Mrs 10 руководство

ComAp InteliLite MRS10 User Manual

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

InteliLite

®

InteliLite

Modular Gen-set Controller

Compact Controller for Single Operating Gen-sets

(IL-CU MRS10/11/15/16 unit)

SW version 2.2, November 2004

Copyright © 2004 ComAp s.r.o.

Written by Adéla Klimentová

Prague, Czech Republic

MRS

ComAp, spol. s r.o.

Světova 7, 180 00 Praha 8, Czech Republic

Tel: +420 2 66316661, Fax: +420 2 66316647

E-mail: info@comap.cz, www.comap.cz

User guide

loading

Related Manuals for ComAp InteliLite MRS10

Summary of Contents for ComAp InteliLite MRS10

  1. Manuals
  2. Brands
  3. ComAp Manuals
  4. Controller
  5. InteliLite MRS10

Manuals and User Guides for ComAp InteliLite MRS10. We have 1 ComAp InteliLite MRS10 manual available for free PDF download: User Manual

Table of Contents for ComAp InteliLite MRS10:

  • J1939 connection description The following diagrams show how to connect the engine control unit to the InteliLite controller: Engines started via CAN bus VOLVO PENTA engines (EMS I, EMS II, EDC III units) 8 7 6 5 4 3 2 1 8-pin Deutsch connector — POWER D+ + IL-MRS15/16 BINARY BO2 OUTPUTS (FUEL)

  • Short-term voltage drops (e.g. during the engine cranking) do not affect the operation at all. Dimensions and weight Dimensions 180x120x55mm Weight 800g Generator Nominal frequency 50-60Hz Frequency measurement tolerance 0,2% Current inputs Nominal input current (from CT) 5 A Load (CT output impedance) < 0,1 Ω CT input burden < 0,2 VA per phase (In=5A) Max. measured current from CT 10 A Current

  • Dimensions IL-CU iL 185 (7,3″) 170 (8,87″) 4 2 , 5 ( 1 , 7 » ) 4 5 ( 1 , 8 » ) 1 2 1 2 1 3 0 ( 5 , 1 » ) 1 2 3 ( 4 , 8 » ) 1 1 3 ( 4 , 4 » ) 1 Cutout for InteliLite 113 x 175 mm (4.4 x 6,9“) Only for service purpose IL-MRS 10, 11 IL-MRS 15, 16 AT-LINK-CONV InteliLite MRS 15 iL 185 (7,3″) 170 (8,87″) 4 2 , 5 ( 1 , 7 » ) 4 5 ( 1 , 8 » ) ~

  • • Gen-set is not running and • No Shut down or Slow stop alarm is active • Controller is not in OFF mode Ready to load The output is closed if genset is running and all electric values are in limits no alarm is active — it is possible to close GCB or it is already closed. The output opens during cooling state. Stop solenoid The closed output energizes stop solenoid to stop the engine. The output opens again 10 s after RPM < 2 and Generator voltage < 10 VAC and Oil pressure < Engine params:

  • Power supply fusing A one-amp fuse should be connected in-line with the battery positive terminal to the controller and modules. These items should never be connected directly to the starting battery. Fuse value and type depends on number of connected devices and wire length. Recommended fuse (not fast) type — T1A. Not fast due to internal capacitors charging during power up. 12VDC + — Ba

  • Magnetic pick-up To ensure proper function: Use a shielded cable + Battery — iL GAC Speed Control Unit ESD 5500 MAGNETIC PICK-UP C D a b Signal Signal + + — — Power Supply Power Supply — Current measurement To ensure proper function Use cables of 2,5mm 2 Use transformers to 5A Connect CT according to following drawings L1 L2 L3 N G COM L1l K L k l L2l K L k l L3l K L k l Voltage measurement G GENERATOR MAINS L3L2L1N L1 L2 L3 N L3L2L1N Hint: Switchboard ligh

  • Terminals and dimensions IL-CU Terminals RPM Grounding Terminal Grounding Terminal POWER 8 — 36 V DC RS 232 — + D+ BOOT JUMPER BO3 BO4 BO5 BO6 BO1 (START) BO2 (FUEL) BINARY OUTPUTS ANALOG INPUTS RPM COM AI1 OIL AI2 TEMP AI3 FUEL RPM IN RPM GND BINARY INPUTSGEN. CURRENT 0 — 5 A GENERATOR VOLTAGE 3 x 230 / 400 V BI1 BI2 BI3 BI4 BI5 BI6 LB 16 N L1 L2 L3 L3l L2l L1l COM EXTENSION MODULE iL-MRS 15 Hint: EXTENSION MODULE and TEST PORT serves for Ext

  • The complete description of Modbus communication protocol can be found in Modbus Protocol Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are available from web site at http://www.modicon.com/openmbus/ . Communication object vs. Register All the data intended for communication has its representation as communication objects in the controller. The communication object is represented by the n-byte array in the controller memory and identified by the unique 16-bit

  • Technical data Power supply Voltage supply 8-36V DC Consumption 0,5-0,1A depend on supply voltage Allowed supply voltage drop-out: 50ms from min. 10V, return to min. 8V (valid for InteliLite of hardware version 3.2 and higher) Battery voltage measurement tolerance 2 % at 24V Hint: For the supply voltage less than 7V the backlight of the display is switched off. Operating conditions Operating temperature IL-CU

  • Alarm management Following alarms are available: Sensor fail Warning Shut down Sensor fail (FLS) Sensor fail is detected when measured value is 6% out of selected sensor characteristic. Sensor fail is indicated by ##### symbol instead measured value. Warning (WRN) When warning comes up, only alarm outputs and common warning output are closed. Possible warnings: See List of possible events Shut down

  • Voltage phase sequence detection InteliLite controller detects phase sequence on both generator and mains/bus voltage terminals. This protections are important after controller installation to avoid wrong voltage phases phase connection. Following alarms can be detected: Wrong phase sequence There is fix defined phase sequence in InteliLite controller L1, L2, L3. When the phases are connected in different order (e.g. L1,L3,L2 or L2,L1,L3) followi

  • • all IL alarms are detected, • IL front panel gen-set RED LED blinks or lights, • alarm is recorded on the IL alarm list screen, • BUT gen-set remains running. Hint: Warning SprinklActive is indicated in the AlarmList if sprinkler mode active to inform the operator that the engine is not protected. Access lock If the input is closed, no setpoints can be adjusted from controller front panel and gen-set mode (OFF- MAN-AUT-TEST) cannot be changed. Hint: Access lock does not protect setpoints and mode changing from Lite

  • InteliLite IL-2.1 R:10.11.2004 MRS16 30.11.2004 2,1 0200FFFF Group Name Value Dimension Com. obj. Data type Engine params Engine Speed 0 RPM 8209 Unsigned 16 Engine params ECU State 000 10034 Binary 8 Analog Batt volt 27,0 V 8213 Integer 16 Analog Oil press 3,6 Bar 8227 Integer 16 Analog Water temp 15 °C 8228 Integer 16 Analog Fuel level ##### % 8229 Integ

  • Gear teeth [-] Number of teeth on the engine gear for the pick-up. Set to zero, if no pick-up is used. Engine speed is counted from the generator frequency. Step: 1 Range: 0 – 500 Hint: Generator frequency can be used only when generator voltage (min 5V) is present before reaching of the firing speed (Starting RPM) after start. Nominal RPM [RPM] Nominal engine speed. Step: 1RPM Range: 100 – 4000 RPM F

Questions, Opinions and Exploitation Impressions:

You can ask a question, express your opinion or share our experience of ComAp InteliLite MRS10 device using right now.

Detail Specifications:

1460/1460628-intelilite_mrs10.pdf file (03 Mar 2023)

Accompanying Data:

ComAp InteliLite MRS10 Controller PDF Operation & User’s Manual (Updated: Friday 3rd of March 2023 03:59:27 AM)

Rating: 4.3 (rated by 53 users)

Compatible devices: IG-NT GC, InteliSys NT, InteliDrive DCU Industrial, InteliGen NTC, intelilite nt amf20, InteliDrive Lite, InteliLite NT AMF Series, InteliCompact NT.

Recommended Documentation:

Text Version of Operation & User’s Manual

(Ocr-Read Summary of Contents, UPD: 03 March 2023)

  • 21, • all IL alarms are detected, • IL front panel gen-set RED LED blinks or lights, • alarm is recorded on the IL alarm list screen, • BUT gen-set remains running. Hint: Warning SprinklActive is indicated in the AlarmList if sprinkler mode active to inform the operator that the engine is not protected. Access lock If the input is closed…

  • 52, ComAp InteliLite MRS10 Alarm management Following alarms are available: Sensor fail Warning Shut down Sensor fail (FLS) Sensor fail is detected when measured value is 6% out of selected sensor characteristic. Sensor fail is indicated by ##### symbol instead measured value. Warning (WRN) When warning comes up, only alarm outputs and common warning output are closed. P…

  • 32, Volvo – “Volvo-MarineD12 Aux” is selected in ECU configuration: Primary or secondary engine speed is set by Frequency select bits in VP Status frame. Scania – “Scania S6 Singlespeed” is selected in ECU configuration: Nominal engine speed is chosen by Nominal speed switch 1 and 2 from DLN1 frame when the engine is running on nominal speed, i.e. binary output Idle/Nomin…

  • 37, AnlInIOM3 lev2 [ ] The level for IOM ANALOG INPUT 3 alarm detection. Step: 1 Range: -100 — +10000 AnlInIOM3 del [s] Delay for IOM ANALOG INPUT 3 alarm. Step: 1 s Range: 0 — 180 s AnlInIOM4 lev1 [ ] The level for IOM ANALOG INPUT 4 alarm detection. Step: 1 Range: -100 — +10000 AnlInIOM4 lev2 [ ] The level for IOM ANALOG INPUT 4…

  • 2, Table of Contents Table of Contents …………………………………………………………………………………………………………………… 2 General guidelines………………………………………………………………………………………………………………….. 4 What describes this manual?……………..…

  • 35, Curr unbal [%] Threshold for generator current asymmetric (unbalance). Step: 1% of Nominal current Range: 1 – 200% of Nominal current Curr unbal del [s] Delay for generator current assymetry Step: 0.1 s Range: 0 – 60.0 s Gen >V Sd [%] Shutdown level for generator overvoltage. All three phases are checked. Maximum out of three is…

  • 43, ComAp InteliLite MRS10 Sensor specification To correct measuring error of each analog input (pressure, temperature, level) calibrating constants within 10 % of measure range should be set. Three calibrating constants are set in physical units — bar, o C, % . From these constants are counted equivalent calibrating resistance which are internally (in software) add to sensor resistance. At the moment …

  • 18, „2“- e.g. 0.36 MPa „3“ — e.g. 0.366 MPa Set to: 1 When Analog input configuration is finished set the setpoints Wrn Oil press, Sd Oil press, Oil press del in Engine protection group. Each Analog input has separate triplet of setpoints: Wrn level, Sd level, Anl Inp del. Names of these setpoints are fix defined Number of decimal poi…

  • 57, The complete description of Modbus communication protocol can be found in Modbus Protocol Reference Guide PI-MBUS-300 and Open Modbus Specification Release 1.0. Both documents are available from web site at http://www.modicon.com/openmbus/ . Communication object vs. Register All the data intended for communication has its representation as communication objects in the controller…

  • 10, ComAp InteliLite MRS10 Getting started How to install General To ensure proper function: Use grounding terminals. Wiring for binary inputs and analog inputs must not be run with power cables. Analog and binary inputs should use shielded cables, especially when length >3m. Power supply To ensure proper function: Use min. power supply cable of 1.5mm 2 Maximum continuous DC power supply voltage is 36VDC. Ma…

  • 8, Dimensions IL-CU iL 185 (7,3″) 170 (8,87″) 4 2 , 5 ( 1 , 7 » ) 4 5 ( 1 , 8 » ) 1 2 1 2 1 3 0 ( 5 , 1 » ) 1 2 3 ( 4 , 8 » ) 1 1 3 ( 4 , 4 » ) 1 Cutout for InteliLite 113 x 175 mm (4.4 x 6,9“) Only for service purpose IL-MRS 10, 11 IL-MRS 15, 16 AT-LINK-CONV InteliLite MRS 15 iL 185 (7,3″) 170 (8,8…

Recommended Instructions:

TH-37PG9W, 3107, CAD-1610-SE, PLC-WL2500, T743

  • =========================================== Adaptec RAID Release dated: April 22, 2008 =========================================== This release notes contain the following: 1. Description of the Release 2. Supported Controllers 3. Enhancements and Bugfixes 1. Description of the Release: =============================== This is the official software releas …

    RAID 51245 2

  • 1 FREEZER CONTROLLER Model FA3F ATTENTION …

    FA3F 3

  • Installation Instructions Issue Date April 9, 2014 © 2014 Johnson Controls, Inc. 1 Part No. 24-10174-26, Rev. B www.johnsoncontrols.com FX Supervisory Controllers Modem Card Installation InstructionsApplication The modem option card (Figure 1) provides 56 Kbps auto-dial/auto-answer modem communications capability to the FX Supervisory Controllers. FIG:Md …

    FX Series 4

Additional Information:

Popular Right Now:
Operating Impressions, Questions and Answers:

Описание на модульный контроллер ComAp MRS10-11-15-16Это описание очень хорошо описывает модуль контроля CompApMRS10-11-15-16

  • InteliLite

    InteliLite MRS

    (IL-CU MRS10/11/15/16) : 3 ? 3 3 ( ) 3 ? 4 iGL — RA15 4 iG
    IOM/PTM 4 5 IL-CU 5 6 7 MRS 7 8 8 12 12 ( CAN) 17 18 IL-CU 18 18
    IL-CU 20 22 22 23 23 24 25 27 28 31 * IOM 31 * 33 , 34 34 35 J1939
    36 37 37 38 — MRS10/11/15/16 38 ? 38

  • 2

    ^ GCB /? 38 38 ? 39 ? 39 ? 39 41 42 43 43 43 44 44 (FLS) 45
    (WRN) 45 SD () 45 45 46 46 47 48 LiteEdit 48 Modbus 48 48 * ISD SDN
    48 * GSM 49 * SIM- 49 49 49 49 49 50 50 50 51 / 51 * RS232 51 * CAN
    51

  • 3

    ? MRS 10/11/15/16″, . ? , InteliLite MRS. : InteliLite . , . :
    RS232. REMOTE START/STOP ( /) GCB / InteliLite, . InteliLite . . :
    () () (MRS10 FW MRS10 HW) , . HARDWARE INCOMPATIBLE ( ). Boot
    LiteEdit; . . . «Basic settings» ( ). !!! !!! ( ) InteliLite iL-MRS
    . IL-MRS 15/16 . InteliLite , , . InteliLite , , . InteliLite .
    InteliLite . /, .

  • 4

    ? IL MRS InteliLite iGL -RA15 MRS15/16 iG-IOM/PTM / I/O MRS15/16
    AT-LINK-CONV RS232 MRS10/11 iGL — RA15 iGL-RA15 MRS15/16 CAN.
    LiteEdit — RA15. / LiteEdit. RA15. iG IOM/PTM iG-IOM iGS-PTM / : 8
    , 8 , 4 . MRS15/16. , iL. , iL, , PTM. IOM/PTM , . iG-IOM ( , iL) 0
    -2,4 . IOM VDO- . iGS-PTM 0-250, 0-100 mV, 0-20 mA. Pt100 . PTM
    VDO. iGS-PTM.

  • 5

  • 6

    CAN

  • 7

    MRS

    CAN Volvo Scania. . .

  • 8

    . . , >3m. : 1.5mm2 — 36V. — 39V. InteliLite . , . :
    InteliLite !! — 4A ( ). 12V InteliLite , , . 10V, 50 — 7V, . , .
    :

    . ; I-LBA.

  • 9

    1 . . . ( ) — T1A. .

    .

    , .

    : . 2,5mm2 .

  • 10

    .

    : 2,5mm2 5A.

    : !!!

  • 11

    . ail-. L1, L2 L3. L1l COM-.

    : : 200 % : 60,0 : 1.4 1 ( — 100% IL 1.4 ). IL-CU .
    LiteEdit.

    2,5 2. 5. L2I L3I .

  • 12

    . COM- . InteliLite. 120 IL-CU . 50% . COM IL. InteliLite: AI1
    AI2 AI3 IL COM-.

    0 — 2,4 . , >3m. IL-CU . (10 6 Bar) 4-20 mA. 4-20mA/100
    4-20mA/60. 50%. InteliLite. , ; 750 . , . — 750 , , 2400 . : : Bar,
    VDO, 0 — 10.0 bars. 3.5 bars, — 1.2 bars.

  • 13

    LiteEdit, Controller — Configuration Modify Oil Press. — Oil
    Press ( ) : Not used ( ) () . . : : Analog () Tri-state ( ) . . «»
    / COM- . / . «Tri-state» / COM- . : Analog : (0C, %, Bar, ). . :
    Bar : , . , . ,,NC» . ,,NO » . : . ,, » . InteliLite «####», .
    ,,Curve A» LiteEdit ( VDO ) ,,Curve B» LiteEdit B( VDO ) ,,Curve C»
    LiteEdit C ( VDO ) ,,Pt1000″ PT1000 IEC 751 ,,Ni1000″ Ni1000 DIN 43
    760 ,,VDO temp» VDO ,,VDO press» VDO ,,VDO level» VDO ,,4-20mA/60″
    120 COM- ,,4-20mA/100″ 120 COM- : VDO — : ,,0″ -, 360 kPa, 100%, 50
    C ,,1″ , 3.6 Bar ,,2″- , .0.36 MPa ,,3″ -, .0.366 MPa : 1

  • 14

    , Wrn () ( ), Sd () , del (Engine protection). : Wrn () (), Sd
    () . . — Wrn () () Sd () , .

  • 15

    ( CAN)

    CAN , ( , , ). 120 . CAN 200 . CAN . IL-CU COM. IL-CU 120 ; CAN.
    IG-IOM IGS-PTM — 120 ( ). . CAN. : IOM, PTM, . IL-CU IG-IOM IL-CU
    IGS-PTM IL-CU IGL-RA15 IL-CU IG-IOM IGL-RA15 IL-CU IGS-PTM IGL-RA15
    IL-CU IG-IOM IGS-PTM IGL-RA15.

  • 16

    : IL-CU LiteEdit. 1 . IL-CU BI1 / BI2 BI3 BI4 OFF () BI5 BI6 , .
    : . . , , EMERGENCY STOP » «. , , . : SprinklActive ( ) , , . , ,
    (OFF—TEST) . : . . (OFF) iL OFF () ( : OFF—TEST). . : . Start ,
    Start InteliLite. ().

  • 17

    Stop , Stop InteliLite. (). FaultRes ( ) , FaultRes InteliLite.
    Res ( ) , HornRes InteliLite. ^ GCB , GCB InteliLite. (). , . , —
    OFF (). , Stop . «Sd () Stop » . «Emerg Man» ( ) . , . , , . , /. ,
    () MODE (). , . IL-CU BO1 ( ) BO2 ( ) BO3 GCB / BO4 BO5 BO6 . , ,
    .

  • 18

    . , : , / . /, 30 /. . /. () . . / / . , . , 2 / . GCB / MRS11,
    16: . MRS10 15 ( GCB/ GCB): ( () , MinStabtime elapsed, . GCB . GCB
    () . GCB UV . *AnInIOM14 Wrn () , IOM/PTM. , , FAULT RESET
    *AnInIOM14 Sd () , IOM/PTM. , , FAULT RESET Prestart. , . : / = 0,
    : Poil, D+ ( ). OK

  • 19

    iL. , . , . , FAULT RESET / . , . : FAULT RESET HORN RESET (Horn
    timeout) / . , : OFF () , . GCB . , , . 10 / < 2 < 10 VAC,
    < : . MainsParams OK IL. , . ChrgAlternFail , , D+ . , , FAULT
    RESET : D+ 80% . Vgen , / . . . , , FAULT RESET Fgen , / . . ,
    FAULT RESET

  • 20

    , . , , FAULT RESET , , , . 60 . , , FAULT RESET , . . , , FAULT
    RESET , . . , , FAULT RESET , . , , FAULT RESET , : * , . . , ,
    FAULT RESET , iL (, — ). , , FAULT RESET V , / . , , FAULT RESET
    Wrn () . , FAULT RESET Sd () , . , No Sd ( ) FAULT RESET , . . , No
    warning ( ) FAULT RESET

  • 21

    , . . , , FAULT RESET Wrn () , . . , , FAULT RESET Water Temp (
    ) , . . , , FAULT RESET Water Temp Wrn ( ) , . . , , FAULT RESET
    OFF () , OFF () . () , () . () , () . FuelLevel ( ) , .
    FuelLevelWrn ( ) , . . , . , . . , , FAULT RESET BI16 stat ()
    *BI18IOM — . , , , . , FAULT RESET , , . CommOK ####, . , .

  • 22

    PwrRelay ( ) , . YellowLamp ( ) . RedLamp ( ) . CtrlHeartBeat ()
    . 500ms : 500ms. . Stop Pulse ( ) 1 Stop solenoid. . CommError
    CommOK, .. , , , #####. .

  • 23

    0 — 2400 . , bar, C ( F) %. . 2.0 : . VDO — 0 — 10.0 bars. . t
    VDO — 0 — 100 C. . VDO — 0-180R = 0-100% 4 . . ENTER. ENTER. : . ,
    InteliLite . 14 LiteEdit. [kW] :1kW : 1 4000 kW [ A ] It is *IDMT ,
    . : *2INo m del, Ishort. . :1 A : 1 — 5000 A CT Ratio [/5A] .

  • 24

    :1 A : 1 5000 A / 5A *PT [/1] :0,1 V / V : 0,1 500,0 V / V [V] (
    — ) :1V : 100 300 V [Hz] ( 50 60 Hz ) :1Hz : 45 65 Hz [-] — , , .
    0, . . :1 :0 500 : , ( 5V) . /[/] . :1 / :100 4000 / FltRes
    [ENABLED ()/ ()] (): () . ENABLED (): (o TEST) () . . TO[min] . :1
    min :0 60 min : 0 , . [OFF, , ] , MODE. : . * RS232
    [STANDARD/MODBUS/CumminsMB] . Standard: LiteEdit.

  • 25

    Modbus: Modbus. CumminsMB: Cummins Modbus. : . Modbus. *- AA [ —
    ] — . :1 : 1 30 : — . . Start /[%] , iL ( ). :1% / :5 50 % POil
    [Bar] ( ). :0,1 bar :-10,0 1000,0 : ( ) : /, POil and D+ ( ). , .
    [s] PRE-START . 0, PRE-START . :1s :0 600 s MaxCrank time [s] . :1s
    :1 60 s CrnkFail pause[s] . :1s :5 60 s Crank attemps [-] :1 :1 10
    time[s] , / /. , / 2.

  • 26

    /NOMINAL , , . /NOMINAL . : 1 s : 0 600 s : , 5s , . Min stab
    time [s] / GCB. :1s :0 300 s Max stab time [s] . :1s :0 300 s : Max
    stab time, ( ). Stop time [s] . . :1s :0 600 s : , : / =0, <
    POil < 10 VAC. , , , /=0, > 10V. [s] . :1s :0 3600 s [
    NOMINAL / ] /NOMINAL. NOMINAL : , . : . : /NOMINAL . . Fuel
    solenoid [ DIESEL / GAS ] FUEL SOLENOID ( ).. DIESEL: 1 STARTER. .
    GAS: IGNITION (), / 30 / ( ).

  • 27

    . D+ function [ENABLED ()/CHRGFAIL/ ()] ENABLED (): D+ , .
    CHRGFAIL: D+ . (): D+ . : . D+ . FreqSelect
    [PRIMARY/SECONDARY/DEFAULT] (// ) Volvo Scania. Volvo
    «Volvo-MarineD12 Aux» : VP Status. Scania «Scania S6 Singlespeed» :
    1 2 DLN1, , .. /No minal (/) . ( ), FreqSelect . Eng prot del[s] (
    ) (, ). . Start /. :1s : 0 300 s Horn timeout[s] ( ) . 0, HORN .
    :1s : 0 600 s [%] . :1% / : 100 150% AnlInp1 level1[ Bar] 1 : 0,1
    bar : AnlInp1 level2 10000 AnlInp1 level2[ Bar] 1 : 0,1 bar : -100
    AnlInp1 level1

  • 28

    AnlInp1 del[s] 1 : 1 s : 0 180 s AnlInp2 level1[ ] 2 : 1 C :
    -100 Anlinp2 level2 AnlInp2 level2[ ] 2 : 1 C : AnlInp2 level1
    10000 AnlInp2 del[s] 2 : 1 s : 0 180 s AnlInp3 level1[ ] 2 : 1 % :
    AnlInp3 level2 10000 AnlInp3 level2[ ] 3 : 1 % : -100 AnlInp3
    level1 AnlInp3 del[s] 3 : 1 s : 0 180 s Batt undervolt[V] ( ) .
    :0,1 V :8V Batt undervolt Batt overvolt [V] ( ) : :0,1 V :Batt
    overvoltage 40 V del [s] . :1s :0 600 s NextServTime[h] . 0 . :1 :0
    65535h

  • 29

    : . [%] (% ) :1% :0 200% del[s] . :0.1s :0 60.0 s Ishort[ % ] ,
    . :1 % :100 — 500 % *2INo m del[ s ] IDMT. 2INo m del IDMT 200% .
    Igen = 2* . :0,1 s : 0,1 — 20 s IDMT . , :

    2INo m del * Reaction time =

    Igen — : 900 sec = 15 minutes. IDMT 15 . Igen . . 200% — 2INo m
    del.

    200% =

    2INo m del 100% 101% 110%

    0,2 20 2 2 200 20

    20 ( >900 )

    200

  • 30

    Curr unbal[%] (). :1% : 1 200% Curr unbal del [s] :0.1 s : 0
    60.0 s >V Sd ()[%] . . . :1% :

  • 31

    . :0.1s : 0 60.0 s >f[%] . :0.1% :

  • 32

    AnlInIOM2 lev1[ ] IOM 2 — . :1 : -100 — +10000 AnlInIOM2 lev2[ ]
    IOM 2 — . :1 : -100 — +10000 AnlInIOM2 del [s] IOM 2. :1 s : 0 —
    180 s AnlInIOM3 lev1[ ] IOM 3 — . :1 : -100 — +10000 AnlInIOM3
    lev2[ ] IOM 3 — . :1 : -100 — +10000 AnlInIOM3 del [s] IOM 3. :1 s
    : 0 — 180 s AnlInIOM4 lev1[ ] IOM 4 — . :1 : -100 — +10000
    AnlInIOM4 lev2[ ] IOM 4 — . :1 : -100 — +10000 AnlInIOM4 del [s]
    IOM 4. :1 s : 0 — 180 s IOM/PTM . CalibrAInIOM 1,2,3,4 [.] IOM/PTM.
    . :1 : -1000 +1000

  • 33

    * — CAN bus/RS232 LiteEdit, (iG-IOM, iGL-RA15). ECU LiteEdit
    (version 2.0 ) , /. /: Standard J1939 engines Scania S6
    Cummins-MODBUS

    Cummins RS232, : RS232 = CUMMINSMB. . , , . ####, . CommOK , ..
    , . PwrRelay , . CAN (Volvo Scania). J1939 . , ( ) J1939 Scania
    J1939 Scania S6, / : 5.2.1.9 ( 5.3.7 EEC1) 5.2.5.28 ( 5.3.29 Engine
    Fluid Level/Pressure)

  • 34

    5.2.5.5 ( 5.3.28 Engine Temperature) 5.2.5.61 — ( 5.3.19 Engine
    Hours, ) 5.2.1.7 ( 5.3.6 EEC2) 5.2.5.63 ( 5.3.32 Fuel EcoNo my)
    5.2.5.36 ( 5.3.36 Inlet/Exhaust Conditions) 5.2.5.4 1 ( 5.3.36
    Inlet/Exhaust Conditions) Cummins MODBUS «Cummins-Modbus», (
    QSX15,QSK45, QSK60): (Register Address:30001) (Register
    Address:30003) (Register Address:30002) — (Register
    Address:30008-30009) (Register Address:30018) (Register
    Address:30530 (QSK45, QSK60 only)) (Register Address:30531 (QSK45,
    QSK60 only)) — Standard J1939 SPN (Suspect Parameter Number ), FMI
    ( ) OC ( ); . SPM/FMI : SAE Truck and Bus Control and
    Communications Network Standards Manual, SAE HS-1939 Publication .
    : SPN:100 SPN:102 SPN:105 SPN:110 SPN:175 SPN:629 1 SPN:636 SPN:637
    — SPN:651 #1 SPN:652 #2 SPN:653 #3 SPN:654 #4 SPN:655 #5 SPN:656 #6
    SPN:677 SPN:1485 Scania: FC:1000-1001 FC:1100-1107 1 FC:1200-1207 2
    FC:2000-2002 FC:2100-2102 FC:2200-2202 FC:2400-2403 FC:2600-2601 1
    FC:2700-2701 2

  • 35

    FC:2800-2802 FC:3200-3205 FC:4300-4303 ( ) FC:6200-6201
    FC:6400-6401 FC:6600-6601 FC:6A00-6A01 FC:B000-B001 FC:B100-B101
    FC:B200 FC:B300 FC:C000-C006 PDE1 FC:C100-C106 PDE2 FC:C200-C206
    PDE3 FC:C300-C306 PDE4 FC:C400-C406 PDE5 FC:C500-C506 PDE6
    FC:C600-C606 PDE7 FC:C700-C706 PDE8 FC:E200 FC:E600 , , , , . , / ,
    , IG-IOM/IGS-PTM. InteliLite, , .

  • 36

    J1939

    (, , ) 10% . — bar, oC, %. , . ( ENTER) . AI1 (AI2).

    , CAN:

  • 37

    : iL-CU — 70 C, 73 C. AI1 +3 C ( ENTER) InteliLite (, .5) . (,
    70 C -> 73 C, 5 C -> 6 C). : (, 80C, 4.0 Bar ..) 1: 6 points
    VDO characteristic, pressure bar 2: 10 points VDO characteristic,
    temperature C 3: 2 points VDO fuel level sensor, 0% = 10 , 100% =
    180

  • 38

    . , MRS10/11/15/16

    1 MODE > (OFF -> -> ) 2.MODE < ( -> ->OFF ) 3
    HORN RESET — 4 FAULT RESET 5 START 6 STOP — 7. 8 GCB ON/OFF^ — 9
    PAGE (MEASUREMENT->ADJUSTEMENT) ( ) 10 , 11 , 12 ENTER 13. 14.
    15 GEN VOLTAGE PRESENT: , 16 GEN-SET FAILURE: , . FAULT RESET ( ) (
    ) 17 ^GCB ON: , GCB . GCB /. ? MODE: ( )

  • 39

    ^ GCB ON/OFF (/)? (AUTO) . (MAN) , . . : MEASUREMENT ()
    ADJUSTMENT (). -. PAGE. ? 1 PAGE MEASUREMENT (). 2 . ? 1 PAGE
    ADJUSTMENT (). 2 . 3 ENTER. 4 . 5 «*» . 6 ENTER. 7 . . 8 ENTER;
    PAGE . 9 PAGE . ? ENTER +/- . MEASUREMENT. ? ENTER, PAGE.
    InteliLite INFO (10 ). InteliLite INFO : 1) 2) InteliLite (8 ) 3) .
    4) Application: MRS16 5) Branch:Standard : MEASUREMENT. , ? —
    MEASUREMENT.

  • 40

    MEASUREMENT . . : Versions 1.4 and lower Version 2.0 and higher
    Description Wrn () * Wrn () Active No t accepted Wrn () Wrn ()
    Active accepted Wrn () * Wrn () Inactive No t accepted Inactive
    accepted FAULT RESET, . . , MEASUREMENT. : , . AMF25 Control
    LiteEdit. .

    1 2 , (L) (!) 3 4. 5 / 6 7 8 (, , .) V1-2, V2-3, V3-1 ph-ph V1,
    V2, V3 ph-N (triple bargraph) I1, I2, I3 (triple bargraph) IL-CU (
    )

  • 41

    ( ) ( ) ( ) IL-CU BI1 — BI6 IL-CU BO1 — BO6 : / , . * : / , . (
    ) ( ) ( ) ( ) — *- kWh () * kVAh () NextServTime * . J1939 ( SPN (
    ), FMI ( ) OC ( Occurrence Counter). . . , SPN ( ). EngOilPress WRN
    () BoostPress FLS EngOilTemp FLS 629(275h) FLS Controller#1
    EngCoolTemp WRN ()

  • 42

    SPN:110 OC:7 FMI:3 : FMI = 0 1, WRN (). FMI FLS.

    NEXT SCREEN ENTER PAGE

  • 43

    OFF () No start is possible Outputs STARTER, GCB / and FUEL
    SOLENOID are Not energized. No reaction if buttons START,STOP,^GCB
    ON/OFF are pressed. . . MAN () START . ^GCB ON/OFF GCB. GCB, . ,
    GCB ON/OFF STOP — . : . MAN () . , REM START/STOP . — () MODE = (
    START STOP / ) MODE = ( REM START/STOP) StateConditionAction Next
    state Start request PRESTART on Prestart / > 2 GenStop (Stop
    fail)> 10V OFF () / < 2, , Vgen < 10V, Prestart 3 STARTER
    Cranking () FUEL SOLENOID on 4 MaxCrank time counter started
    Cranking3 /> Start / STARTER off PRESTART off D+ STARTER off
    Cranking > 25% VgNom PRESTART off StateCondition of the
    transition ActionNext state MaxCrank time elapsed, 1st
    attemptSTARTER off Crank pause ( ) FUEL SOLENOID off STOP SOLENOID
    on CrankFail pause timer started () MaxCrank time elapsed, last
    attemptSTARTER off (Start fail) PRESTART off CrankCrankFail pause
    elapsed STARTER on Cranking pause3FUEL SOLENOID on 4 STOP SOLENOID
    off MaxCrank time counter started

  • 44

    380% speed reached TO LOAD on 1Running Min, MaxStabTime counter
    started / = 0 or any other condition FUEL SOLENOID off STOP
    SOLENOID on 60 sec Elapsed FUEL SOLENOID off (Start fail) STOP
    SOLENOID on RunningStop request TO LOAD offCooling Cooling time
    timer started / = 0 or any other condition TO LOAD off 2 FUEL
    SOLENOID off GCB / closed ed GCB / openedRunning / = 0 condition
    FUEL SOLENOID off STOP SOLENO ID on TO LOAD off CoolingCooling time
    elapsedFUEL SOLENOID offStop STOP SOLENOID on / = 0 or any other
    condition FUEL SOLENOID off STOP SOLENOID on Start 1Running Stop/ =
    0, , Vgen

  • 45

    Warning (WRN ()) When warning comes up, only outputs and common
    warning output are closed. Possible warnings: See List of possible
    events (SD (HORN) ) InteliLite GCB /, FUEL SOLENO ID, STARTER
    PRESTART . InteliLite , / . : InteliLite : L1, L2, L3. (, L1,L3,L2
    L2,L1,L3), : G ph opposed = // OK, 180. : GEN L1 neg= L1 GEN L2
    neg= L2 GEN L3 neg= L3 . . G ph+L1 neg = 1L1 G ph+L2 neg = 1L1 G
    ph+L3 neg = 1L1 : , >50VAC 120 20. 1 . Fls , 6,2% . ####. :
    Ready

  • 46

    Prestart . . Cranking Pause , Running , GCB OPEN/CLOSE Stop ,
    Ready Cooling Oil Press Wrn () WRN () YES . Oil Press Sd () SD
    (HORN) NO Water Temp Wrn () WRN () YES . Water Temp Sd () SD
    (HORN)NO . Fuel Level Wrn () WRN () YES . Fuel Level Sd ()SD
    (HORN)NO . Analog inp IOM/PTM — Wrn ()WRN () YES IG-IOM/IGS-PTM.
    Analog inp IOM/PTM — Sd ()SD (HORN) YES IG-IOM/IGS-PTM. YES
    eWarning/ IL-CU. WRN () YES / Battery flat SD (HORN) YES — , .
    Start failure SD (HORN) YES . ParamFailNONE NO Happends Vgen SD
    (HORN) YES s. Vgen unblSD (HORN) NO , . Fgen SD (HORN)YES . Igen
    unblSD (HORN) NO 0 . SD () YES . SD () YES , , . SD ()YES , — / , .
    . Emergency Stop SD () NO , . PickupFault SD () NO . Stop failSD ()
    YES . Wrn () ServiceTimeWRN () NO . , — . ChrgAlternFailWRN () YES
    . SprinklActive WRN () NO , . *Wrn () RA15 failWRN () IGL-RA15.

  • 47

    *Sd () IOM failSD NO IG-IOM/IGS- PTM. Wrn () NO . InteliLite
    RS232. ** iL MRS15/16 RS232. ** iL MRS10/11 RS232 AT-LINK-CONV ( )
    . : , COM- ( DC- ) . , . 240/20 ( GND () ).

    5 — GND () 2 — RxD 3 — TxD 5 — GND () 2 — RxD 3 — TxD 230 . 0 .
    GND () RS 232 . — LiteEdit ( ) LiteEdit ComAp ( Windows 95 ).
    LiteEdit : * Modbus iL RS232

  • 48

    9600 bps, 8 data bits, 1 stop bit, No parity RTU 3 ( Read
    Multiply Registers) 6 ( — Write Single Register) 16 ( — Write
    Multiply Registers) 4.096 ms . Modbus Modbus Protocol Reference
    Guide PI-MBUS-300 Open Modbus Specification Release 1.0. t
    http://www.modicon.com/openmbus/ . , , . 16- . , Modbus, 16- . . .
    . : , IL , LiteEdit. * ISD SDN Askey TAS-200E ASUScom TA-220ST *
    GSM Wavecom M1200 ( WMOD2; baud rate to 9600 bps) Siemens M20
    Siemens TC35 FALCOM A2D GSM GSM . AT GSM IL-. LiteEdit: MS
    Windows-Start-Program files — LiteEdit Gm_setup.exe. COM port iG-CU
    (=IS-CU) iG-MU Setup GSM odem Setup baud rate GSM — 80 — 90 Bps. :
    (IL ) . * Mobile SIM- SIM- GSM : ( ) PIN- 8-36 .

  • 49

    0,5-0,1A . : 50ms 10, . 8 ( InteliLite 3.2 ). 2 % 24. : 7 .
    IL-CU -20..+700C IL-CU-LT# -30..+700C -30..+800C IP65 95% : Low
    Voltage Directive EN 61010-1:95 +A1:97 Electromagnetic
    Compatibility EN 50081-1:94, EN 50081-2:96 EN 50082-1:99, EN
    50082-2:97 5 — 25 Hz, 1,6mm 25 — 100 Hz, a = 4 a = 200 m/s2 # —
    200C — + 700C, . InteliLite LT , . foil 50C, . IL-CU Standard Order
    code:IL-CU-LT -200C..+700C -300C..+700C -300C..+800C -300C..+800C .
    00C -150C -300C 12VDC 360 mA +50 mA +180 mA +300 mA 24VDC 230 mA
    +25 mA +85 mA +150 mA 36VDC 100 mA +20 mA +65 mA +100 mA -300C
    InteliLite LT , . (., ) . 180x120x55 800 50-60Hz 0,2% ( CT) 5 A ( )
    < 0,1 < 0,2 VA (In=5A) 10 A 2% 150 A / 1

  • 50

    . 12 A 231 (-) 400 () 290 (-) 0,6M (-) 0,3 M (-) 2 % — III
    (EN61010) 6 4,7k 0-36 . 0-2 V 8-36 V 2 — 100 000 12 A DC

    4 A DC 36 . 24 V / 0,1 A 500 Veff o 4 0,5 A 36 . 10 0 — 2,4 k 4
    % — ( ) 2 Vpk-pk ( 4 — 4 ) 50 Veff 4 10 k ( 6Vpk-pk) 0,2 % * RS232
    10 19.2kBd (STD) 9.6kBd (MODBUS) : ADVANTECH ADAM 4520: RS232 to
    RS422/485 converter, DIN rail, automatic RS485 bus supervision, No
    external data flow control signals, galvanic isolated. : ADVANTECH
    PCL-745B or PCL745S : Dual port RS422/485 Interface card, automatic
    RS485 bus supervision, No external data flow control signals,
    galvanic isolated * CAN CAN 200

  • 51

    250kBd 120 : () , , CAN 200 iS-COM: min. 75% (max. 4,4 ns/m)
    .0,25 2 ( 1 ) 2 dB / 100 : BELDEN (see http://www.belden.com):
    3082A DeviceBus for Allen-Bradley DeviceNet 3083A DeviceBus for
    Allen-Bradley DeviceNet 3086A DeviceBus for Honeywell SD (HORN)S
    3087A DeviceBus for Honeywell SD (HORN)S 3084A DeviceBus for
    Allen-Bradley DeviceNet 3085A DeviceBus for Allen-Bradley DeviceNet
    3105A Paired EIA Industrial RS485 cable LAPP CABLE (see
    http://www.lappcable.com) Unitronic BUS DeviceNet Trunk Cable
    Unitronic BUS DeviceNet Drop Cable Unitronic BUS CAN Unitronic-FD
    BUS P CAN UL/CSA

  • 52

    ( ) (MRS10/11/15/16): . . InteliLite IL-2.1 MRS16 30.11.2004 2,1
    0200FFFF MRS16-R:10.11.2004 2.1.ail InteliLiteNo 8637 Short string
    200 kW No 82761 4000 16 350 ANo 827515000 16 CT 2000 /5A No 82741
    5000 16 PT 1,0 /1No 9579 0,1500,0 16 231 VNo 827710022000 16 50 Hz
    No 8278 45 65 16 120No 82520500 16 / 1500 / No 8253100 4000 16
    FltRes No 9983 String list TO0 min No 101210 60 8 OFFNo 8315 String
    list RS232 STANDARD Yes 24522String list — AA3 Yes24512 130 8
    Engine params / 25 %No 8254550 8 Engine params POil4,5 Bar No 9681
    -10,0 1000,0 Integer 16 Engine params 2 s No 83940600 16 Engine
    params MaxCrank time 5 s No 8256 160 8 Engine params CrnkFail pause
    8 s No 8257 560 8 Engine params Crank attempts 3 No 8255 110 8
    Engine params time 12 s No 9097 0 600 16 Engine params Min stab
    time 2 sNo 8259 0300 16 Engine params Max stab time 10 s No 8313 0
    300 16 Engine params Stop time 60 s No 9815 0 600 16 Engine params
    Cooling time 30 s No 8258 03600 16 Engine params Cooling speed No
    10046 String list Engine params Fuel sole No I dDIESEL No 9100
    String list Engine params D+ function No 9683 String list Engine
    params FreqSelectPRIMARY No 10266 String list Engine protect Eng
    prot del 5 s No 8262 0 300 16 Engine protect timeout1 0 s No 8264 0
    600 16 Engine protect 115 % No 826350 150 16 Engine protect AnlInp1
    level1 2,0 Bar No 83691,0 1000,0 Integer 16 Engine protect AnlInp1
    level2 1,0 Bar No 8370 -10,02,0 Integer 16 Engine protect AnlInp1
    del 3 s No 8365 0 180 16 Engine protect AnlInp2 level1 80 C No 8375
    -10090 Integer 16 Engine protect AnlInp2 level2 90 C No 83768010000
    Integer 16 Engine protect AnlInp2 del 5 s No 8371 0180 16 Engine
    protect AnlInp3 level1 20 % No 83811010000 Integer 16 Engine
    protect AnlInp3 level2 10 % No 8382 -10020 Integer 16 Engine
    protect AnlInp3 del 10 s No 8377 0 180 16 Engine protect Batt
    overvolt 36,0 V No 9587 18,040,0 Integer 16 Engine protect Batt
    undervolt 18,0 V No 83878,036,0 Integer 16 Engine protect del 5 s
    No 8383 0 600 16 Engine protect 65534 h No 9648 065535 16 Gener
    protect 120 % No 82800200 16

  • 53

    Gener protect del 5,0 s No 82810,060,0 16 Gener protect Ishort
    250 % No 8282100 500 16 Gener protect 2INo m del 4,0 s No
    82830,120,0 16 Gener protect Curr unbal 50 % No 82841200 16 Gener
    protect Curr unbal del 5,0 s No 8285 0,060,0 16 Gener protect >V
    Sd () 110 % No 8291 70 200 16 Gener protect f1 10,0 % No
    829685,0200,0 16 Gener protect

  • 54

    L30 kW8526 Integer 16 kVAr08203 Integer 16 L1 08527 Integer 16
    L2 08528 Integer 16 L3 08529 Integer 16 0 kVA 8565 Integer 16 L1 0
    kVA 8530 Integer 16 L2 0 kVA 8531 Integer 16 L3 0 kVA 8532 Integer
    16 0,008204 Integer 8 L10,008533 Integer 8 L20,008534 Integer 8
    L30,008535 Integer 8 8395 18626 28627 38628 0,0 Hz 8210 16 V L1-N0
    V8192 16 V L2-N0 V8193 16 V L3-N0 V8194 16 V L1-L20 V9628 16 V
    L2-L30 V9629 16 V L3-L10 V9630 16 L10 A8198 16 L20 A8199 16 L3 0 A
    8200 16 I/O BInpIL001000 8235 16

  • 55

    I/O BOutIL000001 8239 16 Statistics kWhours08205 Integer 32
    Statistics kVArhours08539 Integer 32 Statistics NumStarts08207 16
    Statistics RunHours 0 h 8206 Integer 32 Statistics NextServTime
    65534 h9648 16 IL info TimerText 8954 16 IL info TimerValue0 s 8955
    16 IL info SW version2,18393 8 IL info SW branch18707 8 IL info
    Application 48480 8 IL info 09651 8 IL info DiagData 0 10050 32 IL
    info PasswordDecode2481875985 9090 32 RA15 module
    BOutRA150000000000000009849 16 IOM/PTM module AnInIOM 1 0 U48978
    Integer 16 IOM/PTM module AnInIOM 2 0 U58759 Integer 16 IOM/PTM
    module AnInIOM 3 0 U68760 Integer 16 IOM/PTM module AnInIOM 4 0
    U78761 Integer 16 IOM/PTM module BInpIOM000000008602 16 IOM/PTM
    module BOutIOM 00000000 8604 16 Fuel rate ##### L/h9860 16 ##### C
    9855 Integer 16 ManifoldTemp ##### C 9878 Integer 16 ##### Bar 9929
    16 Boost pressure0,0 Bar 9877 8 PercAtCS0 % 9925 8

Понравилась статья? Поделить с друзьями:
  • Рабочая инструкция кастелянши в рб в учреждении образования
  • Ттк написать жалобу руководству
  • Exprof краситель прямого действия инструкция по применению
  • Инструкция цифровой мультиметр dt 838 инструкция по применению
  • Инструкция цифровой мультиметр dt 838 инструкция по применению