Liebert gxt3 руководство

Liebert GXT3 User Manual

  • Contents

  • Table of Contents

  • Troubleshooting

  • Bookmarks

Quick Links

Liebert

GXT3

UPS 120V/208V 500VA-3000VA

®

User Manual

AC Power

For Business-Critical Continuity™

loading

Related Manuals for Liebert GXT3

Summary of Contents for Liebert GXT3

  • Page 1
    AC Power For Business-Critical Continuity™ Liebert GXT3 UPS 120V/208V 500VA-3000VA ® ™ User Manual…
  • Page 3: Table Of Contents

    ® 2.6.2 Installing the Optional Liebert IntelliSlot Card and Communication Cables … 18 ……….19…

  • Page 4
    ……….23 Disconnecting Input Power from the Liebert GXT3……. . 23 .
  • Page 5
    Liebert GXT3 rack/tower models—front view ……..
  • Page 7: Important Safety Precautions

    When the UPS is connected to an IT power distribution system, a short-circuit protection device must be installed on the neutral line. ® ™ Install and use the Liebert GXT3 in the following environments: • Temperature: 32°F — 104°F (0°C — 40°C), relative humidity: 0% ~ 95% non-condensing •…

  • Page 8
    Operating this device in a residential area is likely to cause harmful interference that users must correct at their own expense. The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the published technical standards. Continued compliance requires installation in accordance with these instructions and use of accessories approved by Emerson.
  • Page 9: Glossary Of Symbols

    LOSSARY OF YMBOLS Risk of electrical shock Indicates caution followed by important instructions AC input AC output Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid battery PbH2SO4 Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON/Alarm Silence/Battery Test…

  • Page 10: Product Description

    GXT3 is a compact, online uninterruptible power system (UPS) that continuously conditions and regulates its output voltage. The Liebert GXT3 is designed to supply microcomputers and other sensitive equipment with clean sine wave input power. Upon generation, AC power is clean and stable. However, during transmission and distribution it is subject to voltage sags, spikes and complete failure that may interrupt computer operations, cause data loss and damage equipment.

  • Page 11: Appearance And Components

    Liebert GXT3 minitower—front view Operation and Display Panel Ventilation Slots 1.3.2 Rear Panel Features The rear panel of the Liebert GXT3 has these features: • USB port • Cooling fan • Power output receptacles • Input circuit breaker ® • Liebert IntelliSlot port •…

  • Page 12: Figure 3 Liebert ® Gxt3 ™ 120V Rack/Tower Models-Rear Panel Components

    Product Description ® ™ Figure 3 Liebert GXT3 120V rack/tower models—rear panel components 500VA, 700VA, 1000VA, 1500VA Models Input Power Plug and Cable 5-15P Input Circuit USB Port Breaker Liebert IntelliSlot Port Output Receptacles, 5-15R External Terminal Block Battery Communication…

  • Page 13: Figure 4 Liebert ® Gxt3 ™ 208V Rack/Tower Models-Rear Panel Components

    Port External Terminal Block Battery Cooling Communication Connector Output Receptacles, L6-15R ™ Figure 5 Liebert GXT3-1000MT120 —rear panel components Input Power Plug and Cable, 5-15P 1000VA Model Terminal Block Input Circuit Communication Breaker Liebert IntelliSlot Port USB Port Cooling Fan…

  • Page 14: Major Components

    Liebert GXT3. Inverter In normal operation, the Liebert GXT3’s inverter utilizes the DC output of the PFC to produce precise, regulated sine wave AC power. When utility power fails, the inverter receives DC power from the DC-to-DC Converter. In either operation mode, the UPS inverter is online, continuously…

  • Page 15: Operating Mode

    Manual Bypass Mode occurs when the Standby/Manual bypass button is pressed and held for about 2 seconds while the Liebert GXT3 is in Utility (AC) Mode. Bypass operation is indicated by an audible alarm and illuminated amber bypass indicator (If other indicators are illuminated, refer to 7.0 — Troubleshooting).

  • Page 16: Battery Mode

    • Auto Sensing — 50Hz or 60Hz – Bypass Disabled • Frequency Converter — 50Hz – Bypass Disabled • Frequency Converter — 60Hz – Bypass Disabled The default for all models of the Liebert GXT3 is “Auto Sensing — 50Hz or 60Hz – Bypass Enabled.”…

  • Page 17: Installation

    77°F (25°C) reduces battery life. Installation Clearances Maintain at least 4 inches (100mm) clearance in the front and rear of the Liebert GXT3. Do not obstruct the air inlets on the front panel and rear panel of the UPS; blocking the air inlets reduces…

  • Page 18: Mechanical Installation

    The Liebert GXT3 may be installed as a tower or in a rack, depending on space and use considerations. The Liebert GXT3 may be used alone, as a single UPS, or with up to four battery cabinets. NOTE When installing the UPS or making input and output connections, comply with all relevant safety codes and standards 2.4.1…

  • Page 19: Figure 9 Rotate The Operation And Display Panel

    90 degrees clockwise, which provides upright viewing for users. 5. Place the Liebert GXT3 and any battery cabinets on the support bases. Each Liebert GXT3 needs two support assemblies, as shown in Figure 10.

  • Page 20: Rack Installation

    3. Determine the Liebert GXT3’s mounting position inside the racks vertical rails. CAUTION Reduce the risk of tipping the rack by installing the Liebert GXT3 as low as possible in the rack. 4. Attach the rear member of each slide rail assembly to the rack’s rails with two factory-supplied M5 screws (see Figure 12).

  • Page 21: Figure 13 Installing Front Member Of Each Slide Rail Assembly

    M4 screws provided in this kit. Make sure that the retaining latch is near the rear of the UPS, as shown in Figure 15. Figure 15 Installing inner members Liebert GXT3 UPS Inner Member Retaining Latch M4 screw , 8 pieces…

  • Page 22: Figure 16 Installing Rack-Mount Handles

    Installation Figure 16 Installing rack-mount handles Liebert GXT3 UPS Rack-Mount Handles, 2 pieces M4 Screw , 8 pieces 9. Insert the UPS, with inner members attached, into slide rail assemblies by inserting top and bottom edges of inner members into the top and bottom, curved tracks of front members and sliding the UPS into rack, as shown in Figure 17.

  • Page 23: Cable Connection

    GXT3 rear panel has an input cable and plug, output receptacles and output cable(s) (Output cables are on GXT3-3000 models only). Refer to 1.3.2 — Rear Panel Features for details. The battery cables are supplied with the battery cabinet. 2.5.1…

  • Page 24: Connecting Communication Cables

    Connecting USB Communication Cables 1. Take the USB communication cables out of the accessories box. ® 2. Insert one end of the USB communication cable to the USB port on the rear panel of the Liebert ™ GXT3 (see Figures 3 and 5).

  • Page 25: Controls And Indicators

    Controls and Indicators ONTROLS AND NDICATORS ® ™ The operation and display panel, shown in Figure 18, is on the front panel of the Liebert GXT3 (see Figures 1 and 2). Figure 18 Operation and display panel Battery Level Indicators…

  • Page 26: Indicators

    The battery level indicator is composed of five sets of LED bars that illuminate and flash to indicate ® ™ the battery capacity level. The Liebert GXT3 battery capacity level is shown in 20% increments (±5%). The battery level indicators will illuminate as shown in Figure 19.

  • Page 27: Ups Status Indicators

    Controls and Indicators 3.2.2 UPS Status Indicators UPS status is indicated by five symbols: fault indicator, AC input indicator, battery indicator, inverter indicator and bypass indicator. Table 5 shows the symbols and their meaning. Table 5 UPS status indicators UPS Status Indicator Icon Color…

  • Page 28: Operation

    3. Once the inverter LED has been illuminated, turn On the connected loads. 4. Check the status indicators to determine whether the Liebert GXT3 is operating normally. 5. Check the load level indicators to verify that the connected load does not exceed the UPS’ rated capacity.

  • Page 29: Shut Down The Liebert ® Gxt3

    Disconnecting Input Power from the Liebert GXT3 ® ™ 1. Once the UPS has been shut down as detailed in 4.5 — Shut Down the Liebert GXT3 disconnect the input cable plug. 2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the power-off is complete.

  • Page 30: Communication

    Liebert MultiLink monitors the UPS continuously and can shut down your computer or server in the event of an extended power failure. Liebert MultiLink can also be configured to shut down the UPS. Liebert’s MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot SNMP Card or Liebert IntelliSlot Web Card is installed in the UPS.

  • Page 31: Usb Port Communication

    5.2.1 Configuration Program ™ Accessing the Configuration Program via USB is a new feature of the Liebert GXT3 . For most users, the factory default settings will be adequate. This section illustrates the features available for modification, as well as the factory default setting.

  • Page 32: Terminal Block Communication

    When the Auto-Enable output option is selected and the UPS output is disabled using Pin 1 ® ™ and Pin 2, the Liebert GXT3 ’s output can turn On automatically and without warning if the Pin 1 and Pin 2 connection is changed.

  • Page 33: Battery Mode Shutdown

    This timer cannot be stopped once triggered. If utility power returns during this countdown, the Liebert GXT3 will still shut down and must remain shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.

  • Page 34: Maintenance

    Maintenance AINTENANCE ® This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions. WARNING The battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the battery pack: •…

  • Page 35: Figure 22 Removing The Front Bezel Cover And Battery Door

    Maintenance Figure 22 Removing the front bezel cover and battery door Battery Door Screws, 6 Front Bezel 4. Gently pull the battery wire out and disconnect the battery plug and battery receptacle, as shown in Figure 23. Figure 23 Disconnecting the battery plug and battery receptacle (front view) Battery Connector Battery Receptacle 5.

  • Page 36: Battery Charging

    If the Liebert GXT3 will be stored for a long time, Emerson recommends connecting the UPS to input power for at least 24 hours every four to six months to ensure full recharge of the batteries.

  • Page 37: Troubleshooting

    B&E Short circuit on the output ™ port) (no C&E UPS shutdown by command from communication (USB port or Liebert IntelliSlot audible) Utility LED flash L-N reverse Battery Indicator Battery not connected (continuous horn); check battery connection, power down and restart…

  • Page 38: Audible Alarm

    Troubleshooting 7.1.2 Audible Alarm An audible alarm will be used in conjunction with the visual indicators to indicate to the user a change in UPS operating status. The audible alarm will enunciate as given in Table 9. Table 9 Audible alarm description Condition Alarm Battery discharge…

  • Page 39
    When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the ® ™ top panel of the Liebert GXT3…
  • Page 40: Battery Cabinet

    . The battery connectors and input breaker are on the battery cabinet’s rear panel, as shown in Figure 26. For battery cabinet specifications, refer to Table 13. The Liebert GXT3 may be equipped with a maximum of four extension battery packs.

  • Page 41: Specifications

    Specifications PECIFICATIONS Table 11 Specifications of GXT3-500RT120 — GXT3-1000RT120 and GXT3-1000MT120 UPS Product Model GXT3-500RT120 GXT3-700RT120 GXT3-1000RT120 GXT3-1000MT120 Parameters (500VA/450W) (700VA/630W) (1000VA/900W) (1000VA/900W) Dimensions, D × W × H, in. (mm) 19.7 x 16.9 x 3.4 15.4 x 6.9 x 8.9 Unit (497 ×…

  • Page 42: Table 12 Specifications Of Gxt3-1500Rt120 — Gxt3-3000Rt120 And Gxt3-3000Rt208 Ups

    Specifications Table 12 Specifications of GXT3-1500RT120 — GXT3-3000RT120 and GXT3-3000RT208 UPS Product Model GXT3-1500RT120 GXT3-2000RT120 GXT3-3000RT120 GXT3-3000RT208 Parameters (1500VA/1350W) (2000VA/1800W) (3000VA/2700W) (3000VA/2700W) Dimensions, D × W × H, in. (mm) 19.7 x 16.9 x 3.4 23.7 x 16.9 x 3.4 Unit (497 ×…

  • Page 43: Table 13 Operating Temperature Parameters

    Specifications Table 13 Battery cabinet specifications Model Number Parameter GXT3-48VBATT GXT3-72VBATT GXT3-500RT120,GXT3-700RT120 GXT3-1000RT120,GXT3-1500RT120, GXT3-3000RT120 Used w/UPS Model GXT3-2000RT120 GXT3-3000RT208 Dimensions, D × W × H, in (mm) 19.7 x 16.9 x 3.3 23.7 x 16.9 x 3.3 Unit (497 × 430 × 85) (602 ×…

  • Page 44: Table 15 Battery Run Times

    Specifications Table 15 Battery run times 208 VAC RT 120VAC RT Models Model Load Percent Number of of Capacity 500VA 700VA 1000VA 1500VA 2000VA 3000VA 3000VA Batteries/Cabinets Internal Battery 100% Internal Battery + 1 External Battery Cabinet 100% Internal Battery + 2 External Battery Cabinets 100%…

  • Page 45: Product Warranty Registration

    77°F (25°C). To increase this time, turn Off non-essential loads (such as idle computers and monitors) or add optional external battery cabinets. Product Warranty Registration ® To register for warranty protection, visit the Quick Links section of the Liebert Web site at: http://www.liebert.com Click on Product Warranty Registration and fill in the form.

  • Page 46
    Specifications…
  • Page 48
    +39 049 9719 111 Fax: +39 049 5841 257 While every precaution has been taken to ensure the accuracy and completeness of this literature, Liebert Corporation assumes no Asia responsibility and disclaims all liability for damages resulting from use of 29/F, The Orient Square Building this information or for any errors or omissions.

инструкцияEmerson Liebert GXT3 1500VA

AC Power

For Business-Critical Continuity™

Liebert

®

GXT3

UPS 230V 700VA-3000VA

User Manual

Посмотреть инструкция для Emerson Liebert GXT3 1500VA бесплатно. Руководство относится к категории источники бесперебойного питания, 4 человек(а) дали ему среднюю оценку 9. Руководство доступно на следующих языках: английский. У вас есть вопрос о Emerson Liebert GXT3 1500VA или вам нужна помощь? Задайте свой вопрос здесь

  • Important Safety Precautions
  • Save These Instructions
  • Glossary of Symbols
  • 1.0 Product Description
  • 2.0 Installation
  • 3.0 Operation and Display Panel
  • 4.0 Operation
  • 5.0 Communication
  • 6.0 Maintenance
  • 7.0 Troubleshooting
  • 8.0 Battery Cabinet
  • 9.0 Specifications

Нужна помощь?

У вас есть вопрос о Emerson а ответа нет в руководстве? Задайте свой вопрос здесь Дай исчерпывающее описание проблемы и четко задайте свой вопрос. Чем детальнее описание проблемы или вопроса, тем легче будет другим пользователям Emerson предоставить вам исчерпывающий ответ.

Габен • 26-1-2021Нет комментариев

У нас предупреждение когда включаешь на сети а выходе нет напряжений

Количество вопросов: 1

Свойства
Выходная мощность 1.5 kVA
Выходная мощность 1350 W
Частота входного сигнала 40/70 Hz
Уровень шума 46 dB
Прочие свойства
Номинальное входное напряжение 230 V
Размеры (ШхГхВ) 430 x 497 x 85 mm
Размеры упаковки (ШхГхВ) 570 x 617 x 262 mm
Совместимые операционные системы Windows 2000/XP/Vista
Батарея
Технология батареи Герметичная свинцово-кислотная (VRLA)
Время подзарядки батареи 3 h
Вес и размеры
Условия эксплуатации
Диапазон температур при эксплуатации 0 — 40 °C
Диапазон относительной влажности при эксплуатации 0 — 95 %
Рабочая высота 0 — 3000 m
Диапазон температур при хранении -15 — 50 °C
Дизайн
Безопасность EC/EN/AS 62040-1-1:2008

показать больше

Не можете найти ответ на свой вопрос в руководстве? Вы можете найти ответ на свой вопрос ниже, в разделе часто задаваемых вопросов о Emerson Liebert GXT3 1500VA.

Какой вес Emerson Liebert GXT3 1500VA?

Сколько времени нужно, чтобы зарядить аккумулятор Emerson Liebert GXT3 1500VA?

Инструкция Emerson Liebert GXT3 1500VA доступно в русский?

Не нашли свой вопрос? Задайте свой вопрос здесь

Посмотреть все Emerson руководства Посмотреть все Emerson источник бесперебойного питания руководства

AC Power 
For Business-Critical Continuity

One of the most affordable UPS systems in 
its class, Liebert GXT3 leads the industry in 
combining small size, high capacity and high 
reliability features:

On-line design means zero transfer time 
from external to internal power. When 
utility power fails, your critical load remains 
supported by a seamless flow of power. 

Liebert GXT3 rated output power factor 
of 0.9 better matches up with switch-
mode power supplies used in today’s IT 
equipment. A higher output power factor 
allows for a more efficient utilization of  
the UPS.

The UPS provides easy serviceability with 
user replaceable hot-swappable batteries. 

For maximum control, Liebert GXT3 is 
custom configurable to your needs  
using a specially designed Windows 
software package.

ENERGY STAR® qualified

models available.

Trade Compliance: Public sector customers 
may select from four capacities (1000, 
1500, 2000 and 3000 VA, 120V) to provide 
TAA compliance.Refer to Liebert GXT3-
GVG3 models.

Ideally suited for:

PCs

Network workstations

Servers

Network closets

Large network peripherals

VoIP

Liebert GXT3 is a true on-line UPS that delivers continuous, high-quality  
AC power to IT equipment with no break when transferring to battery. It protects 
equipment from virtually all power disturbances due to blackouts, brownouts,  
sags, surges or noise interference. The UPS is available in rack/tower and  
mini-tower configurations.

Liebert

®

 GXT3, 500VA -3000VA Models

Reliable On-Line UPS Protection In A Compact 2U Package

Скачать файл PDF «Emerson Liebert GXT3- 10 000 T220 UPS Инструкция по эксплуатации» (2.05 Mb)

Популярность:

4116 просмотры

Подсчет страниц:

32 страницы

Тип файла:

PDF

Размер файла:

2.05 Mb

Detail Specifications:

214/214015-liebert_gxt3.pdf file (11 Apr 2023)

Accompanying Data:

Emerson Liebert GXT3 UPS PDF Operation & User’s Manual (Updated: Tuesday 11th of April 2023 02:50:46 AM)

Rating: 4.4 (rated by 71 users)

Compatible devices: Liebert GXT4-700RT230, GXT5000R-208, Liebert PowerSure PST, Liebert PowerSure PSP Series, GXT4-5000RT230, Liebert NXL series, Liebert APM 15-90kVA, GXT4-6000RT230.

Recommended Documentation:

Text Version of Operation & User’s Manual

(Ocr-Read Summary of Contents, UPD: 11 April 2023)

  • 11, Product Description 5 1.3 Appearance and Components 1.3.1 Appearance The Liebert GXT3 rack/tower models in various power ratings have the same general appearance, controls and features (see Figure 1). The various rack/tower models differ largely in the type of receptacles each has. Figure 1 Liebert GXT3-700RT230 — GXT3-3000RT230 UPS 1.3.2 Rear Panel Features T…

  • 13, Product Description 7 Rectifier/Power Factor Correction (PFC) Circuit In normal operation, the Liebert GXT3’s rectifier/power factor correction (PFC) circuit converts mains power to regulated DC power for use by the inverter while ensuring that the wave shape of the input current used by the UPS is near ideal. Extracting this sine wave input current achieves two objec- tives: • Efficie…

  • 31, Maintenance 25 6.0 MAINTENANCE This section describes replacing the internal battery pack, precautions, checking the Liebert GXT3’s status and checking UPS functions. 6.1 Replacing the Internal Battery Pack The Liebert GXT3 is designed to allow the user to replace the internal battery pack safely. Read the safety cautions before proceeding. Contact your local dealer or Emerson represen…

  • 37, Emerson Liebert GXT3 Battery Cabinet 31 8.0 BATTERY CABINET Optional battery cabinets are available for the Liebert GXT3. The battery port and input breaker are on the battery cabinet’s rear panel, as shown in Figure 25. For battery cabinet specifications, refer to Table 12. Figure 25 Battery cabinet ! WARNING Do not contact the battery ports and ground without wearing protective gloves and clot…

  • 8, 2 Battery Safety ELECTROMAGNETIC COMPATIBILITY—The Liebert GXT3 series complies with the limits for a Class A digital device. Operating this device in a residential area is likely to cause harmful interfer- ence that users must correct at their own expense. The Liebert GXT3 series complies with the requirements of EMC Directive 2004/108/EC and the pub- lished tec…

  • 12, Emerson Liebert GXT3 Product Description 6 Figure 4 Rear panel components, Liebert GXT3 230V 3000VA models 1.4 Major Components The operating principle of the UPS is shown in Figure 5. Figure 5 Operating principle diagram The UPS is composed of mains input, TVSS and EMI/RFI filters, rectifier/PFC, inverter, battery char- ger, DC-to-DC converter, battery, dynamic bypass and UPS output. Transient Voltag…

  • 28, Emerson Liebert GXT3 Communication 22 5.2 USB Port Communication The standard B-type USB port is used to connect the UPS and network server or other computer sys- tem using Liebert MultiLink. The configuration program can be completed through the communica- tion port. 5.2.1 Configuration Program Accessing the Configuration Program via USB is a new feature of the Liebert GXT3. For most users, the factory default set…

  • 7, 1 IMPORTANT SAFETY PRECAUTIONS SAVE THESE INSTRUCTIONS This manual contains important safety instructions that must be followed during the installation and maintenance of the UPS and batteries. Read this manual thoroughly before attempting to install or operate this UPS. UPS Safety Notes The UPS contains no user-serviceable parts except the internal battery pack.…

  • 36, Troubleshooting 30 When reporting a UPS issue to Emerson, include the UPS model and serial number. These are on the top panel of the Liebert GXT3. Fault and Bypass indicators and diagnostic C indicator are illuminated UPS DC/DC fault UPS requires service. Contact your local dealer, Emerson representative or Emerson Channel Support. Fault indicator and diagnostic D indicator are illuminated U…

  • 16, Installation 10 2.4.1 Tower Installation To install the Liebert GXT3 as a tower: 1. Take out support bases from the accessories (see Figure 6). Figure 6 Support bases 2. If optional Liebert external battery cabinets will be connected to the Liebert GXT3, take out the spacers delivered with the battery cabinet. 3. Connect the spacers and the support bases as shown in Figure 6. Each Liebert GXT…

Recommended Instructions:

TimeLine 100, PCG-GRX616MP, Bowery Crib, HP6493/00, 045

  • Owner’s Manual1111 W. 35th Street, Chicago, IL 60609 USA www.tripplite.com/supportCopyright © 2011 Tripp Lite. All rights reserved.SmartOnline™ Single-Phase 10kVAIntelligent True On-Line UPS Systems (Rackmount/Tower)For all UPS system modules (power module, transformer module and battery module) sold separately or combined. Select UPS system modules ma …

    SmartOnline Single-Phase 10kVA 84

  • 231© 2004 Hewlett-Packard Development Company, L.P.Title in HP Futura Book14-20 pt., centeredSubtitle in 10-14 pt., centered, whiteEnglishArabicBahasaPortuguêsHrvatskiCeskyDanskNederlandSuomiFrançaisDeutschGreekHangulHebrewMagyarItalianoEspañolMagyarItalianoJapaneseEspañolNorskPortuguêsRussianSimplified ChineseSlovencinaSlovenšcinaEspañol Svenska Traditional- ChineseThai T …

    Photosmart 2710 16

  • SITOP UPS1600 under STEP 7 V5 ___________________ ___________________ ___________________ ___________________ ___________________ ___________ SITOP UPS1600 under STEP 7 V5 Getting Started Introduction 1 Safety notes 2 Description 3 Assigning the IP address 4 Installing and configuring the SITOP UPS1600 in STEP 7 V5 5 Parameterizing the SITO …

    SITOP UPS1600 40

Additional Information:

Operating Impressions, Questions and Answers:

Понравилась статья? Поделить с друзьями:
  • Руководство мастера днд 5 на русском pdf
  • Флуконазол инструкция по применению при грибке ушей у взрослого
  • Мясорубка редмонд мульти про 8 в 1 инструкция
  • Магний сульфат инструкция по применению в ампулах для чего назначают
  • Инструкция по охране труда для штукатура маляра