Bc3250 spirax sarco инструкция на русском

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

4033452 / 8

BC3250

Blowdown Controller

Installation and Maintenance Instructions

BC3250

100

50

0

%

SP

PV

AL

OK

IM-P403-89

EMM Issue 8

1.

Safety information

2.

User instructions and

delivery information

3.

System overview

4.

Mechanical installation

5.

Electrical installation

6.

Commissioning

— Quick set-up

— Full

7.

Communications

8.

Maintenance

9.

Fault finding

10. Technical information

— Default settings

11. Appendix

— Summary of the

Modbus protocol

12. Menu map

© Copyright 2017

Printed in GB

Commissioning password

Current legislation states that in order to prevent tampering and potentially

hazardous programming errors, access to the pass codes required to enter

commissioning mode should only be available to qualified and trained personnel.

Enter commissioning

This is done from the run mode by pressing and holding down the

The bar graphs will disappear and the display will show ‘PASS

PASS

CODE’ with ‘8888’ at the bottom right corner of the screen. The

flashing leading digit indicates the position of the cursor. The

CODE

default, or factory set pass code is 7452 but this can be changed

from within the commissioning mode. The pass code can be

entered by using the

the flashing value and the

Pressing

will enter the pass code. If an incorrect pass code is

OK

used, the display automatically returns to the run mode.

8888

This page MUST be removed after

commissioning and kept in a safe,

access controlled location.

button for 5 seconds.

OK

and

buttons to increase or decrease

and

buttons to move the cursor.

IM-P405-89 EMM Issue 8

loading

Summary of Contents for Spirax Sarco BC3250

Контроллер продувки котла BC3250 Spirax Sarco

Контроллер продувки котла BC3250 Spirax Sarco

  • Описание

  • ЗАДАЙТЕ ВОПРОС ПРОДАВЦУ

Описание

Устройство BC3250 – это контроллер продувки для парогенераторов. Открывая и закрывая клапан
продувки, контролирует TDS (общее содержание растворенных в растворе солей) в воде. Кроме того,
контролирует дренажный клапан, который удаляет с днища котла растворенные соли.
Функция оборудования – контроль электрической проводимости жидкости вместе с датчиком
проводимости, дренажным клапаном днища или дренажным клапаном конденсата.
Дренажный клапан днища регулируется таймером.
Контроллер может быть установлен на панели, на DIN-рейке или непосредственно на специальной
монтажной раме, питание 99/264 Vca.
Передняя панель снабжена графическим LCD дисплем и клавиатурой из 5 кнопок.
В случаях, когда датчик установлен непосредственно на котле, можно дополнительно использовать
фильтр с целью увеличения эффекта угасания. Данная система поможет избежать слишком частого
срабатывания клапана в случае турбулентности.

ЗАДАЙТЕ ВОПРОС ПРОДАВЦУ

Table of Contents for Spirax Sarco BC3250:

  • IM-P403-89 EMM Issue 8 68 RETRANS – SET – 20 mA (Set PV to correspond to 20 mA) Ranges 0 – FSD Default FSD Resolution (steps) 0.1% FSD Units µS / cm or ppm COMMS – ADDRESS (MODBUS communication) Ranges 1 – 247 Default 1 COMMS – BAUD (MODBUS communication) Ranges 1200, 9600, 19200 Default 9600 COMMS – IR (Infrared communication) Ranges SLAVE or MASTER Default SLAVE

  • IM-P403-89 EMM Issue 8 62 10.6 Input technical data Water conductivity Probes type: CP10, CP30 and CP32 Ranges Minimum ≥ 1 µS @ 25 °C 0 – 9.99 ppm or µS / cm 0 – 99.9 ppm or µS / cm 0 – 999 ppm or µS / cm 0 – 9990 ppm or µS / cm Accuracy ±2.5% FSD (Poss > if high EMC) ±5% FSD for 0 — 9.999 range pH factor 0.50 – 1.00 (0.7 default) Neutralising factor 0.7 Resolution 0.1% FSD Drive ac – 4 wires Tempe

  • IM-P403-89 EMM Issue 8 10 2.6 Information line The information line will show ‘PPM’ or ‘US / CM’ and will alternate with information about alarms or the TDS / Bottom Blowdown Valve status. If an alarm occurs, the TDS / Bottom Blowdown Valve status will not show. ‘ALARM’ will be shown first followed by the type of alarm. See Section 9 – ‘Fault finding’ for types of errors. Example of alarm status: 7000 PPM 7000 ALARM 7000 HIGH TDS If a bottom or

  • IM-P403-89 EMM Issue 8 57 9.3 Operational error messages Any operational errors that occur will be displayed in the run mode, on the alarms and errors screen. Error message Cause Action 1 Powerout There has been a loss of power to the product during operation. 1. Remove power from product. 2. Check that all wiring is correct. Power fail. 3. Check that the power supply is secure, i.e. does not suffer from ‘brown outs’ 4. Reapply power. 5. Press OK to Clear. 2 SETUP MENU TIME OUT The operator has entered the commissioning mo

  • IM-P403-89 EMM Issue 8 51 TEST INPUT INT TEMP TEST INPUT RESIST TEST INPUT OP TEMP TEST INPUT PROBE F TEST INPUT SWITCH TEST INPUT BURNER Displays the internal temperature of the microcontroller. Displays the calculated water resistance in ohms, Kohms or Mohms. Not visible if no Pt100 is fitted. Displays the equivalent operating temperature, measured by the Pt100 (if connected). Displays the equivalent calculated Cell or Probe Factor, indicating the condition of the probe. Shows if the bottom blowdown switch is OPEN or CLOSED (if connected).

  • IM-P403-89 EMM Issue 8 41 6.4.4 INPUT menu Allows selection of the type of measurement to be performed. INPUT T COMP INPUT TDS Temperature compensation. If no Pt100 is fitted, a constant temperature can be entered. e.g. 184 °C (default). Allows selection of all the TDS control features: Sensor type, purge, filter, range, set point, hysteresis, calibration, and calibration interval. 6.4.5 INPUT – TDS sub-menu INPUT TDS SENSOR INPUT TDS PURGE INPUT TDS FILTER I

  • IM-P403-89 EMM Issue 8 16 3.3.2 Purge output Used only when the probe is mounted in the blowdown line, Purge ensures the sensor measures the conductivity at boiler temperature. The purge duration time is the time the valve is open to enable a representative boiler sample to reach the probe. A purge occurs every PURGE — INTERVAL time either independent of burner firing, or dependent on cumulative boiler firing time. Fig. 7 Output with purge time set (>0s) 3.3 Outputs 3.3.1

  • IM-P403-89 EMM Issue 8 38 6.3 Commissioning — Quick set-up This section allows the user to carry out the minimum commissioning necessary to operate the system. It accepts the defaults set in the factory, so will only work if the original default settings have not been altered. See the default settings in Section 10, Technical information, to confirm. Settings can then be tailored to suit the individual requirements of the customer / application if required. Warning: — It is essential that you comply with

  • IM-P403-89 EMM Issue 8 54 8. Maintenance Note: Read the ‘Safety information’ in Section 1 before starting any maintenance. No special servicing, preventative maintenance or inspection of the product is required. During installation or maintenance, the rear of the product must be protected from environmental pollutants entering the product. Alternatively, the tasks can be performed in a dry clean environment. 8.1 Cleaning instructions Use a cloth dampened with tap / de-ionised water or isopropyl alcohol. Use of other

  • IM-P403-89 EMM Issue 8 15 3. System overview 3.1 Function The controller has an adjustable alarm and set point levels. The product can be configured to control TDS / conductivity of water. Once fully commissioned, the TDS value is displayed in μS / cm (or ppm if selected). Note: Conductivity is expressed in parts per million (ppm) or micro Siemens per centimetre (µS / cm). Micro Siemens / centimetre is becoming the more common unit, and is therefore the default setting. If the water conductivity exce

  • IM-P403-89 EMM Issue 8 58 Error message Cause Action 5 VALVE FAILED TO CLOSE Blowdown valve fails to close fully 1. Check the correct closing time has been entered in the INPUT — CLOSING menu. 2. See VALVE FAILED TO OPEN. 3. Enter the commissioning mode and enter the correct passcode.* 4. Press OK to Clear. 6 PROBE SCALED (CP32 Only) The probe drive has increased to the maximum voltage. 1. The probe tip may be scaled. Ensure the correct water treatment is be used. 2. Ensure the boiler water is not been contaminated. 3. Check the probe wiring. 4. I

  • OK BC3250 100 50 0 % SP PV AL 1. Safety information 2. User instructions and delivery information 3. System overview 4. Mechanical installation 5. Electrical installation 6. Commissioning — Quick set-up — Full 7. Communications 8. Maintenance 9. Fault nding 10. Technical information — Default settings 11. Appendix — Summary of the Modbus protocol 12. Menu map IM-P405-89 EMM Issue 8 Commissioning password Current legislation states that in order to prevent tampering and potentially hazardous progr

  • IM-P403-89 EMM Issue 8 9 PV AL PV Fig. 3 PV (conductivity) bar graph definitions Fig. 4 SP and alarm bar graph definitions Highest process variable reached This can be reset by entering the commissioning mode. Lowest process variable This can be reset by entering the commissioning mode. Current process variable Graphical representation of the process variable in terms of percentage of full scale. High alarm Set Point (T

  • IM-P403-89 EMM Issue 8 20 Optional OK BC3250 100 50 0 % SP PV AL Fig. 13 CCD system Dump valve (spring- to-open). Opens when conductivity level is above set point allowing contaminated condensate to flow to drain. Isolating valve (spring-to-close) opens to allow clean condensate to be returned to the boiler. Fig. 14 Alternative arrangement of a CCD system using separate valves Spring retract pneumatic actuator QL 3-port diverter valve Check va

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of Spirax Sarco BC3250 device using right now.

Special functions in run mode

Purge

Manually opens the blowdown valve for the purge time set during commissioning. If the purge

time has been set to zero,· the valve will open for 1 minute.

Using the ‘

‘ or ‘

‘ buttons, select ‘PURGE’.

Pressing the ‘

‘ or ‘

‘ opens the blowdown valve for the purge time or 1 minute.

The display will return to the process variable run menu.

‘BLOWDOWN-PURGE’ or ‘BLOWDOWN-TDS TEST’ will appear on the information line

during this period.

On completion of the purge time, the controller will revert to normal control.

Cleaning

Activates a probe cleaning cycle for the period of time set during commissioning.

Using the ‘

‘ or ‘

‘ buttons, select ‘CLEAN’.

Pressing the ‘

‘ or ‘

‘ to active the cleaning cycle and the blowdown valve will close.

The display will return to the process variable run menu.

‘CLEANING’ will appear on the information line during this period.

On completion of the cleaning time, the controller will revert to normal control after 20

seconds. This is to allow any bubbles to disperse.

CAL

Enables the water treatment engineer / specialist to calibrate the controller from the run

menu. A pass code is not required.

Using the ‘

‘ or ‘

‘ buttons, select ‘CAL’.

Pressing the ‘

‘ or ‘

‘ will access the calibration menu in commission mode. See Section

6.4.6.5 INPUT-TDS-CAL.

On completion or exiting calibration, the display will return to the process variable run

menu and normal control will be resumed.

This page MUST be removed after

commissioning and kept in a safe,

access controlled location.

IM-P405-89 EMM Issue 8

1. Safety information

Safe operation of this product can only be guaranteed if it is properly installed,

commissioned, used and maintained by qualified personnel (see Section 1.11) in

compliance with the operating instructions. General installation and safety instructions

for pipeline and plant construction, as well as the proper use of tools and safety

equipment must also be complied with.

Your attention is drawn to IEE Regulations (BS 7671, EN 12953, EN 12952 and

EN 50156). Elsewhere, other regulations will normally apply.

All wiring materials and methods shall comply with relevant EN and IEC standards

where applicable.

Warning

This product is designed and constructed to withstand the forces encountered during

normal use. Use of the product other than as a boiler controller, or failure to install the

product in accordance with these Instructions, product modifications or repair could:

Cause injury or fatality to personnel.

Cause damage to the product / property.

Invalidate the

marking.

These instructions must be stored in a safe place near the product installation at

all times.

Warning

This product complies with Electromagnetic Compatibility Directive 2014/30/EU and

all its requirements.

This product is suitable for Class A Environments (e.g. industrial). A fully detailed EMC

assessment has been made and has the reference number UK Supply BH BC3250 2008.

The product may be exposed to interference above the limits of Heavy Industrial

Immunity if:

The product or its wiring is located near a radio transmitter.

Excessive electrical noise occurs on the mains supply. Power line protectors

(ac) should be installed if mains supply noise is likely. Protectors can combine

filtering, suppression, surge and spike arrestors.

Cellular telephones and mobile radios may cause interference if used within

approximately 1 metre (39″) of the product or its wiring. The actual separation

distance necessary will vary according to the surroundings of the installation

and the power of the transmitter.

This product complies with Low Voltage Directive 2014/35/EU by meeting the

standards of:

EN 61010-1:2010 Safety requirements for electrical equipment for measurement,

control, and laboratory use.

Static precautions (ESD)

Static precautions must be observed at all times to avoid damage to the product.

2

IM-P405-89 EMM Issue 8

e-mail: info@oep.by

tel: +375 33 648-55-51

tel: +375 29 825-55-51

tel: +375 29 865-55-51

e-mail: info@oep.by

tel: +375 33 648-55-51

  • ГЛАВНАЯ
  • КАТАЛОГ ТОВАРОВ
    • КОТЛЫ
    • ГОРЕЛКИ
    • ЗАПАСНЫЕ ЧАСТИ ДЛЯ ГОРЕЛОК
      • Топочные автоматы
      • Газовые фильтры
      • Датчики контроля пламени
      • Кабели поджига
      • Реле давления
      • Сервоприводы
      • Форсунки для горелок
      • Электроды поджига
      • Трансформаторы поджига
      • Жидкотопливные насосы
      • Газовые клапана
      • Трансформаторы поджига
      • Антивибрационные муфты
      • Электродвигатели
      • Регуляторы давления
      • Электрокомпоненты
      • Фланцы и прокладки
      • Жидкотопливные компоненты
      • Вентиляторы горелок
      • Жаровые трубы
      • Уравнительные диски
    • ЗАПАСНЫЕ ЧАСТИ ДЛЯ КОТЛОВ
    • ТРУБОПРОВОДНАЯ АРМАТУРА
    • ТЕПЛООБМЕННОЕ ОБОРУДОВАНИЕ
    • ЭЛКТРОТЕХНИЧЕСКАЯ ПРОДУКЦИЯ
    • ОБОРУДОВАНИЕ SIEMENS
    • СВЕТОТЕХНИЧЕСКАЯ ПРОДУКЦИЯ
  • НАШИ УСЛУГИ
    • Техническое обслуживание
    • Пусконаладочные работы котельных
    • Режимно-наладочные испытания
    • Техническое обслуживание ГРП, ГРУ, ШРП
    • Техническое обслуживание систем водоочистки
    • Водно-химический режим котлов
    • Пусконаладочные работы водоподготовительных установок
    • Автоматизация котельных
    • Внутренняя чистка котлов по газо-воздушному тракту
    • Техническое обслуживание и наладка зерносушильных комплексов
    • Сервисное обслуживание и ремонт горелок
  • ДОСТАВКА И ОПЛАТА
  • КОНТАКТЫ

ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ

  • Напряжение: 99 — 264 V
  • Потребляемая мощность: 7,5 Вт
  • Описание
  • ДОСТАВКА И ОПЛАТА

Описание

BC3250 является регулятором продувки паровых котлов. Он контролирует (общее количество растворенных твердых веществ — солей в растворе) по открытию и закрытие клапана продувки.
Продукт работает в сочетании с датчиком проводимости, клапаном продувки котла, клапаном сброса давления и для обнаружения конденсата загрязнения.

МАРКИРОВКИ

  • Spirax Sarco BC3250

Оплата производится в безналичной форме путем перечисления денежных средств на расчетный счет поставщика. Способы доставки: — Самовывоз, со склада поставщика по адресу г. Минск ул. Скрипникова д. 35, пом. 143
— Доставка транспортной компанией в любую точку Беларуси.

Похожие товары

ПОПУЛЯРНЫЕ ТОВАРЫ

ООО «ОПТЭНЕРГОПРОМ»

Поставка комплектующих к отопительному оборудования, техническое обслуживание и пусконаладочные работы

СОЦИАЛЬНЫЕ СЕТИ

Понравилась статья? Поделить с друзьями:
  • Как собрать прыгунки с пружиной инструкция по применению
  • Скачать мануалы для ремонта авто
  • Инструкция по работе с крипто про
  • Нурофен для детей суппозитории ректальные инструкция
  • Свечи лонгидаза инструкция по применению для женщин в гинекологии отзывы