Datasheet excerpt: Technical data of
KFD2-SR2-Ex1.W.LB
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 … 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 45 mA | |
Power dissipation | ≤ 0.9 W | |
Power consumption | ≤ 0.9 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 | |
Output I | signal ; relay | |
Output II | signal or fault message ; relay | |
Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | ≤ 10 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010+A1:2019+A1:2019/AC:2019 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 , EN 61326-3-1:2017 , EN IEC 61326-3-2:2018 | |
Degree of protection | IEC 60529:1989+A1:1999+A2:2013 | |
Functional safety | IEC/EN 61508:2010 | |
Input | EN 60947-5-6:2000 | |
Ambient conditions | ||
Ambient temperature | -20 … 70 °C (-4 … 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2080 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Input | Ex ia | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Supply | ||
Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) | |
Output | ||
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | II (3)G [Ex ic Gc] IIC | |
Input | Ex ic | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | II 3G Ex ec nC IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN IEC 60079-15:2019 | |
International approvals | ||
FM approval | ||
FM certificate | FM19US0207X | |
Control drawing | 116-0035 | |
UL approval | E106378 | |
Control drawing | 116-0473 (cULus) | |
Contact loading | 250 V AC/2 A/cos φ > 0.75; 126.5 V AC/4 A/cos φ > 0.75; 30 V DC/2 A resistive load | |
IECEx approval | ||
IECEx certificate | IECEx PTB 11.0034 , IECEx TUN 19.0013X | |
IECEx marking | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I Ex ec nC IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
---|---|
ECLASS 11.0 | 27210121 |
ECLASS 10.0.1 | 27210121 |
ECLASS 9.0 | 27210121 |
ECLASS 8.0 | 27210121 |
ECLASS 5.1 | 27210121 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
Details:
KFD2-SR2-Ex1.W.LB
Function
This isolated barrier is used for intrinsic safety applications.
The device transfers digital signals from NAMUR sensors or dry contacts from the hazardous area to the non-hazardous area.
The proximity sensor or the mechanical contact controls the control side load for a relay contact output. The device output changes the state when the input signal changes the state.
Via switches the mode of operation can be reversed and the line fault detection can be switched off.
During a fault condition, the relay reverts to its de-energized state and the LEDs indicate the fault according to NAMUR NE 44.
If the device is operated via Power Rail, additionally a collective error message is available.
Associated Products:
KFD2-SR2-Ex1.W.LB
Matching System Components | ||||
---|---|---|---|---|
|
||||
|
||||
|
||||
Accessories | ||||
|
||||
|
||||
|
||||
|
- Manuals
- Brands
- Pepperl+Fuchs Manuals
- Amplifier
- KFD2-SR2-Ex1.W.LB
Manuals and User Guides for Pepperl+Fuchs KFD2-SR2-Ex1.W.LB. We have 2 Pepperl+Fuchs KFD2-SR2-Ex1.W.LB manuals available for free PDF download: Manual, Instruction Manual
1
103
36
7_
EN
G.xm
l
2
003
-03-
2
5
Subject to reasonable modifications due to technical advances.
Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
KFD2-SR2-Ex1.W
Isolated switch amplifiers
yellow
green
Output
Power
supply
Saf
e area
Input I EEx ia IIC
Switch S3 in position I
Switch S3 in position I
Switch S3 in position I
Switch S3 in position II
Hazar
dous area
LB
SC
red
Power
Rail
LB/SC
collective
error message
only
KFD2-SR2-Ex1.W
without LB, SC
without SC
&
3-
1+
7
8
9
S1
14 15
+
+
—
2+
II
I
1+
3-
1+
3-
3-
2+
3-
1+
10 k
Ω
10 k
Ω
400
Ω ≤ R ≤ 2 kΩ
S3
—
Composition
24 V DC
• 1-channel
• Control circuit EEx ia IIC
• Reversible mode of operation
• 1 relay output with 1 changeover
contact
• EMC acc. to NAMUR NE 21
• LB/SC monitoring
• LB/SC collective error message via
Power Rail
• Usable up to SIL 2 acc. to IEC 61508
The transformer isolated barrier
transfers digital signals from the
hazardous area. Sensors per
DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as
alarms. Control circuits are monitored
for lead breakage (LB) and short circuit
(SC). The external faults are indicated
according to NAMUR NE44 by a red
flashing LED. For type KFD2-SR2-
Ex1.W, an LB/SC collective error
message is in addition transferred
through the Power Rail to the power
feed module. The intrinsically safe input
is per DIN EN 50020 safely isolated
from the output and the power supply.
The relay output is in accordance with
IEC 61140 safely isolated from the
power supply.
Function
Output: relay
Isolated switch amplifiers |
KFD2-SR2-Ex1.W |
Output: relay |
|
24 V DC
•1-channel
•Control circuit EEx ia IIC
•Reversible mode of operation
•1 relay output with 1 changeover contact
•EMC acc. to NAMUR NE 21
•LB/SC monitoring
•LB/SC collective error message via Power Rail
•Usable up to SIL 2 acc. to IEC 61508
Function
The transformer isolated barrier transfers digital signals from the hazardous area. Sensors per DIN EN 60947-5-6 (NAMUR) and
mechanical contacts may be used as alarms. Control circuits are monitored for lead breakage (LB) and short circuit (SC). The external faults are indicated according to NAMUR NE44 by a red flashing LED. For type KFD2-SR2- Ex1.W, an LB/SC collective error message is in addition transferred through the Power Rail to the power feed module. The intrinsically safe input is per DIN EN 50020 safely isolated from the output and the power supply. The relay output is in accordance with IEC 61140 safely isolated from the power supply.
Input I EEx ia IIC
1+ |
3- |
400 Ω ≤ R ≤ 2 kΩ |
|
1+ |
10 kΩ |
3- |
without SC |
10 kΩ |
||
2+ |
3- |
||
without LB, SC 1+ |
3- |
||
1+ |
2+ |
3- |
|
LB |
|||
SC |
|||
I |
II |
S3 |
|
S1 |
red |
&
yellow
7 8 9
Output
Composition
Subject to reasonable modifications due to technical advances.
Switch S3 in position I
area |
||
Switch S3 in position I |
||
Hazardous |
||
Switch S3 in position I |
||
Switch S3 in position II
+ |
— |
Safearea |
|
green |
|||
+ — |
|||
14 |
15 |
||
Power |
Power |
LB/SC |
|
supply |
Rail |
collective |
|
only |
error message |
||
KFD2-SR2-Ex1.W |
103367_ENG.xml 2003-03-25
Copyright Pepperl+Fuchs, Printed in Germany
1 |
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com |
Loading…
You can only view or download manuals with
Sign Up and get 5 for free
Upload your files to the site. You get 1 for each file you add
Get 1 for every time someone downloads your manual
Buy as many as you need
Артикул: 132959
Барьер искрозащиты для сигналов DI. 1 канал
Производитель:
PEPPERL+FUCHS
Производитель: PEPPERL+FUCHS
Технические данные PDF
Краткое описание: технические характеристики KFD2-SR2-EX1.W.LB
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 … 30 V DC | |
Ripple | ≤ 10 % | |
Rated current | ≤ 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 … 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I ≤ 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 ; output II: terminals 10, 11, 12 | |
Output I | signal ; relay | |
Output II | signal or error message ; relay | |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | ≤ 10 Hz | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Output/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Input | EN 60947-5-6:2000 | |
Ambient conditions | ||
Ambient temperature | -20 … 60 °C (-4 … 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 00 ATEX 2080 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Input | Ex ia | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Supply | ||
Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) | |
Output | ||
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | II (3)G [Ex ic Gc] IIC | |
Input | Ex ic | |
Voltage | 10.5 V | |
Current | 13 mA | |
Power | 34 mW (linear characteristic) | |
Output | ||
Contact loading | 253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | II 3G Ex nA nC IIC T4 | |
Output | ||
Contact loading | 50 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Input/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. | |
Accessories | ||
Optional accessories | — power feed module KFD2-EB2(.R4A.B)(.SP) — universal power rail UPR-03(-M)(-S) — profile rail K-DUCT-BU(-UPR-03) |
Оформить заказ на KFD2-SR2-EX1.W.LB вы можете в компании compeq-pepperl отправив заявку по почте, а также по телефону или в офисе компании.
Вам может понравиться
Барьер искрозащиты для датчиков температуры, универсальный. 2 канала.
Барьер искрозащиты. 1 канал
Барьер искрозащиты. 1 канал
Барьер искрозащиты. 1 канал
Барьер искрозащиты. 1 канал