Chapter 9 Technical Data
9.6
FCU 2160
Ambient operating temperature
Power Supply
Group bus interface
Field bus interface
Explosion protection
Number of tanks per FCU
9-6
Service Manual
-40 °C to +70 °C (-40 °F to +158 °F)
115 or 230 VAC, +10% to -15%, 50-60
Hz, max. 10 W
TRL/2 Bus, RS-232 or RS-485,
Modbus based protocol
TRL/2 Bus. Max 8 units on one port
None
Max 32 (max 8 per field bus is recom-
mended)
308012En, Ed.2
May 2013
User Manuals, Guides and Specifications for your Rosemount TankRadar Rex FCU 2160 Measuring Instruments. Database contains 1 Rosemount TankRadar Rex FCU 2160 Manuals (available for free online viewing or downloading in PDF): Service manual .
Модуль полевого соединения FCU 2160 осуществляет опрос устройств системы: радарных уровнемеров RTG, модулей DAU – и записывает данные в буферную память. При получении запроса модуль FCU незамедлительно пересылает их из буферной памяти.
Модуль FCU является основным (мастер) устройством для полевой шины, и подчиненным устройством для групповой. Прибор имеет 6 коммуникационных портов. Порты могут быть индивидуально сконфигурированы либо в качестве портов групповой шины, либо в качестве портов полевой шины.
Если у вас есть вопросы, пожалуйста, позвоните по телефону: +7 (499) 922-40-10 или заполните форму обратной связи.
Reference Manual
300530EN, Rev BA
September 2012
Rosemount 2410 Series
4-6 Section 4. Configuration
4.6.3 FCU 2160 Configuration
In case the system includes a 2160 Field Communication Unit (FCU), it has to
be installed prior to installing the Rosemount 2410 Tank Hub. The following is
a brief description of how to install a 2160 FCU. See the Raptor System
Configuration Manual (Document no. 300510EN) for a more comprehensive
description.
To install and configure a 2160 FCU:
1. Start the installation wizard in TankMaster WinSetup and choose Device
Type=FCU 2160.
2. Enable communication with the TankMaster PC:
• Select communication channel
• Set the communication address
3. Configure the FCU: specify Port type (Field Bus/Group Bus), Baud rate,
Data bits, Stop bits, and Parity.
4. Configure the Slave Database.
Set Slave Type=2410_Level in the first free position of the Slave Type
column.
A 2410_Temp device is automatically added to the Slave Database.
Ensure that the Modbus Addresses of the connected devices are
properly set. These addresses must correspond to the 2410 Tank Hub
database settings (see “Basic Configuration of a Rosemount 2410” on
page 4-3 for more information).
Figure 4-2. The Slave Database
has to be configured for level
gauges and temperature
transmitters
2410_Level
2410_Temp is
automatically added