Информация
- О Нас
- Скачать каталоги
Интернет-Магазин Электрооборудования Вигор-Энерго. Работаем с 2008 года. Более 100 тысяч наименований. Заказать можно на сайте по выгодной цене с доставкой по России.
Данный веб-сайт носит исключительно информационный характер и ни при каких условиях не является публичной офертой, определяемой положениями Статьи 437 (часть 2) ГК РФ.
По всем возникающим вопросам звоните по телефону +7 (351) 776-93-51 в Челябинске
ИНН 7453194460, КПП 745301001, ОГРН 1087453003329
User manual for the Altistart 22 soft starter soft stop unit. This document includes the following topics: mounting, wiring diagrams, dimensions and weights, programming, configuration, maintenance information, diagnostics and troubleshooting, and Modbus information.
Date : 09/13/2015
Type : User guide
Languages : English
Version : 04
Document Number : BBV51330
Date : 09/13/2015
Type : User guide
Languages : English
Version : 04
Document Number : BBV51330
Завершен монтаж загрузки и…
Завершены монтаж и пуско-наладка автоматической системы загрузки и выгрузки фанеры в г.Киров на предприятии ООО «Вятский фанерный комбинат» входящем в ПАО…
Завершены работы по проектированию…
Нашей компанией завершены работы по проектированию и сборке Центрального Щита Управления предназначенного для управления работой технологического…
Идет пуско-наладка линии по…
Идет пуско-наладка линии по производству домов из клееного бруса в п.Приволжский р.Марий Эл.
Заводом был приобретен разукомплектованный швейцарский…
Command channel
Command channel: local or remote command
A command channel gives the possibility to command the motor by the soft starter (start, stop…).
it can also read or write parameters.
In local command mode, the Altistart 22 can be set from the display terminal:
• Use the 4 keys to enter into the menu.
In remote command, the Altistart 22 soft starter can be set from the remote keypad:
• The remote keypad can be used in a similar way than the embedded keypad, it means that the HMI on the remote keypad has the same behavior as the HMI on the product.
Note: Some command channels can also read or write parameters.
Priority stop
Soft starter command
Keypad or
PLC
Modbus
Active channel
CtrL configuration parameter
(CtrL = Modbus)
Forced local:
LI3= LIL or
Command word, bit 15 = 1
In this example, LI3 is configured to forced local command (LIL).
If CtrL = Modbus + forced local: it’s forced local in first.
LOCAL mode: The soft starter is entirely controlled via the terminals. The parameters can be read and written via Modbus. The soft starter remains in LOCAL mode as long as the
CtrL
=
0
.
FORCED LOCAL mode: The soft starter is entirely controlled via the terminals. Write access to the parameters from the Modbus link is prohibited. Reading is possible.
Note: LI1 must be activated (LI1 = 1) to allow the remote command.
A switch can be used on LI1 if a local stop by the terminal is needed. In this case, the stop will be in freewheel.
BBV51330 08/2012
65
Command channel
Behavior on channel change
In the COP menu (Advanced communication), the active channel can be changed via CtrL parameter:
Code
CtrL
Name Range
command channel 0: local command
1: Remote command: Modbus
Default value
0
CtrL
parameter is a configuration parameter that can be modified when the motor is stopped.
In the IO menu (Advanced IO), a Logic input can be assigned to local command: :
Code
LI2 or
LI3
Name
Logic input 2 or logic input 3
Value
LIL : Forced Local command
The local remote input is active at level 1.
When the input local remote is active, the active command channel is the local channel.
When the local force function is active from a Logic input, the parameters can only be written by the local HMI or the external keypad. If written by Modbus function 6 or 16, the exception 1 bad function is sent back.
When the local force function is active, Modbus command word and parameters can be written also by Modbus.
The Logic input assign to «Forced local command» has the priority on bit 15 from Modbus command word. If LI3 is assigned to LIL and
LI3=1, even if bit 15=1 the «Forced local command» is active.
When CTRL = Modbus and LI force local command activated, then a Modbus request 6 or 16 sends back an exception code 1 illegal function.
When on Modbus, only LI1 stop is taken into account.
Command word
The control register write definition is changed as follows: bit 9 bit 10 bit 11 bit 12 bit 13 bit 14 bit 15 bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7 bit 8
The Altistart 22 incorporates one control register intended for controlling the Altistart 22.
Address: The control register address is: 752.
In order to control the Altistart 22 using the control register:
• Use Function 16 or function 6
• Use Address_High (page) = 2
• Use Address_Low = 240 (0F0H)
• Write to one register only
• Set comm_control (CtrL) to 1 for Modbus
Bit
bit 0
Function
RUN/STOP
Comment
Write «1» (On) to RUN
Write «0» (oFF) to STOP, in configured stop (DEC parameter) reserved reserved trip reset reserved reserved reserved reserved reserved
Write «1» to reset reserved
Freewheel stop
2nd set of parameters reserved
Write «1» to set freewheel deceleration, linked with bit 0
Write «1» to enable second set of parameters reserved reserved
Forced local command Write «1» (On) forces local command
66
BBV51330 08/2012
Command channel
bit 1 bit 2 bit 3 bit 4 bit 5 bit 6 bit 7 bit 8 bit 9 bit 10 bit 11 bit 12 bit 13
Status word
The Status register address is: 256
• Use Function 3 only
• Use Address_High (page) = 1
• Use Address_Low = 0 (00H)
• Read one register only
Bit Function
bit 0 Ready
On
Trip
Warning
Reserved
LI3
LI2
LI1
Comment
All the conditions that will permit the operation of a switching device by the remote host controller have been fulfilled.
The main circuit contacts are closed or the semiconductor switches of semiconductor switching device are in the conducting state (ACC, DEC and BYPASS).
A trip condition exists.
A warning condition exists.
(Motor current in %)
The motor current is expressed as a percentage of the motor rated current.
Range is 0-200%.
6 bits code
200% = 63 (decimal) = 111111 (binary) bit 14 Local control bit 15 Ramping
The indication to a remote host controller that as a result of operator intervention, commands received will not be accepted or acted upon (forced local command).
Accelerating or decelerating the motor.
BBV51330 08/2012
67
Modbus Function
This section describes the connection to the bus or network, signaling, diagnostics, and configuration of the communication-specific parameters via the 7-segment LED display.
It also describes the communication services of the Modbus protocol.
Modbus Protocol
The transmission mode used is RTU mode. The frame contains no message header byte, nor end of message bytes.
It is defined as follows:
Slave address
Request code Data CRC16
The data is transmitted in binary code.
CRC16: cyclical redundancy check.
The end of the frame is detected on a silence greater than or equal to 3 characters.
Principle
The Modbus protocol is a master-slave protocol.
Master Only one device can transmit on the line at any time.
The master manages the exchanges and only it can take the initiative.
It interrogates each of the slaves in succession.
No slave can send a message unless it is invited to do so.
The master repeats the question when there is an incorrect exchange, and declares the interrogated slave absent if no response is received within a given time period.
If a slave does not understand a message, it sends an exception response to the master. The master may or may not repeat the request.
Slave i Slave j
Direct slave-to-slave communications are not possible.
Slave k
For slave-to-slave communication, the application software must therefore be designed to interrogate a slave and send back data received to the other slave.
Two types of dialogue are possible between master and slaves:
• the master sends a request to a slave and waits for its response
• the master sends a request to all slaves without waiting for a response (broadcasting principle)
Addresses
• The soft starter Modbus address can be configured from 1 to 247.
• Address 0 coded in a request sent by the master is reserved for broadcasting. ATS22 take account of the request, but do not respond to it.
Supported Modbus functions
The Altistart 22 supports the following Modbus functions.
Function name
Read holding registers
Write one output word
Write multiple registers
(Sub-function)
Read device Identification
Code
03
16#03
06
16#06
16
16#10
43
16#2B
Description
Read N output words
Write one output word
Write N output word
Read device identification
Remarks
Max PDU length : 63 words
Max PDU length : 61 words
68
BBV51330 08/2012
Modbus Function
The following paragraphs describes each supported function.
Read Holding registers
Request
Function code
Starting Address
Quantity of Registers
1 Byte
2 Bytes
2 Bytes
0x03
0x0000 to 0xFFFF
1 to 63 (0x 3F)
Response
Function code
Byte count
Register value
*N: Quantity of Registers
Error
Error code
Exception code
1 Byte
1 Byte
N* x 2 Bytes
0x03
2 x N*
1 Byte
1 Byte
0x83
01 or 02 or 03 or 04 (see details on page 72 )
Example
Note: Hi = high order byte, Lo = low order byte.
This function can be used to read all ATS22 words, both input words and output words.
Request
Slave no.
1 byte
03
1 byte
No. of first word
Hi Lo
2 bytes
Number of words
Hi Lo
2 bytes
Lo
CRC16
2 bytes
Hi
Response
Slave no.
1 byte
03
1 byte
Number of bytes read
1 byte
First word value
Hi Lo
2 bytes
——Last word value
Hi Lo
2 bytes
Lo
CRC16
2 bytes
Hi
Example: read 2 words ‘ACC and DEC at Modbus address 19 and 20 to W3105 (16#0013 to 16#0014) in slave 2, using function 3, where:
• ACC — Acceleration = 10
• DEC — Deceleration = 0
Request 02 03 0019 0002 CRC16
Response 02 03
Value of:
Parameters:
04 000A
W0019
ACC
0000
W020
DEC
CRC16
BBV51330 08/2012
69
Modbus Function
Write one output word
Request
Function code
Register Address
Register value
1 Byte
2 Bytes
2 Bytes
Response
Function code
Register Address
Register value
Error
Error code
Exception code
1 Byte
2 Bytes
2 Bytes
1 Byte
1 Byte
0x06
0x0000 to 0xFFFF
0x0000 to 0xFFFF
0x06
0x0000 to 0xFFFF
0x0000 to 0xFFFF
0x86
01 or 02 or 03 or 04 (see details on page 72 )
Example
Request and response (the frame format is identical)
06 Slave no.
1 byte 1 byte
Hi
Word number
Lo
2 bytes
Hi
Value of word
Lo
2 bytes
Example: write value 16#0008 in word W0022 (16#2329) in slave 2 Snb Number of starts 8.
Request and response 02 06 0016 0008 CRC16
Lo
CRC16
2 bytes
Hi
70
BBV51330 08/2012
Modbus Function
Read Device Identification
ID
0x00
0x01
0x02
Name / Description
VendorName
ProductCode
MajorMinorRevision
Type
ASCII String
ASCII String
ASCII String
Example
Default values to be detailed
Request
Slave no.
1 byte
2B
1 byte
Type of MEI
0E
1 byte
Response
Slave no.
1 byte
——-
2B
1 byte
Type of MEI
0E
1 byte
Number of additional frames
00
1 byte
ReadDeviceId
01
1 byte
Object Id
00
1 byte
Lo
CRC16
2 bytes
Hi
ReadDeviceId
01
1 byte
Degree of conformity
02
1 byte
Next object Id
00
1 byte
——-
Number of objects
03
1 byte
——-
————Id of object no. 1
00
1 byte
Length of object no. 1
12
1 byte
——Id of object no. 2
01
1 byte
——Id of object no. 3
02
1 byte
——-
Lo
1 byte
CRC16
Hi
1 byte
Length of object no. 2
0B
1 byte
Length of object no. 3
04
1 byte
Value of object no. 1
“Schneider Electric”
18 bytes
Value of object no. 2
“ATS22XXXXXX”
11 bytes
Value of object no. 3
“0201”
0 4 bytes
——-
——-
The total response size equals 49 bytes
The three objects contained in the response correspond to the following objects:
• Object no. 1:
• Object no. 2:
• Object no. 3:
Manufacturer name (always “Schneider Electric”, ie. 18 bytes).
Device reference (ASCII string; for example: “ATS22XXXXXX”, ie. 11 bytes).
Device version, in “MMmm” format where “MM” represents the determinant and “mm” the subdeterminant (4-bytes
ASCII string; for example: “0201” for version 2.1).
Note: The response to function 43 may be negative; in this case, the response located at the top of the next page is sent by the Altistart 22 rather than the response described above.
BBV51330 08/2012
71
Modbus Function
Error management
Exception responses
An exception response is returned by a slave when it is unable to perform the request which is addressed to it.
Format of an exception response:
Slave no.
1 byte
Response
code
1 byte
Error code
1 byte
Lo
CRC16
2 bytes
Hi
Response code: request function code + 16#80.
Error code:
1 = The function requested is not recognized by the slave
2 = The bit or word addresses indicated in the request do not exist in the slave
3 = The bit or word values indicated in the request are not permissible in the slave
4 = The slave has started to execute the request but cannot continue to process it completely
CRC16 calculation
The CRC16 is calculated on all the message bytes by applying the following method:
Initialize the CRC (16-bit register) to 16#FFFF.
Enter the first to the last byte of the message:
CRC
Enter
XOR
8 times
<byte> —> CRC
Move the CRC one bit to the right
If the output bit = 1, enter CRC XOR 16#A001—> CRC
End enter
End enter
The CRC obtained will be transmitted with the low order bytes sent first, followed by the high order ones (unlike the other data contained in
Modbus frames).
XOR = exclusive OR.
72
BBV51330 08/2012
Connection to RS485 bus
Standard schematic
The standard schematic corresponds to the Modbus specification published on the Modbus.org
site in 2002
(Modbus_over_serial_line_V1.pdf, Nov 2002) and in particular to the schematic of the 2-wire multidrop serial bus.
The ATS22 follows this specification.
Schematic diagram:
Master
Type of trunk cable
Maximum length of bus
Maximum number of stations (without repeater)
Maximum length of tap links
Bus polarisation
Line terminator
Common polarity
Slave 1 Slave n
Shielded cable with 1 twisted pair and at least a 3 rd
conductor
1000 m at 19200 bps with the Schneider Electric TSX CSA ppp
cable
32 stations, ie. 31 slaves
• 20 m for one tap link
• 40 m divided by the number of tap links on a multiple junction box
• One 450 to 650
:
pulldown resistor at 5 V (650
:
recommended)
• One 450 to 650
:
pulldown resistor at the Common (650
:
recommended)
This polarization is recommended for the master.
One 120
:
0.25 W resistor in series with a 1 nF 10 V capacitor
Yes (Common), connected to the protective ground at one or more points on the bus
BBV51330 08/2012
73
Maintenance
Servicing
It is advisable to perform the following actions regularly:
• Check the condition and tightness of connections.
• Ensure that the temperature around the unit remains at an acceptable level and that ventilation is effective (average service life of fans: 3 to 5 years depending on the operating conditions).
• Ensure proper fan operation.
• Remove any dust from the soft starter.
• Check physical damages to the soft starter.
Spare parts and repairs
Consult Schneider Electric products support.
74
BBV51330 08/2012
Diagnostics / Troubleshooting
Soft starter does not start, no trip code displayed
• No display:
— check that the line supply is present on the control supply CL1/CL2,
— check if a short circuit is not existing on the Modbus network cable (especially between RJ45 pin 7 and RJ45 pin3 or pin8. See pages 35 and 36 ).
• Check that the code displayed does not correspond to the normal state of the soft starter (see page 46 ).
• Check for the presence of the RUN/STOP commands (see page 37 ).
Soft starter does not start, trip code displayed
• Trip code flashes on the display.
• Storing of the last 7 trips, visible with SoMove software workshop.
• The soft starter locks and the motor stops with to freewheel mode.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Read and understand this manual before installing or operating the Altistart 22. Installation, adjustment, repair, and maintenance must be performed by qualified personnel.
• The user is responsible for compliance with all international and national electrical code requirements with respect to grounding of all equipment.
• Many parts of this soft starter, including the printed circuit boards, operate at the line voltage. DO NOT TOUCH. Use only electrically insulated tools.
• DO NOT touch unshielded components or terminal strip screw connections with voltage present.
• Before servicing the soft starter:
— Disconnect all power, including external control power that may be present.
— Place a “DO NOT TURN ON” label on all power disconnects.
— Lock all power disconnects in the open position.
• Install and close all covers before applying power or starting and stopping the soft starter.
Failure to follow these instructions will result in death or serious injury.
Trip code displayed
bPF
CFF
EtF
GrdF
InF
OCF
OHF
OLF
OSF
DtF
Name Remedy
Bypass contactor detected fault • Check for a welded bypass contactor or shorted SCR
• Replace it if necessary
Invalid configuration on power-up • Revert to the factory setting in the soft starter UtIL menu
• Reconfigure the soft starter
External detected fault • Clear the cause of the detected fault
Ground leakage current detected fault
Internal detected fault
• Check the electrical insulation of the motor
• Check the installation
• Check the values of Grdd , Grdt parameters in PrO menu page 57
• Disconnect and reconnect the control supply. If the detected fault persists, contact
Schneider Electric product support
Motor overcurrent
Over heat detected fault
Overload motor
• Check the values of OId and OIt parameters in PrO menu page 56
• Check the sizing of the soft starter in relation to the motor and the mechanical requirement
• Check the operation of the fan (if the Altistart 22 used has one), ensuring that the air passage is not obstructed in any way and the heatsink is clean. Ensure that the mounting recommendations are observed
• Wait for the Altistart 22 cooling before restarting
• Check the mechanism (wear, mechanical play, lubrication, blockages, etc.)
• Check the sizing of the soft starter motor in relation to the mechanical requirement
• Check the value of tHP parameter in SEt menu page 52 and In parameter in conF
menu page 50
• Wait for the motor to cool before restarting
Overvoltage
Motor Over Temperature
• Motor thermal trip detected by the PTC probes
• Check ULn parameter in conF menu
• Check the power supply circuit and voltage
• Check
OSd
and
OSt
parameters in
PrO
menu
• Check the mechanism (wear, mechanical play, lubrication, blockages, etc.)
• Check the sizing of the soft starter motor in relation to the mechanical requirement
• Check the value of PtC setting in PrO menu page 59
• Wait for the motor to cool before restarting
75
BBV51330 08/2012
Diagnostics / Troubleshooting
Trip code displayed
PHbd
PHF
PIF trAP
SCF
SLF
SnbF
SSCr
StF tbS
UCF
USF
Name Remedy
Phase unbalance
Loss of a line phase
Short circuit:
• short-circuit on soft starter output
Modbus Time Out
Too many starts
Shorted thyristor or wrong connection
Starting time detected fault
• Too long start time
Too many starts
Motor underload (undercurrent)
Under voltage or no voltage
• Check the line voltage.
• Check the values of
Ubd
,
Ubt
parameters in
PrO
menu page 57 .
• Check the line voltage, the connection to the soft starter and any isolating devices located between the line and the soft starter (contactors, fuses, circuit breakers, etc.).
• Check the motor connection and any isolating devices located between the soft starter and the motor (contactors, circuit breakers, etc.).
• Check the motor state.
• Check the line frequency.
• Check the configuration of PHL .
Line frequency, out of tolerance
This detected fault can be configured in
PrO
menu
Phase inversion
Line phase inversion does not conform to the selection made by
PHr
in
PrO
menu
Trap code
• Invert two lines phases or set
PHr
= oFF.
• Disconnect and reconnect the control supply. If the detected fault persists, contact
Schneider Electric support.
• Switch the soft starter off.
• Check the connecting cables and the motor insulation.
• Check the thyristors.
• Check the bypass contactor (contact stuck).
• Serial link detected fault. Check the RS485 connection.
• The number of soft starts has exceeded the maximum allowed by
Snb
in
SLG period. See Snb page 53 .
• Check the thyristors.
• Check the bypass contactor (contact stuck).
• Check the motor connections.
• Check the mechanism (wear, mechanical play, lubrication, blockages, etc.)
• Check that tLS (Max start time) is bigger than ACC (Acceleration time). See
SEt
menu page 51.
• Check the sizing of the soft starter motor in relation to the mechanical requirement
• Check ILt value : if the value is too low, the motor may not reach acceleration and full speed.
• Wait 5 minutes for frame size A.
• Wait 15 minutes for frame sizes B, C, D and E.
tbS
appears after
SnbF
trip message, when trying to reset the soft starter before end of the timer.
• Check the values of UId and UIt parameters in PrO menu page 57.
• Check
UIn
,
USd
and
USt
parameters in
PrO
menu
• Check line voltage.
Remote keypad messages
InIt
Display
COME
A-17
CLr dEUE rOME rAME
CPUE flashing flashing flashing flashing flashing flashing flashing
Message
On initializing itself
Communication interruption
Key alarm
Confirm trip reset
Description
Microcontroller initializing.
Communication configuration searching.
It has 50 ms time out.
This message is shown after 20 times retrying.
• Key has been held consecutively more than 10 seconds.
• Membrane switch disconnected.
• Keypad waked up while a key is holding.
This is shown when :
First time STOP key has been pressed while the soft starter has tripped in detected fault.
Soft starter mismatch Soft starter type (brand) did not match with keypad type (brand).
ROM trip Keypad ROM detected fault.
RAM trip
CPU trip
Keypad RAM detected fault.
Keypad CPU detected fault.
76
BBV51330 08/2012
Parameter Index and Modbus addresses
Code
ACC
52
ACC2
55
Add bSt
Page
62
53
Name
Acceleration time
2nd acceleration time
Modbus address
Boost time
Unit
Modbus code and
Adjustment
Range (1)
s
1
to
60 s
1
to
60
s
0 = oFF
1 to 247
0.0
to
1.0
Cod
CtrL dEC dEC2 dEF1 dEF2
50
62
52
55
63
63
Setting lock
Command channel
Deceleration time
2nd deceleration time
Trip history 1
Trip history 2
—
s s
—
—
0 = nLOC
1 =
LOC
0 = LCL
1 = dbS
0 = FrEE
1
to
60
0 =
FrEE
1
to
60
01 = UCF
02 = OCF
03 =
PHbd
04 =
GrdF dEF3 dEF4 dEF5 dEF6 dEF7 dEF8 dEF9 dEFt dICL dLtA
EdC
FAn
63
63
63
63
63
63
63
63
63
50
52
61
Trip history 3
Trip history 4
Trip history 5
Trip history 6
Trip history 7
Trip history 8
Trip history 9
Total number of trips
Trip current
Connection type
End of deceleration
Fan management
—
—
—
—
—
—
—
—
—
—
05 = OLF
06 = OtF
07 =
OHF
08 =
PIF
09 =
PHF
10 = USF
11 = OSF
12 =
StF
13 =
SnbF
14 =
SSCr
15 = EtF
16 = InF
17 =
SLF
18 = trAp
19 =
SCF
20 = bPF
21 = CFF
—
A
0 to 999
—
0 =
LInE
1 = dLt
0
to
10
0 =
AUto
1 = On
2 = oFF
3 =
HAnd
Description
—
off
Modbus address
1 with Modbus = 0.1s
not locked locked
0 – Local (LCL)
1 – Modbus (dbS) freewheel deceleration
freewheel deceleration
—
01 = Motor underload (undercurrent)
02 = Motor overcurrent
03 = Phase unbalance
04 = Ground leakage current detected fault
05 = Overload motor
06 = Motor Over Temperature
07 = Over heat detected fault
08 = Phase inversion
09 = Loss of a line phase
10 = Under voltage or no voltage
11 = Over Voltage
12 = Starting time detected fault
13 = Too Many Starts
14 = Shorted thyristor or wrong connection
15 = External detected fault
16 = Internal detected fault
17 = Modbus Time Out
18 = Trap code
19 = Short-circuit
20 = Bypass contactor detected fault
21 = Invalid configuration on power-up
—
in line connection inside delta connection
auto on off manual
FCS 64
Back to factory settings
—
1 = 1 to perform FCS
Modbus address
Factory setting
User setting
19
42
80
34
4
84
20
43
282
283
284
285
286
287
288
289
290
278
280
1
21
76
130
10
10 oFF
0 nLoc
LCL
FrEE
FrEE
—
—
—
—
—
—
—
—
—
—
—
LInE
0
AUto
—
(1) Modbus code = Soft starter message example : oFF on the soft starter will be equivalent to «0» with Modbus protocol (remote command)
* : parameter visible only with Modbus
BBV51330 08/2012
77
Parameter Index and Modbus addresses
Code
For
Freq*
Grdd
Grdt
Page
62
57
57
Name
Modbus format
Unit
—
Frequency
Ground leakage current threshold
Ground leakage current time delay
Hz
% of
In s
Modbus code and
Adjustment
Range (1)
0 =
8o1
1 =
8E1
2 = 8n1
3 = 8n2
—
10 to 100
101
= oFF
1 to 60
—
—
Off
—
Description
8 bit, odd parity, 1 stop bit
8 bit, even parity, 1 stop bit
8 bit, no parity, 1 stop bit
8 bit, no parity, 2 stop bit
Modbus address
82
265
54
55
Factory setting
8E1
—
25 for S6 and S6U
OFF for Q
5
IcL
IG*
ILt
ILt2
50
51
55
Soft starter rated current
A
—
Integral gain
%
0 to 100%
Current limit
2nd current limit
% of
In
% of
In
200 to 700% max. value:
350% of
IcL
200 to 700% max. value:
350% of IcL
Motor rated current
A
0.4 IcL to IcL
—
—
—
This parameter is reserved for expert mode.
Active when
SSC
=
On
0
38
17
41
Read from the power card’s serial
EEPROM
20
350
350
In 50
3
In2
55
2nd motor rated
Current
A
0.4
IcL
to
IcL
—
44
ItH
LAC
LED*
59
50
LCr1 47
LCr2 47
LCr3
47
Overload protection
Advanced mode
LCr1
LCr2
LCr3
LEDS Status
—
—
0 = oFF
1 = rUn
2 =
On off run on
0 = oFF
1 = On
Phase 1 Current, Amp off on
Phase 2 Current, Amp
Phase 3 Current, Amp d4: COMM LED (0=OFF,1=ON) d6: Ready LED (0=OFF,1=ON) d7: Run LED (0=OFF,1=ON). Flashing during soft start
/ soft stop.
d8: Trip LED (0=OFF,1=ON)
Note: other bits are reserved.
same as dEF1 to dEF9
63
269
279
5
257
258
259
LFt 63 Last trip
—
(1) Modbus code = Soft starter message example : oFF
on the soft starter will be equivalent to «0» with Modbus protocol (remote command)
* : parameter visible only with Modbus
According to the soft starter rating
According to the soft starter rating
On oFF
—
User setting
78
BBV51330 08/2012
Parameter Index and Modbus addresses
Code
LI*
LI2
LI3
Lo
OIt
OId
OSd
Page
60
60
47
57
56
59
Name
Logical inputs
Logic input 2
Logic input 3
Logic Output relays status
Overcurrent time delay
Overcurrent threshold
Over voltage threshold
Unit
—
s
% of In
% of
Uln
Modbus code and
Adjustment
Range (1)
Description
d0: Input 1. 0 – open, 1 – closed.
d1: Input 2.
d2: Input 3.
d3…d15: Reserved
0 =
Strt
1 = rUn
2 =
2nd
3 = EtF
4 = rSt
5 =
FAn
6 =
FI
7 =
LIL start:for a 3-wire control run:for a 2-wire control
2nd set of parameters external detected fault remote reset fan control trip inhibition forced local command
2 = 2nd
3 = EtF
4 = rSt
5 =
FAn
6 =
FI
7 = LIL
2nd set of parameters external detected fault remote reset fan control trip inhibition forced local command d0: Relay 1. 0 – not energized, 1 — energized d1: Relay 2 d2…d15: reserved
0 to 50 s
5 with Modbus = 0.5s
50 with Modbus = 5.0s
100 to 300, by increment of 5
110 to 125
—
—
OSt
58
Under voltage time delay s
1
to
10
—
PG*
PHL
PHr
PtC
58
57
59
Proportional gain
Phase loss detection
Phase sequence
PTC probes motor monitoring
%
—
—
—
0 to 100%
0 =
1 =
0 =
1 = oFF
On
123
1 = 321
2 = oFF
0 = oFF
On
123
321 off off on
This parameter is reserved for expert mode.
Active when
SSC
=
On off on
Modbus address
261
72
73
262
51
50
60
61
37
57
56
62
Factory setting
rUn rSt
0.5
200
120
2
60
On oFF oFF
(1) Modbus code = Soft starter message example : oFF on the soft starter will be equivalent to «0» with Modbus protocol (remote command)
* : parameter visible only with Modbus
User setting
BBV51330 08/2012
79
Parameter Index and Modbus addresses
Code
r1 r2 rnt rPr
SICL 63
SLG
Snb
SPCU
SSC
53
53
54
Stnb
63
StPr
63 t90 t92
Page
61
61
63
64
54
51
55
Name
Relay 1
Unit
Modbus code and
Adjustment
Range (1)
—
0 =
StPd
1 = nStP
2 = Strt
3 = rUn
4 = rdY
5 = trIp
6 =
ALr
as r1 hours
—
—
—
Relay 2
Total run time
Reset of trip history and counters
Last start maximum current
Starts period
Number of starts
Start-stop profile control voltage
Start-stop control
Total number of starts
Last starting time
Initial voltage
2nd initial voltage
A
0 to 999 min
1 to 60
—
1 to 10
11 = oFF
—
0
1
2
3
—
s
%
%
0 = oFF
1 =
On
—
0
to
999
10 to 50% of full voltage, by increment of 5
10 to 50% of full voltage
Uln
, by increment of 5
Description
stopped not stopped starting running ready trip alarm as r1
—
—
—
—
—
—
2
3
0
1
Number of starts off off on
—
—
(1) Modbus code = Soft starter message example : oFF on the soft starter will be equivalent to «0» with Modbus protocol (remote command)
* : parameter visible only with Modbus
Modbus address
74
75
273
NA
276
33
32
36
35
274
275
16
40
Factory setting
User setting
nStP trIP
—
—
—
30 oFF
0
On
—
—
30%
30%
80
BBV51330 08/2012
Parameter Index and Modbus addresses
Code
tbr tESt tHP tLS ttO
Ubd
Ubt
UdP
UId
Uln
UIt
USd
USt
Voltage*
Page
62
64
52
51
62
57
57
64
56
50
56
58
58
Name
Modbus baudrate
Soft starter self test
Motor thermal protection
Max start time
Modbus time out
Unbalance threshold
Unbalance time delay
Soft starter software version
Under current threshold
Line voltage
Under current time delay
Under voltage threshold
Under voltage time delay
Voltage
Unit
Kbps
—
s s
0 =
4
.8
1 =
9
.6
2 = 19 .2 on off
Modbus code and
Adjustment
Range (1)
1 =
10
2 =
20
3 = 30
1 to 250
1 = 0 .1 to
600 =
60
.0
—
% of
In s
101 = oFF
10 to 100%
1 to 60
—
0000
to
9999
—
—
—
% of
In
V
0 = oFF
20 to 90% of
In
Q range: 200 to 440
S6-S6U ranges: 200 to
600
—
—
Description
on off class 10 class 20 class 30 (heavy duty)
—
1 with Modbus = 0.1s
600 with
Modbus = 60.0s
Modbus address
81
NA
22
18
83
52
53
317
48
2
Factory setting
19.2
—
10
15
5.0
25
10 oFF
Q range: 400
S6-S6U ranges: 480
User setting
s
1 to 40
% of
In
50 to 90% of
Uln s
V
1
to
10
Line voltage, volts
—
—
—
49
58
59
260
10
70
5
(1) Modbus code = Soft starter message example : oFF
on the soft starter will be equivalent to «0» with Modbus protocol (remote command)
* : parameter visible only with Modbus
BBV51330 08/2012
81
Annex 1: UL508 schematics
ATS22
•••
Q or ATS22
•••
S6: 230 V, 2-wire control, freewheel stop
Z1
(1) Check the operating limits of the contact, for example when connecting to high rating contactors. See “Electrical characteristics” page 35 .
(2) Insert a voltage transformer if the power voltage is higher than the Altistart 22 acceptable value. Characteristics: min 100 VA page 13 .
2-wire control setting
In the menu Advanced I/O IO , set the following parameters:
Parameter Value
LI2 rUn r2 trlP
Description
Logic Input 2 is set to Run
Trip relay is de-energized upon trip
82
BBV51330 08/2012
Annex 1: UL508 schematics
ATS22
•••
S6U: 110V, 2-wire control, freewheel stop
Z1
(1) Check the operating limits of the contact, for example when connecting to high rating contactors. See “Electrical characteristics” page 36 .
(2) Insert a voltage transformer if the power voltage is higher than the Altistart 22 acceptable value. Characteristics: min 100 VA page 13 .
2-wire control setting
In the menu Advanced I/O IO , set the following parameters:
Parameter Value
LI2 rUn r2 trlP
Description
Logic Input 2 is set to Run
Trip relay is denergized upon trip
BBV51330 08/2012
83
84
BBV51330 08/2012
ATS22_User Manual_EN_BBV51330_02
BBV51330 08/2012
Altistart_22_ATS22D62Q.pdf
Наименование | Краткое описание | Карточка товара |
||
---|---|---|---|---|
ATS22D62Q (SCHNDR) | — | — |
Скачать документацию: Документация на ATS22D62Q (78.4 Кб)