Quick Start
Quick Start
OPTIMASS 1400
Twin, straight tube mass fl owmeter
Installation, assembly, start-up and maintenance may only be performed by appropriately
trained personnel. Check the nameplate for correct operating conditions.
For use in hazardous areas, special codes and regulations are applicable. Instruments must
not be connected to power supply before reading instructions described in the supplementary
manual.
This instrument complies with the requirements of the Pressure Equipment Directive. Please
refer to the nameplate for operating condition limits. Instruments must not be pressurised
before reading instructions described in the manual.
This instrument complies with the requirements of the Low Voltage Directive. Instruments must
not be connected to the power supply before reading the instructions described in the manual.
For devices used in SIL applications, additional safety notes apply. For detailed information
refer to the «Safety Manual».
The responsibility as to the suitability, intended use and corrosion resistance of the used
materials against the measured fl uid of this device rests solely with the operator.
For complete documentation (manuals, supplementary manuals, data sheets and certifi cates)
please refer to www.krohne.com/Downloads.
1 Installation
Special conditions of use to be observed
• The OPTIMASS measuring system and MFC converter must be included in the equipoten-
tial bonding system of any hazardous area installation.
• Allow the electronics to de-energise before opening the electronics enclosure inside a
hazardous area. The time needed to de-energise is 35 minutes for temp. class T6 and 10
minutes for Temp. class T5. There is no waiting time for Temp. class T1
• Use certifi ed cable glands on cable entries. Use a certifi ed plug to seal unused cable
entries.
• Install connecting cables as fi xed wiring so that they are protected against damage.
Connecting cables must not exceed the parameters specifi ed in the Supplementary
Instructions for Hazardous Areas.
• For details on the relationship between: maximum permissible ambient temperature, maxi-
mum medium temperature, maximum surface temperature and the relevant temperature
class for each individual meter, please refer to the tables provided in the relevant meter
Handbook and/or the Supplementary Instructions for Hazardous Areas.
04/2020 — 4008121701- QS-OPTIMASS 1400-R01- en
For initial set up, we strongly recommend that you also refer to the relevant manual!
Handling the meter
Supporting the meter
Flange connections
Mounting positions
Self draining (hygienic)
Hygienic connections
If the hygienic installation requires the meter to
be self draining, mount the meter at an angle.
DO NOT mount the meter horizontally!
1
1
Table of Contents for KROHNE OPTIMASS 1400:
-
3 Cable connections (sensor and converter) Procedure 1 Unscrew the housing cover 1 2 Put the electrical cable/s through the related cable gland/s 4 3 Connect the conductors 2 4 Run the twisted sink wires and the braided screen under the earth clamp 3 5 Fix the clamp in place using the two screws 6 Tighten the cable gland/s 4 7 Replace the housing cover and tighten it with your hand 5 1 Signal converter 2 Flow sensor 3 Cable shielding 4 Shielding Display Converter keys 3 Quick setup 1 Display (ER1.0.x shown) 2 Optical operating keys Procedu
-
4 Contact To view all KROHNE locations and contact details visit: www.krohne.com Then “Select your country“ from the drop down list at the top left of the page Quick setup menu Measuring mode Select Menu Select menu and/or submenu Select function & set data Press for 2.5 s A Quick Setup A1 Language A2 Tag A3 Reset A3.1 Reset Errors A3.2 All Totalisers A3.3 Totaliser 1 A3.4 Totaliser 2 A3.5 Totaliser 3 A4 Ana
-
For initial set up, we strongly recommend that you also refer to the relevant manual! Quick Start 1 Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. Check the nameplate for correct operating conditions. For use in hazardous areas, special codes and regulations are applicable. Instruments must not be connected to power supply before reading instructions described in the supplementary manual. This instrument complies with the requirements of the Pressure Equipment Directive. Please refer to the namep
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of KROHNE OPTIMASS 1400 device using right now.
Detail Specifications: 1726/1726512-optimass_1400.pdf file (18 Feb 2023) |
Accompanying Data:
KROHNE OPTIMASS 1400 Measuring Instruments PDF Quick Start (Updated: Saturday 18th of February 2023 03:34:42 PM)
Rating: 4.7 (rated by 49 users)
Compatible devices: ALTOFLUX M900, LEVEL-SONIC BM90 Series, OPTISYS TSS 050 Series, OPTIMASS 2000, OPTIWAVE-M 7400, OPTIMASS 1000 Series, IFC 090, OPTISWITCH 5200C.
Recommended Documentation:
Text Version of Quick Start
(Ocr-Read Summary of Contents, UPD: 18 February 2023)
-
1, For initial set up, we strongly recommend that you also refer to the relevant manual! Quick Start 1 Installation, assembly, start-up and maintenance may only be performed by appropriately trained personnel. Check the nameplate for correct operating conditions. For use in hazardous areas, special codes and regulations are applicable. Instruments must not be connected…
-
2, KROHNE OPTIMASS 1400 2 CAUTION! If there is excessive vibration in the process pipework, you must isolate the meter from its mounting. It is recommended that you place an insert made from rubber (or similar material) between the meter body, or pipework, and the mounting clamp or fi xing point. For more information, contact the manufacturer. Danger: • Turn off the power supply befo…
-
3, 3 Cable connections (sensor and converter) Procedure 1 Unscrew the housing cover 1 2 Put the electrical cable/s through the related cable gland/s 4 3 Connect the conductors 2 4 Run the twisted sink wires and the braided screen under the earth clamp 3 5 Fix the clamp in place using the two screws 6 Tighten the cable gland/s 4 7 Replace the housing cover and tighten it with you…
-
4, 4 Contact To view all KROHNE locations and contact details visit: www.krohne.com Then “Select your country“ from the drop down list at the top left of the page Quick setup menu Measuring mode Select Menu Select menu and/or submenu Select function & set data Press for 2.5 s A Quick Setup A1 Language A2 Tag A3 Reset A3.1 Reset Errors A3.2 All Totalisers A3.3 T…
Recommended Instructions:
260 Series, FI-3005, POWER WAVE 11124, RoomMate, GT-P5210
-
ChallengerOptics.comWavelength Specic Optical Testing and Measurement EquipmentMPO Optical Power Meter- 12 berChallengerOpticsCO-OPM-MPO12OPERATING MANUAL1.0 Introduction . . . . . . . . . . . . . . . . 3 1.1 Special Features . . . . . . . . . . . . . 3 1.2 Specications . . . . . . …
CO-OPM-MPO12 9
-
Startup_HTA104-P_r1a Page 1 of 2 STARTUP INSTRUCTIONS: 1. Verify that the sensor probes are located where they meet EBTRON published installation guides. 2. Verify that the probes are properly spaced with the airflow arrows pointing in the direction of airflow. Improperly installed probes will compromise the installed accuracy of the device and degrade system performance. 3. Verify that t …
Advantage IV HTA104-P 2
-
Installation Guide RIGOL 1Rack Mount Kit MSO4000/DS4000 This rack mount kit is designed to mount RIGOL MSO4000/DS4000 series digital oscilloscope into a 19-inch cabinet that conforms to the Electronic Industries Association (EIA) standard. Kit Part Checklist No. Name Qty. Description 1 Front Plate 1 — 2 Right Plate 1 — 3 Left Plate 1 — 4 M4 Screw 4 M4x8 Phil …
MSO4000 Series 4
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Quick setup menu
ER 1.0.x
Measuring mode
Select Menu
Select menu and/or submenu
Press
for 2.5 s
A Quick Setup
A1 Language
A2 Tag
A3 Reset
A4 Analogue Output
A5 Digital Outputs
A6 GDC IR Interface
A7 Flow Direction
A8 Zero Calibration
A9 Operation Mode
04/2020 — 4008121701- QS-OPTIMASS 1400-R01- en
Select function & set data
A3.1 Reset Errors
A3.2 All Totalisers
A3.3 Totaliser 1
A3.4 Totaliser 2
A3.5 Totaliser 3
A4.1 Measurement
A4.2 Units
A4.3 Range
A4.4 Low Flow Cutoff
A4.5 Time Constant
A5.1 Measurement
A5.2 Pulse Value Unit
A5.3 Value p. Pulse
A5.4 Low Flow Cutoff
ER 2.x.x
Measuring mode
Select Menu
Select menu and/or submenu
Press
for 2.5 s
A Quick Setup
A1.0.0 Language
A2 Reset
A3 Confi guration
A 4.0.0 Safety Mode
A 5.0.0 SIL Verifi cation
A 6.0.0 Unlock Device
A 7.0.0 Calibrate Zero
A 8.0.0 Operation Mode
Select function & set data
A2.1.0 Reset Errors
A2.2.0 Stop all Simulations
A2.3.0 All Totalisers
A2.4.0 Totaliser 1
A2.5.0 Totaliser 2
A2.6.0 Totaliser 3
A3.1.0 Tag
A3.2.0 Measurement
A3.3.0 Range
A3.4.0 Alarm Code
A3.5.0 Low Flow Cutoff
A3.6.0 Damping
A3.7.0 Terminals C Type
A3.8.0 Flow Direction
Contact
To view all KROHNE locations and contact
details visit:
www.krohne.com
Then «Select your country» from the drop down
list at the top left of the page
4
Информация о товаре
Код Товара:
31870
SKU:
OPTIMASS 1400
OPTIMASS 1400 Кориолисовый массовый расходомер для универсальных применений и управления технологическим процессом OPTIMASS 1400 представляет собой экономически эффективный кориолисовый массовый расходомер со сдвоенной прямой трубой для газов или жидкостей в разнообразных стандартных применениях (д… →
-
Описание
-
Способы получения товара
-
Отзывов (0)
OPTIMASS 1400 Кориолисовый массовый расходомер для универсальных применений и управления технологическим процессом
OPTIMASS 1400 представляет собой экономически эффективный кориолисовый массовый расходомер со сдвоенной прямой трубой для газов или жидкостей в разнообразных стандартных применениях (до 170000 кг/ч). Расходомер предлагает функцию контроля вовлеченного газа (EGMTM) при измерении жидкостей; прибор работает даже при 100-процентном содержании вовлеченного газа
- Измерение массы, плотности и объёмного расхода газов и жидкостей; бесперебойное функционирование при наличии газовых фракций различного содержания и сложных условий потока (EGMTM)
- Также сертифицирован для использования в гигиенических применениях
- Фланец: DN15…100 / ½…4″, макс. PN100 / ASME класс 600; различные гигиенические фитинги3 x 4…20 мА, HART®7, FF, Profibus-PA/DP, Modbus, PROFINET, EtherNet/IP™, Bluetooth®
Отличительные особенности прибора
- Конструкция со сдвоенной прямой трубой
- Контроль вовлеченного газа (EGMTM): обеспечивает функционирование расходомера при наличии воздушных или газовых фракций в измеряемой среде
- Быстрая и полностью цифровая обработка сигнала
- Наилучшее в своём классе соотношение цены и качества
- Высокоточное измерение массы, плотности и объёмного расхода сред (±0,15 от ИЗ)
- Всесторонняя диагностика измерительного устройства и технологического процесса (включая NE 107)
- Встроенное измерение температуры
- Оптимизированная конструкция разделителя потока для минимизации потерь давления
- Опционально доступный взрывонепроницаемый внешний корпус, сертифицированный в соответствии с директивой PED, для давления до 100 бар изб / 1450 фунт/кв.дюйм изб
- Опционально доступная теплоизоляция, обогревающий кожух или отверстия для продувки
- Нечувствительность к перекрёстным помехам: невосприимчивость к монтажному положению и устойчивость к изменениям рабочих условий
- Поверка расходомера по месту эксплуатации с помощью диагностического устройства OPTICHECK
Типичные применения
Общее
- Стандартные технологические процессы при температуре до 130°C / 266°F
- Измерение расхода газов и жидкостей с газовыми включениями
- Мобильные установки на грузовых автомобилях, железнодорожных цистернах, передвижных стендах и т.д.
- Для сред с очень низкой плотностью (<10 кг/м3)
Пищевая промышленность и производство напитков
- Измерение расхода, плотности, удельного веса в процессах пивоварения
- Измерение расхода напитков и фруктовых соков
- Молочные продукты
- Жир, маслянистые и жиросодержащие продукты
- Дозирование добавочных пищевых компонентов
Фармацевтическая промышленность
- Розлив, дозирование, наполнение
- Экстракция растворителями
- Измерение расхода воды высшей степени очистки в магистральных трубопроводах
Химическая и иные перерабатывающие отрасли промышленности
- Крупнотоннажная загрузка
- Дозирование в реакторы
Судостроение и судоходство
- Измерение потребления топлива
Целлюлозно-бумажная промышленность
- Розлив и дозирование добавок, отбеливателей и красителей
Сектор водоподготовки и очистки сточных вод
- Дозирование флокулянтов
В нашем интернет-магазине Вы можете получить счет и договор поставки на это оборудование. Для оформления заказа нажмите «Купить» или позвоните по номеру тел.: +7(846)359-13-00.
Обеспечиваем сохранение всех гарантийных обязательств по поставке.
В случае необходимости подбираем аналог на данную позицию. Доставка в любой город России на склад ТК — бесплатно.
Нашли низкие цены — покупайте у нас ещё дешевле.
На нашем сайте представлены и другие товары известного производителя KROHNE Messtechnik GmbH.
Нет отзывов об этом товаре.