ENDA ETC4420 PID TEMPERATURE CONTROLLER

Thank you for choosing ENDA ETC4420 temperature controller.

* 48 x 48mm sized.

* Selectable sensor type.

*

Automatic calculation of PID parameters (SELF TUNE).

Enter PID parameters of the system if they are known at the beginning.

Otherwise, Self-Tune should be activated.

* Soft-Start.

* Communication vai RS-485 ModBus protocol (Optional).

* Selectable SSR or relay control output.

* Relay output can be programmable as second alarm or control output.

* AL1 relay output for first alarm out.

* Selectable Heat/Cool control.

* Input offset feature.

* In the case of sensor failure

selected.

*

Parameter access protection on 3 levels.

*

Programming by using keypad or Modbus.

*

CE marked according to European Norms.

TECHNICAL SPECIFICATIONS

Input type

Pt 100 Resistance Thermometer

Pt 100 Resistance Thermometer

J (Fe-CuNi) Thermocouple

K (NiCr-Ni) Thermocouple

T (Cu-CuNi) Thermocouple

S (Pt/0Rh-Pt) Thermocouple

R (Pt13Rh-Pt) Thermocouple

ENVIRONMENTAL CONDITIONS

Ambient/storage temperature

0 … +50

Max. Relative humidity

80

According to EN 60529

Rated pollution degree

Height

Max. 2000m

Do not use the device in locations subject to corrosive and flammable gases.

ELECTRICAL CHARACTERISTICS

Supply

230V AC +10

Power consumption

Max. 5VA

Wiring

2.5mm² screw-terminal connections

Line resistance

For thermocouple max.100ohm, for 3 wired Pt 100 max. 20ohm

Data retention

EEPROM (minimum 10 years)

EMC

EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B for standard EN 61000-4-3)

Safety requirements

EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)

OUTPUTS

CONT./AL2

Relay : 250V AC, 2A ( for resistive load), NO/NC.

AL1

Relay : 250V AC, 2A ( for resistive load), NO/NC selectable.

SSR out

Selectable logic control output. (Max 12V 20mA(

Life expectancy for relay

Mechanical 30.000.000 operation; Electrical 300.000 operation

CONTROL

Control type

Single set-point and alarm control

Control algorithm

On-Off / P, PI, PD, PID (selectable)

A/D converter

15 bits

Sampling time

500ms

Proportional band

Adjustable between 0

Adjustable between 0.0 and 100.0 minutes

Integral time

Derivative time

Adjustable between 0.00 and 25.00 minutes

Control period

Adjustable between 1

Hysteresis

Adjustable between

Output power

The ratio of power at a set point can be adjusted between 0

HOUSING

Housing type

Suitable for flush-panel mounting according to DIN 43 700.

Dimensions

W48xH48xD87mm

Weight

Approx. 250g (after packing)

Self extinguishing plastics.

Enclosure material

While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.

periodical running or

relay state can be

Temperature range

°C

EN 60751

-200…600

°C

EN 60751

-99.9…300.0

°C

EN 60584

0… 600

°C

0…1200

EN 60584

°C

0… 400

°C

EN 60584

EN 60584

0…1600

°C

EN 60584

0…1600

°C

°C -25… +70°C (with no icing)

/

%

up to 31

°C

decreasing linearly 50

Front panel :

Rear panel :

%

-20 , 50/60Hz or 24V AC ±10 , 50/60Hz.

%

%

and 100 . If Pb=0 , On-Off control is selected.

%

and 250 seconds

1 and 50

°C/F

1/4

ETC 4420

CNT/AL2

SSR

AL1

SET

CSET

ENDA

Accuracy

°F

0,2% (

of full scale

-328… +1112

°F

0,2% (

of full scale

-99.9…+543.0

°F

+32… +1112

°F

0,2% (

of full scale

0,2% (

of full scale

+32… +2192

°F

+32… +752

°F

0,2% (

of full scale

+32… +2912

°F

0,2% (

of full scale

0,2% (

of full scale

+32… +2912

°F

%

at 40

°C

.

IP65

IP20

%

Selectable as Control or Alarm2 output.

(Alarm1 output).

%

%

and 100

%

PV

SV

ASET

TEMPERATURE CONTROLLER

)

1 digit

)

1 digit

)

1 digit

)

1 digit

)

1 digit

)

1 digit

)

1 digit

ETC4420-E-02-R

Рейтинг 5.00 из 5 на основе опроса 1 пользователя

(1 отзыв клиента)

Доступность: Уточняйте

7 540


Терморегулятор одноканальный ETC4420-230, вход: ХА(К), ЖК(J), T, S, R, Pt100, выход: реле + SSR, аварийный выход, 48х48мм

Уточняйте


  • Описание

  • |

  • Отзывы (1)

  • |

Общепромышленный контроллер с PID регулятором.

  • Размер: Ш48xВ48мм
  • Питание: 240 VAC
  • Программируемый вход выбора термодатчика: ХА(К), ЖК(J), T, S, R, Pt100
  • Тип выхода: релейный 2А 250VAC + SSR 12VDC 20mA
  • Релейный аварийный выход
  • Двойной экран: одновременное отображение уставки и температуры процесса
  • Дискретный вход
  • Автонастройка PID
  • Защита передней панели IP65
  • Рабочая температура: 0..+50

Термоконтроллер ET4420. Инструкция по эксплуатации

=

Band Alarm With Inhibition

A1tP. bAn.i.

ON

ON

OFF

OFF

Begining

of procedure

SV = et

i

ASV =
(ASV min. = 0, ASV ma . = 300 )

S

point of CONT output

Set point of AL1 output

x

Band alarm is possible

Band alarm is possible

Begining

of procedure

SV

SV

SV+ASV

SV+ASV

SV-ASV

SV-ASV

230V

AC

or 24V

Supply

Cable size: 1,5mm²

Holding screw
0.4-0.5Nm

Equipment is protected throughout
by DOUBLE INSULATION

Switch

Fuse

F 100 mA 250V AC

N

L

Fuse should
be connected

ALARM1 AND ALARM2 OUTPUT TYPES

CONNECTION DIAGRAM

J-K-T-S-R t

t ermo

upl :

For

ype h

co

e

Use suitable compensation cables. Don’t use
jointed cables. Pay attention to the polarities
of the thermocouple cables as shown in the

figure right are connected to the.

For r s

ce h

e

e istan

t ermomet r :

When 2 wired Pt 100 is used, terminals that are
shown at the right of there must be short
circuited for each product.

184-253V AC
50/60Hz 7VA

SUPPLY :

SENS

:

OR INPUT

NOT :

E

ETC9420

ENDA ETC series are intended for installation in control panels. Make sure that the device is used only for intended purpose. The shielding
must be grounded on the instrument side. During an installation, all of the cables that are connected to the device must be free of energy.
The device must be protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation temperature is not
exceeded. All input and output lines that are not connected to the supply network must be laid out as shielded and twisted cables. These
cables should not be close to the power cables or components. The installation and electrical connections must be carried on by a qualified
staff and must be according to the relevant locally applicable regulations

.

Logic output of the instrument is not electrically
insulated from the internal circuits. Therefore,
when using a grounding thermocouple, do not
connect the logic output terminals to the ground.

1) Mains supply cords shall meet the requirements
of IEC 60227 or IEC 60245.
2) In accordance with the safety regulation, the
power supply switch shall bring the identification of
the relevant instrument and it should be easily
accessible by the operator.

Note:

Independent Alarm
A1.tP. indE

=

=

Deviation Alarm

A1.tP. DE.

Band Alarm

=

A1.tP. bAnd

A.StA. Hi

=

A1.St. boHi

=

=

A.StA. Lo

=

A1.St. biHi

ASV

SV

SV

SV

SV+ASV

SV+ASV

SV-ASV

OFF

OFF

OFF

OFF

OFF

OFF

-300

300

+300

300

ON

ON

ON

ON

ON

ON

SV    =

ASV =

Set point of CONT output

Set point of alarm output

(ASV min.  =-300, ASV max. = +300)

(ASV min. = 0, ASV max. = +300)

(

)

ASV min = beginning of scale

ASV max = end of scale

SV =

ASV =

Set point of CONT output

Set point of AL1 output

a1.Hy.

A1.Hy..

A1.Hy.

A1.Hy.

(If

,

inP Pt..0

=

ASV min.   = -30.0,

ASV max. = +30.0)

(If

,

inP Pt..0

=

ASV min. = 0.0, ASV max. = +30.0)

MODIFICATION OF CONTROL AND ALARM SET POINTS

C.SEt

150

A1.sE.

250

C.SEt

150

A1.sE.

250

A1.sE.

249

First, press and hold          key until the massage

appears on the display. Then, the value is adjusted by using                  keys.

C.Set

SET

CSET

SET

CSET

SET

CSET

SET

CSET

ASET

ASET

ASET

When

is released, it

returns to normal operation.

CSET

When

s released, it

returns to normal operation.

ASET i

130

150

PV

PV

PV

PV

PV

PV

SV

SV

C.SEt

149

PV

SV

SV

SV

SV

SV

First,  press and  hold             key, alarm setpoint value appears on the display. Then, the value is adjusted by using                      keys.

different from

Alarm1 and Alarm2 setpoint values can be adjusted in sequence when per press          key.

.

If

C.ot.S

out1.

ASET

ASET

SET

CSET

ASET

NOTE:

The maximum of

is the value of

parameter and the minimum of it is the value of

parameter.

If independent alarm is selected,

values can be adjusted between  the limits of  the full scale.

If deviation alarm is selected,

and

values can be adjusted between

If band alarm is selected,

and

values can be adjusted between

C.SEt

C.Hi.L.

C.Lo.L.

A1.SE.

and

and +

.

and +

.

A2.SE.

A1.SE.

A2.SE.

A1.SE.

A2.SE.

300

300

0

300

— — — —

— — — —

PFA
150

PSC

150

PV

PV

PV

PV

SV

SV

SV

SV

Error Messages

Temperature  value is

higher than the scale

Temperature value is

lower than the scale

Temperature sensor

is broken or over temperature

Pt 100 or a sensor

line is short circuited

150

150

15

16

17

18

19

20

21

10

11

12

11

12

13

14

15

16

17

15

16

17

18

19

20

21

10

11

12

11

12

13

14

15

16

17

8

9

10

ETC742 -230VAC

0

ETC742 -2

0 4VAC

ETC842 -230VAC

0

ETC942 -230VAC

0

ETC842 -2

0 4VAC

ETC9420-24VAC

8

9

10

8

9

10

11

12

13

14

3

4

5

ETC442 -230VAC

0

8

9

10

11

12

13

14

3

4

5

ETC442 -2 VAC

0 4

+

+

CONT./AL2

Al1

AC 250V 2A
RESISTIVE
LOAD

AC 250V 2A
RESISTIVE
LOAD

230V AC

+10% -20%

50/60Hz  5VA

TC

Pt 100

RS-485 COM.

RS- 485

SSR

OUT

B

+

2

1

A

6

7

15

1

2

6

7

15

1

2

3

4

5

6

7

1

2

3

4

5

6

7

1

2

3

4

5

6

7

8

9

13

14

1

2

3

4

5

6

7

8

9

13

14

SSR

OUT

+

+

TC

Pt 100

CONT./AL2
AC 250V 2A
RESISTIVE
LOAD

Al1

AC 250V 2A
RESISTIVE
LOAD

24V AC ±10%
50/60Hz  7VA

+

RS-485
COM.

RS- 485

SSR

OUT

A

B

+

230V AC

+10% -20%

50/60Hz 7VA

CONT./AL2
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

TC

+

Pt 100

SSR

OUT

+

TC

+

Pt 100

CONT./AL2
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

24V AC ±10%
50/60Hz  5VA

+

RS-485
COM.

RS- 485

A

B

SSR

OUT

+

TC

+

Pt 100

230V AC

+10% -20%

50/60Hz 7VA

CONT./AL2
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

SSR

OUT

+

TC

+

Pt 100

CONT./AL2
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

24V AC ±10%
50/60Hz

VA

7

8

9

10

11

12

13

14

3

4

5

2

1

6

7

15

230V AC

+10% -20%

50/60Hz  7VA

CONT./AL2 OUT
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

+

Pt 100

TC

SSR

OUT

+

+

RS-485 COM.

RS- 485

A

B

8

9

10

11

12

13

14

3

4

5

2

1

6

7

15

CONT./AL2 OUT
AC 250V 2A
RESISTIVE
LOAD

AL1
AC 250V 2A
RESISTIVE
LOAD

+

Pt 100

TC

SSR

OUT

+

24V AC ±10%
50/60Hz

VA

7

2./4

ETCx420-E

10

9

12

11

16

15

2

1

ETC4420 ETC7420 ETC8420

ETC9420

Pt 100

9

Pt 100

10

8

TC

TC

+

+

8

ETC9420

ETC9420

8

Pt 100

9

7

7

8

6

TC

+

+

9

8

+

+

8

7

ETC4420

ETC7420

ETC8420

ETC4420

ETC7420

ETC8420

TC

+

+

7

Pt 100

8

8

6

7

9

TERMS

ETC 4420

CNT/AL2

SSR

( 7 )

AL1

SET

CSET

ASET

ENDA

TEMPERATURE CONTROLLER

( 1 ) PV display

4 digits 7 segment red LED

( 2 ) SV display

4 digits 7 segment yellow LED

PV

Character heights

SV display :7 mm

Micro switch

( 3 ),( 4 ),( 5 ),( 6 ) Keypad

( 7 ) State indicator

3 red LEDs for Control, Alarm1 and SSR outputs

ALARM1 AND ALARM2 OUTPUT TYPES

Independent Alarm

A1.tP.=indE

SV

ON

OFF

ON

OFF

a1.Hy.

ASV

(

ASV min = beginning of scale

-300

ASV max = end of scale)

(ASV min. =-300, ASV max. = +300)

inP = Pt..0

(

If

SV

=

Set point of CONT output

SV+ASV

SV

SV-ASV

ON

OFF

Band alarm is possible

Beginning

of procedure

SV =Set point of CONT output

MODIFICATION OF CONTROL AND ALARM SET POINTS

PV

130

C.SEt

SET

SV

150

150

CSET

SET

First, press and hold

key until the massage

CSET

A1.sE.

250

ASET

First, press and hold

C.ot.S

If

different from

C.SEt

NOTE:

The maximum of

If independent alarm is selected,

If deviation alarm is selected,

A1.SE.

If band alarm is selected,

— — — —

PV

SV

150

Temperature value is

Temperature value is

higher than the scale

lower than the scale

( 1 )

Process value during normal operation

Mnemonic parameter code during programming

PV

( 2 )

Set point during normal operation.

Data value during programming

SV

( 3 )

Increment key during normal operation and programming

Parameter selection key during programming

( 4 )

Decrement key during normal operation

If only this key is pressed in normal operation, software version number is seen.

Parameter selection during programming

( 5 )

Alarm set key during normal operation

Menu selection key during programming

( 6 )

Heat set key during normal operation

Parameter selection key during programming

display :

7 mm

Deviation Alarm

A1.tP.= DE.

SV

ON

A.StA.= Hi

OFF

ON

A.StA.= Lo

OFF

A1.Hy..

SV+ASV

+300

,

ASV min. = -30.0,

ASV max. = +30.0)

ASV =

Set point of alarm output

Band Alarm With Inhibition

A1.tP.= BAn.i.

SV+ASV

SV

SV-ASV

ON

OFF

Beginning

of procedure

ASV = Set point of AL1 output (ASV min. = 0, ASV max. = 300 )

PV

PV

C.SEt

SET

SET

SV

SV

149

CSET

CSET

C.Set

appears on the display. Then, the value is adjusted by using

PV

A1.sE.

PV

SV

249

SV

ASET

ASET

key, alarm setpoint value appears on the display. Then, the value is adjusted by using

ASET

out1.

Alarm1 and Alarm2 setpoint values can be adjusted in sequence when per press

C.Hi.L.

is the value of

parameter and the minimum of it is the value of

A1.SE.

A2.SE.

and

values can be adjusted between the limits of the full scale.

A1.SE.

A2.SE.

and

values can be adjusted between —

A2.SE.

values can be adjusted between 0 and +300.

and

Error Messages

PV

PFA

— — — —

SV

150

150

Temperature sensor

is broken or over temperature

Band Alarm

A1.tP.= bAnd

SV

A1.Hy.

A1.Hy.

SV-ASV

SV+ASV

300

SV =

Set point of CONT output

ASV =

(ASV min. = 0, ASV max. = +300)

inP = Pt..0 ASV min. = 0.0, ASV max. = +30.0)

(If

,

Band alarm is possible

When CSET is released, it

returns to normal operation.

PV

C.SEt

SET

SV

150

CSET

PV

A1.sE.

SV

250

ASET

C.Lo.L.

300

300

and +

.

PV

PV

PSC

SV

SV

150

Pt 100 or a sensor

line is short circuited

3/4

ON

A1.St.= boHi

OFF

ON

A1.St.= biHi

OFF

300

Set point of AL1 output

keys.

When ASET is released, it

returns to normal operation.

keys.

.

key.

ASET

parameter.

ETC4420-E-02-R

РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ ETC4420-230V
файл в формате JPG
загружен 31-08-2019 19:42

  • Grundig 40vle7130bm прошивка USB

    https://remont-aud.net/dump/lcd_pdp_tv/grundig/grundig_chassis_tf_40vle7131bf_shassi_main_board_vpz190r_4_v_0/252-1-0-81555

    Вано
    Сегодня в 16:52

  • Решено Bravis LED-32E1800 Smart+T2 Black, шасси CV338-T42

    В личку гляньте

    Помогите пожалуйста с прошивкой Bravis LED-32E1800 +T2+Smart

    триод
    Сегодня в 12:18

  • LG 70UM7100PLA дамп EEPROM(IC200)

    Или файл конфигурации json под эту модель.

    mastak1972
    Сегодня в 03:34

  • Амагнитола Alpine INE-W970BT ищу схему

    Всем привет, неисправность вроде пустяковая, не работает инвертор подсветки, но ремонтопригодность коробка никакая, два этажа. Схема очень помогла бы.

    mono
    Среда в 11:33

  • Samsung PS-42C91HR майн BN94-01224B. Помогите найти прошивку

    24C560N. Хочу попробовать прошить.

    Может не стоит. А то ситуация может обернуться подобным образом http://creative3d.ru/index/0-82

    ФАРТ
    Вторник в 21:03

  • Visio 43k92fs (Bad Update) – 358M3C2 Motherboard, LK430WDD1 Panel bad image

    (mauvaise mise à jour)

    déplacé vers les demandes de firmware.

    où puis-je trouver le firmware ?

    elbakkal
    Понедельник в 12:25

Понравилась статья? Поделить с друзьями:
  • Музыкальный центр lg cj45 инструкция по применению
  • Танакан инструкция по применению цена отзывы аналоги кому прописывают
  • Тип руководства это форма управляющего воздействия
  • Кетанов дуо цена инструкция по применению взрослым
  • 1 рэвс мосводоканал руководство