference REF1. Corresponds to the minimum setting of the used source signal. 0.0…500.0 Hz Minimum value. Example: Analog input AI1 is selected as the reference source (value of parameter 1103 REF1 SELECT is AI1).
  • Page 74: Constant Speeds

    Index Name/Selection Description 12 CONSTANT SPEEDS Constant speed selection and values. It is possible to define seven positive constant speeds. Constant speeds are selected with digital inputs. Constant speed activation overrides the external speed reference. Constant speed selections are ignored if drive is in local control mode.

  • Page 75
    Index Name/Selection Description -5 = DI5(INV) Speed defined by parameter 1206 CONST SPEED 5 is activated through inverted digital input DI5. 0 = active, 1 = inactive. -7 = DI1,2 (INV) Constant speed selection through inverted digital inputs DI1 and DI2. 1 = DI active, 0 = DI inactive.
  • Page 76: Analog Inputs

    Index Name/Selection Description 13 ANALOG INPUTS Analog input signal processing 1301 MINIMUM AI1 Defines the minimum %-value that corresponds to minimum mA/(V) signal for analog input AI1. When used as a reference, the value corresponds to the reference minimum setting. 0…20 mA 0…100% 4…20 mA…

  • Page 77: System Controls

    Index Name/Selection Description 8 = SUPRV 1 OVER Status according to supervision parameters 3201…3203. 9 = SUPRV 1 UNDER See selection SUPRV 1 OVER. 10 = SUPRV 2 OVER Status according to supervision parameters 3204…3206. 11 = SUPRV 2 UNDER See selection SUPRV 2 OVER. 12 = SUPRV 3 OVER Status according to supervision parameters 3207…3209.

  • Page 78
    Index Name/Selection Description 2 = DI2 See selection DI1. 3 = DI3 See selection DI1. 4 = DI4 See selection DI1. 5 = DI5 See selection DI1. -1 = DI1(INV) External signal required through inverted digital input DI1. 0 = Run Enable. If Run Enable signal is switched on, the drive will not start or coasts to stop if it is running.
  • Page 79: Freq Input

    FlashDrop Manual. FlashDrop parameter values are activated by setting parameter 9902 APPLIC MACRO to OEM SET LOAD. 0 = ABB STANDARD Complete long and short parameter lists 1 = OEM VIEW FlashDrop parameter list. Does not include short parameter list. Parameters which are hidden by the FlashDrop device are not visible.

  • Page 80: Limits

    Index Name/Selection Description 1803 FILTER FREQ IN Defines the filter time constant for frequency input, i.e the time within 63% of a step change is reached. 0.0…10.0 s Filter time constant 20 LIMITS Drive operation limits 2003 MAX CURRENT Defines the allowed maximum motor current. 1.8 ·…

  • Page 81: Start/Stop

    Index Name/Selection Description 21 START/STOP Start and stop modes of the motor 2101 START FUNCTION Selects the motor starting method. 1 = AUTO 1 = AUTO Frequency reference ramps immediately from 0 Hz. 2 = DC MAGN The drive pre-magnetises the motor with DC current before the start. The pre-magnetising time is defined by parameter 2103 DC MAGN TIME.

  • Page 82
    Index Name/Selection Description 2106 DC CURR REF Defines the DC braking current. See parameter 2104 DC HOLD CTL. 0…100% Value in percent of the motor nominal current (parameter 9906 MOTOR NOM CURR) 2107 DC BRAKE TIME Defines the DC braking time. 0.0…250.0 s Time 2108…
  • Page 83: Accel/Decel

    Index Name/Selection Description 2112 ZERO SPEED DELAY Defines the delay for the Zero Speed Delay function. The function is useful in applications where a smooth and quick restarting is essential. During the delay the drive knows accurately the rotor position. No Zero Speed Delay With Zero Speed Delay Speed…

  • Page 84
    Index Name/Selection Description 2202 ACCELER TIME 1 Defines the acceleration time 1 i.e. the time required for the speed to change from zero to the speed defined by parameter 2008 MAXIMUM FREQ. — If the speed reference increases faster than the set acceleration rate, the motor speed will follow the acceleration rate.
  • Page 85
    Index Name/Selection Description 2205 ACCELER TIME 2 Defines the acceleration time 2 i.e. the time required for the speed to change from zero to the speed defined by parameter 2008 MAXIMUM FREQ. See parameter 2202 ACCELER TIME 1. Acceleration time 2 is used also as jogging acceleration time. See parameter 1010 JOGGING SEL.
  • Page 86: Critical Speeds

    Index Name/Selection Description 25 CRITICAL SPEEDS Speed bands within which the drive is not allowed to operate. A Critical Speeds function is available for applications where it is necessary to avoid certain motor speeds or speed bands because of e.g. mechanical resonance problems.

  • Page 87
    Index Name/Selection Description 2603 IR COMP VOLT Defines the output voltage boost at zero speed (IR compensation). The Type function is useful in applications with high break-away torque. To prevent dependent overheating, set IR compensation voltage as low as possible. The figure below illustrates the IR compensation.
  • Page 88: Fault Functions

    Index Name/Selection Description 2608 SLIP COMP RATIO Defines the slip gain for the motor slip compensation control. 100% means full slip compensation, 0% means no slip compensation. Other values can be used if a static speed error is detected despite of the full slip compensation. Example: 35 Hz constant speed reference is given to the drive.

  • Page 89
    Index Name/Selection Description 3005 MOT THERM PROT Selects how the drive reacts when motor overtemperature is detected. 1 = FAULT The drive calculates the temperature of the motor on the basis of the following assumptions: 1) The motor is in the ambient temperature of 30°C when power is applied to the drive.
  • Page 90
    Index Name/Selection Description 3008 ZERO SPEED LOAD Defines the load curve together with parameters 3007 MOT LOAD CURVE 3009 BREAK POINT FREQ. 25.…150% Allowed continuous motor load at zero speed in percent of the nominal motor current 3009 BREAK POINT FREQ Defines the load curve together with parameters 3007 MOT LOAD CURVE…
  • Page 91
    Index Name/Selection Description 3012 STALL TIME Defines the time for the stall function. See parameter 3010 STALL FUNCTION. 10…400 s Time 3013 UNDERLOAD FUNC Selects how the drive reacts to underload. The protection wakes up if 0 = NOT SEL — the motor torque falls below the curve selected by parameter 3015 UNDERLOAD CURVE,…
  • Page 92: Automatic Reset

    Index Name/Selection Description 3017 EARTH FAULT Selects how the drive reacts when an earth (ground) fault is detected in the 1 = ENABLE motor or the motor cable. The protection is active only during start. An earth fault in the input power line does not activate the protection Note: Changing this parameter setting is not recommended.

  • Page 93
    Index Name/Selection Description 3105 AR OVERVOLTAGE Activates/deactivates the automatic reset for the intermediate link 0 = DISABLE overvoltage fault. Automatically resets the fault (DC OVERVOLT, code: F0002) after the delay set by parameter 3103 DELAY TIME. 0 = DISABLE Inactive 1 = ENABLE Active 3106…
  • Page 94: Supervision

    Index Name/Selection Description 32 SUPERVISION Signal supervision. The drive monitors whether certain user selectable variables are within the user-defined limits. The user may set limits for speed, current etc. Supervision status can be monitored with relay output. See parameter group 14 RELAY OUTPUTS.

  • Page 95: Information

    E.g. 1.30b 3302 LP VERSION Displays the version of the loading package. Type dependent 0x2001…0x20FF 0x2021 = ACS150-0x (Eur GML) (hex) 3303 TEST DATE Displays the test date. 00.00 Date value in format YY.WW (year, week) Actual signals and parameters…

  • Page 96: Panel Display

    Index Name/Selection Description 3304 DRIVE RATING Displays the drive current and voltage ratings. 0x0000 0x0000…0xFFFF Value in format XXXY: (hex) XXX = Nominal current of the drive in Amperes. An “A” indicates decimal point. For example if XXX is 8A8, nominal current is 8.8 A. Y = Nominal voltage of the drive: 2 = 200…240 V 4 = 380…480 V…

  • Page 97
    Index Name/Selection Description 3404 OUTPUT1 DSP Defines the format for the displayed signal selected by parameter 3401 9 = DIRECT FORM SIGNAL1 PARAM. 0 = +/-0 Signed/Unsigned value. Unit is selected by parameter 3405 OUTPUT 1 UNIT. 1 = +/-0.0 Example PI (3.14159): 2 = +/-0.00 3404 value…
  • Page 98
    Index Name/Selection Description 3408 SIGNAL2 PARAM Selects the second signal to be displayed on the control panel in display mode. See parameter 3401 SIGNAL1 PARAM. 0, 102…162 Parameter index in group 01 OPERATING DATA. E.g. 102 = 0102 SPEED. If value is set to 0, no signal is selected. If parameter 3401 SIGNAL1 PARAM,…
  • Page 99: Start-Up Data

    Selects the application macro or activates FlashDrop parameter values. See 1 = ABB chapter Application macros. STANDARD 1 = ABB STANDARD Standard macro for constant speed applications 2 = 3-WIRE 3-wire macro for constant speed applications 3 = ALTERNATE Alternate macro for start forward and start reverse applications…

  • Page 100
    Index Name/Selection Description 9908 MOTOR NOM SPEED Defines the nominal motor speed. Must be equal to the value on the motor Type rating plate. dependent 50…30000 rpm Speed 9909 MOTOR NOM Defines the nominal motor power. Must equal the value on the motor rating POWER plate.
  • Page 101: Fault Tracing

    An alarm or fault message on the panel display indicates abnormal drive status. Using the information given in this chapter most alarm and fault causes can be identified and corrected. If not, contact an ABB representative. How to reset The drive can be reset either by pressing the keypad key on the control panel, through digital input, or by switching the supply voltage off for a while.

  • Page 102: Alarm Messages Generated By The Drive

    Alarm messages generated by the drive CODE ALARM CAUSE WHAT TO DO OVERCURRENT Output current limit controller is Check motor load. A2001 active. (programmable Check acceleration time (2202 and 2205). fault function 1610) Check motor and motor cable (including phasing). Check ambient conditions.

  • Page 103
    Stop drive and change parameter value. A5023 Drive is executing task. Wait until task is completed. A5024 Value is at or below minimum limit. Contact your local ABB representative. A5026 Value is at or above maximum limit. Contact your local ABB representative. A5027 Invalid value Contact your local ABB representative.
  • Page 104: Fault Messages Generated By The Drive

    Fault messages generated by the drive CODE FAULT CAUSE WHAT TO DO OVERCURRENT Output current has exceeded trip Check motor load. F0001 level. Check acceleration time (2202 and 2205). Overcurrent trip limit for drive is Check motor and motor cable (including phasing). 325% of drive nominal current.

  • Page 105
    Check fault function parameter settings. equipment. fault function Check motor power against unit power. 3013…3015) THERM FAIL Drive internal fault. Thermistor Contact your local ABB representative. F0018 used for drive internal temperature measurement is open or short-circuited. CURR MEAS Drive internal fault. Current Contact your local ABB representative.
  • Page 106
    CODE FAULT CAUSE WHAT TO DO PAR HZRPM Incorrect speed/frequency limit Check parameter settings. Following must apply: F1000 parameter setting 2007 < 2008, 2007/9907 2008/9907 are within range. PAR AI SCALE Incorrect analog input AI signal Check parameter group 13 ANALOG INPUTS F1003 scaling settings.
  • Page 107: Maintenance

    Fan failure can be predicted by the increasing noise from the fan bearings. If the drive is operated in a critical part of a process, fan replacement is recommended once these symptoms start appearing. Replacement fans are available from ABB. Do not use other than ABB specified spare parts.

  • Page 108: Capacitors

    Fan replacement (R1 and R2) Only frame sizes R1 and R2 include a fan; frame size R0 has natural cooling. 1. Stop the drive and disconnect it from the AC power source. 2. Remove the hood if the drive has the NEMA 1 option. 3.

  • Page 109: Technical Data

    Current and power The current and power ratings are given below. The symbols are described below the table. Type Input Output Frame size ACS150- 2,1min/10min 2max x = E/U 1-phase U = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 0.37 01x-04A7-2 11.4…

  • Page 110
    Symbols Input continuous rms input current Output continuous rms current. 50% overload is allowed for one minute every ten minutes. maximum (50% overload) current allowed for one minute every ten minutes 2,1min/10min maximum output current. Available for two seconds at start, otherwise as long as 2max allowed by the drive temperature.
  • Page 111
    The total heat dissipation is the sum of the heat dissipation in the main and control circuits. Type Heat dissipation Air flow ACS150- Main circuit Control circuit x = E/U Rated I…
  • Page 112: Power Cable Sizes And Fuses

    Type Fuses Size of Cu conductor IEC (500 V) UL (600 V) U1, V1, W1, U2, BRK+ and BRK- ACS150- V2 and W2 x = E/U Type Type (IEC60269) 1-phase U = 200…240 V (200, 208, 220, 230, 240 V)

  • Page 113: Power Cables: Terminal Sizes, Maximum Cable Diameters And Tightening Torques

    Power cables: terminal sizes, maximum cable diameters and tightening torques Input power, motor cable and brake resistor terminal sizes, accepted cable diameters and tightening torques are given below. Frame U1, V1, W1, U2, V2, W2, BRK+ and BRK- size cable Terminal (flexible/rigid) Tightening Clamp capacity (solid or stranded) Tightening…

  • Page 114: Input Power Connection

    Input power connection Voltage (U 200/208/220/230/240 VAC 1-phase for 200 VAC drives 200/208/220/230/240 VAC 3-phase for 200 VAC drives 380/400/415/440/460/480 VAC 3-phase for 400 VAC drives ±10% variation from converter nominal voltage is allowed as default. Short-circuit capacity Maximum allowed prospective short-circuit current at the input power connection as defined in IEC 60439-1 is 100 kA.

  • Page 115: Control Connections

    The brake resistor output is conditionally short-circuit proof by IEC/EN 61800-5-1 and (IEC 61800-5-1, IEC 60439-1, UL 508C. For correct fuse selection, contact your local ABB representative. Rated UL 508C) conditional short-circuit current as defined in IEC 60439-1 and the Short-circuit test current by UL 508C is 100 kA.

  • Page 116: Ambient Conditions

    EU. They must be removed and handled according to local regulations. For further information on environmental aspects and more detailed recycling instructions, please contact your local ABB distributor. Technical data…

  • Page 117: Ce Marking

    Applicable standards The drive complies with the following standards: • IEC/EN 61800-5-1 (2003) Electrical, thermal and functional safety requirements for adjustable frequency a.c. power drives • IEC/EN 60204-1 (1997) + Safety of machinery. Electrical equipment of machines. Part 1: General requirements. Amendment A1 (1999) Provisions for compliance: The final assembler of the machine is responsible for installing — an emergency-stop device…

  • Page 118: Ul Marking

    UL marking See the type designation label for the valid markings of your drive. UL checklist Input power connection – See section Input power connection on page 114. Disconnecting device (disconnecting means) – See section Supply disconnecting device on page Ambient conditions –…

  • Page 119: Compliance With The Iec/En 61800-3 (2004)

    Compliance with the IEC/EN 61800-3 (2004) The immunity performance of the drive complies with the demands of IEC/EN 61800-3, second environment (see page for IEC/EN 61800-3 definitions). The emission limits of IEC/EN 61800-3 are complied with the provisions described below. First environment (drives of category C2) To be added later.

  • Page 120: Brake Resistors

    Brake resistors ACS150 drives have an internal brake chopper as standard equipment. The brake resistor is selected using the table and equations presented in this section. Brake resistor selection 1. Determine the required maximum braking power P for the application. P…

  • Page 121
    Type BRmax ACS150- 1-phase U = 200…240 V (200, 208, 220, 230, 240 V) 01x-02A4-2 0.37 01x-04A7-2 0.75 01x-06A7-2 01x-07A5-2 01x-09A8-2 3-phase U = 200…240 V (200, 208, 220, 230, 240 V) 03x-02A4-2 0.37 03x-03A5-2 0.55 0.75 03x-04A7-2 0.75 03x-06A7-2…
  • Page 122
    Below is a simple wiring diagram example. L1 L2 L3 Fuses Thermal switch of the resistor ACS150 U1 V1 W1 Parameter set-up To enable resistor braking, switch off the drive’s overvoltage control by setting parameter 2005 to 0 (DISABLE).
  • Page 123: Dimensions

    Dimensions Dimensional drawings of the ACS150 are shown below. The dimensions are given in millimeters and [inches]. Dimensions…

  • Page 124: Frame Sizes R0 And R1, Ip20 (Cabinet Installation) / Ul Open

    Frame sizes R0 and R1, IP20 (cabinet installation) / UL open R1 and R0 are identical except for the fan at the top of R1. Dimensions…

  • Page 125: Frame Sizes R0 And R1, Ip20 / Nema 1

    Frame sizes R0 and R1, IP20 / NEMA 1 R1 and R0 are identical except for the fan at the top of R1. Dimensions…

  • Page 126: Frame Size R2, Ip20 (Cabinet Installation) / Ul Open

    Frame size R2, IP20 (cabinet installation) / UL open Dimensions…

  • Page 127: Frame Size R2, Ip20 / Nema 1

    Frame size R2, IP20 / NEMA 1 Dimensions…

  • Page 128
    Dimensions…
  • Page 130
    ABB Oy ABB Inc. ABB Ltd AC Drives Automation Technologies Daresbury Park P.O. Box 184 Drives & Motors Daresbury FI-00381 HELSINKI 16250 West Glendale Drive Warrington FINLAND New Berlin, WI 53151 Cheshire Telephone +358 10 22 11 WA4 4BT +358 10 22 22681…

ABB

Компонентные электроприводы ABB ACS150, от 0,37 до 4 кВт / от 0,5 до 5 л.с. Технические характеристики.

Скачать
Pdf 232.54 Kb
Язык: RU

Понравилась статья? Поделить с друзьями:
  • Облепиховое масло таблетки инструкция по применению
  • Стрезам инструкция побочные действия отзывы врачей
  • Р 415 радиорелейная станция инструкция по эксплуатации
  • Уроцел мочеприемное устройство для мужчин инструкция по применению видео онлайн
  • Ceramic pro leather инструкция по применению