- Manuals
- Brands
- Softing Manuals
- Test Equipment
- BC-600-PB
- Manual
-
Contents
-
Table of Contents
-
Troubleshooting
-
Bookmarks
Quick Links
Manual
PROFIBUS Tester 4
BC-600-PB
FW version 1.13 (rev. 17)
Revision 2013-05-31
Related Manuals for Softing BC-600-PB
Summary of Contents for Softing BC-600-PB
-
Page 1
Manual PROFIBUS Tester 4 BC-600-PB FW version 1.13 (rev. 17) Revision 2013-05-31… -
Page 3
© Copyright 2013 Softing Industrial Automation GmbH No part of this manual may be reproduced, photocopied, stored on a retrieval system, transmitted, processed or translated without the express prior written consent. -
Page 4: Table Of Contents
Contents Introduction General Test Functions 1.2.1 Stand-alone mode of operation 1.2.2 PC mode of operation Delivery Scope Optional Accessories D-sub adapter cable for testing live systems Adapter Set for M12 Connection Technology Fieldbus Shield Digital Leakage Current Clamp Portable Power Supply Service Interface for PROFIBUS DP 3.5.1 Connection Type D-sub…
-
Page 5
Master Simulator and Topology Scan 7.4.1 Special case: Active devices at both ends of the bus Display and Control in Stand-Alone Mode Main Display Operating Concept Functions 8.3.1 Live Status function 8.3.1.1 Bus status summary 8.3.1.2 Segment status 1 8.3.1.3 Segment status 2 8.3.1.4 Station status… -
Page 6: Introduction
Introduction Manual Introduction General The PROFIBUS Tester 4 is a powerful tool that allows full testing of the bus physics and bus communication on PROFIBUS DP segments. Using the integrated master simulator, you can also test the bus physics if the PLC is currently not in operation, or individually check “suspicious”…
-
Page 7: Pc Mode Of Operation
BC-600-PB Introduction 1.2.2 PC mode of operation The PC software provides many additional features for performing, analyzing and managing bus tests. Quick Tests and Trends stored in the tool can be imported. In the PC mode four main functions are available. Two of them provide complex functionality that only experts need and that are accessed separately from the standard functionality.
-
Page 8: Delivery Scope
Wide-range power supply with European and US mains power cables • Connecting cable for direct power supply with 24 VDC • RS485 D-sub adapter cable BC-600-PB-CB-DSUB-2 “Standard” (cable petrol blue, light connector) for PROFIBUS DP • USB cable, 3 m •…
-
Page 9: Optional Accessories
(see page 23). Fig. 2: D-sub adapter cable with reduced influence on bus operation Softing Order No.: BC-600-PB-CB-DSUB-1 Adapter Set for M12 Connection Technology Using the M12 adapter set, you can connect the PROFIBUS Tester 4 to field devices with M12 connectors.
-
Page 10: Fieldbus Shield Digital Leakage Current Clamp
There is also an empty compartment for the fieldbus shield digital leakage current clamp in the carrying case of the BC-600-PB. Fig. 4: Fieldbus shield digital leakage current clamp Softing Order No.: PB-LSZ-CHB3…
-
Page 11: Service Interface For Profibus Dp
The compact unit is rail mounted like a terminal block and powered by an external 24 VDC power supply. The package includes an 90° angled PROFIBUS connector with a switchable terminating resistor. Fig. 6: D-sub service interface for testing a live bus Softing Order No.: BC-PBMB-PB-S Softing Page 11…
-
Page 12: Connection Type M12
The M12 service interface comprises an IP68 rated T piece, an end cap for the service output of the T piece, and a 1m PROFIBUS DP cable fitted with a male/female M12 connector on each end. Fig. 7: M12 service interface for testing a live bus Softing Order No.: BC-M12DP-PB Page 12 © 2013…
-
Page 13: Connectors And Controls
Function selection Back/Cancel Power Connection to Connection to notebook/PC power supply Status LED 24 VDC Trigger input Status LED Trigger Output Detail view: Terminal block for trigger input/output Fig. 8: Connectors and status displays on the BC-600-PB Softing Page 13…
-
Page 14: Power Supply And Auto Power On
Power Supply and Auto Power On Manual Power Supply and Auto Power On The tool is powered with 24 VDC either through the external AC adapter or by using the single-ended cable for direct 24 VDC power supply. Both are included in delivery.
-
Page 15: Power-Up Behaviour When Usb Connected
BC-600-PB Power Supply and Auto Power On Power-Up Behaviour when USB Connected Attention: The “PROFIBUS Diagnostics Suite” PC software also includes the required USB driver. You therefore need to install the software first before connecting the test tool to the PC or notebook.
-
Page 16: Software Installation
ROM does not start automatically when inserted, please run the “start.exe” file in the main directory. Future updates can be downloaded from our web site at industrial.softing.com. Attention: The “PROFIBUS Diagnostic Suite” PC software also includes the required USB driver. You therefore need to install the software first before connecting the test tool to the PC or notebook.
-
Page 17: Connection Types
7.1.3 Adapter cable The PROFIBUS Tester 4 is supplied with the D-sub adapter cable BC-600-PB- CB-DSUB-2 „Standard“ (light connector). For testing on live systems the optional D-sub adapter cable BC-600-PB-CB-DSUB-2 is recommended. An M12 adapter set is optionally available, see on page 9.
-
Page 18: Strain Relief
Connection to PROFIBUS Manual 7.1.4 Strain relief Attention: When you connect the PROFIBUS Tester 4, its weight can place a high mechanical stress on the connectors and the bus station. Ensure proper strain relief by using suitable supports, cable ties, etc. When this is not possible, you need to select a different connection point to avoid damage.
-
Page 19: Simple Connection For Tests During System Shutdown
BC-600-PB Connection to PROFIBUS Simple Connection for Tests During System Shutdown If all bus stations provide D-sub connectors with an additional service socket, you can simply plug in the PROFIBUS Tester 4 at that socket (see figure below). If a D-sub connector does not provide a service socket, you can plug in the D-sub adapter cable underneath.
-
Page 20: Connection For Testing A Live Bus
PROFIBUS; in other words, you need to shut down the whole installation. Attention: For testing on live systems the optional D-sub adapter cable BC-600-PB-CB-DSUB-1 with reduced influence on bus operation is highly recommended! See page 9. Page 20…
-
Page 21: Connection Via D-Sub Connector With Service Socket
BC-600-PB Connection to PROFIBUS 7.3.1 Connection via D-sub connector with service socket If all bus stations provide D-sub connectors with an additional service socket, you can simply plug in the PROFIBUS Tester 4 at that socket (see figure below). Remote I/O…
-
Page 22: Direct Cable Connection
Connection to PROFIBUS Manual 7.3.2 Direct cable connection To test a live PROFIBUS, you will need additional D-sub service interface of the type BC-PBMB-PB-S (see page 11). Diagnostic repeater PBMB PBMB PBMB D-sub Connection points Fig. 15: Service interface provide connection points at direct cable connection Page 22 ©…
-
Page 23: Connection Via M12 Connector
BC-600-PB Connection to PROFIBUS 7.3.3 Connection via M12 connector Tests on a live PROFIBUS are only allowed on bus segments providing D-sub connection technology. Only D-sub connectors with service socket can be used as connection points for the test tool. For this reason, tests can often only be performed at a bus end.
-
Page 24
Both features can only be used during shutdown of the installation. The D-sub cable BC-600-PB-CB-DSUB-2 which is included in the standard scope of supply must be used. As long as communication is detected on the bus, i.e. at least one device is an active master, the functions are disabled. If necessary, disconnect every single active device (PLC, MPI and, if necessary, diagnostic repeaters) from the power supply or the bus. -
Page 25: Special Case: Active Devices At Both Ends Of The Bus
BC-600-PB Connection to PROFIBUS Attention: Bus stations must only be disconnected from the power supply or the bus during shutdown of the installation. Attention: The two functions can be started also when the PROFIBUS Tester 4 is disconnected from the bus. If you then connect the…
-
Page 26: Display And Control In Stand-Alone Mode
Display and Control in Stand-Alone Mode Manual Display and Control in Stand-Alone Mode The PROFIBUS Tester 4 always starts in stand-alone mode unless it is USB connected to a PC or notebook. The readings are shown on the display. You can control the tool with the four function keys.
-
Page 27
BC-600-PB Display and Control in Stand-Alone Mode The PROFIBUS status is shown in line 2. The following displays are possible: 3. The PROFIBUS is not connected: • Display: “DP n/a” 4. The PROFIBUS is connected, but no master is active: •… -
Page 28: Operating Concept
Display and Control in Stand-Alone Mode Manual Operating Concept Fig. 20: Display control with the four function keys Page 28 © 2013…
-
Page 29: Functions
BC-600-PB Display and Control in Stand-Alone Mode Functions 8.3.1 Live Status function The Live Status function very quickly gives you an overview of the bus status. Even transient disturbances during the test are reliably detected. Once you start the function, the tool determines and continuously updates the status for the segment and for each bus station.
-
Page 30
Display and Control in Stand-Alone Mode Manual Bus physics: 1. “Error” • One or more bus stations failed to respond during the last physical test cycle „Warning“ • One or more quality indexes* are below the user-defined limit value (default: 2500) „OK“… -
Page 31: Segment Status 1
BC-600-PB Display and Control in Stand-Alone Mode 8.3.1.2 Segment status 1 Fig. 22: Live Status with segment status 1 To the right of “DP Segm.” in line 1, the display shows changes in the live list (added and dropped bus stations). The following displays are possible: 1.
-
Page 32: Segment Status 2
Display and Control in Stand-Alone Mode Manual 8.3.1.3 Segment status 2 Fig. 23: Live Status with segment status 2 Line 1 is the same as for segment status 1. In line 2 you see, on the left, the number of retries on the entire segment and, on the right, the worst quality index of all bus stations.
-
Page 33: Station Status
1. The letter in the middle indicates whether the device is a master (M) or slave (S). If the letter is enclosed in square brackets, the BC-600-PB was able to determine the address of the PROFIBUS device to which it is connected.
-
Page 34: Quick Test Function
Display and Control in Stand-Alone Mode Manual 8.3.2 Quick Test function The Quick Test allows full testing of bus physics and bus communication. The test data is stored in the tool. It can subsequently be imported by the PROFIBUS Diagnostics Suite software application. To start the function, choose one of 10 internal memory locations.
-
Page 35: Trend Function
BC-600-PB Display and Control in Stand-Alone Mode 8.3.3 Trend function Trend logging is used for detecting rare or sporadic faults over a prolonged period of time. The function monitors both the bus physics and critical events in the bus communication. The PROFIBUS Tester 4 can automatically test the bus in stand-alone mode from within the control cabinet for up to 41 days.
-
Page 36: Master Simulator Function
Display and Control in Stand-Alone Mode Manual 8.3.4 Master Simulator function The master simulator is disabled by default when you switch on the tool. You can only select a baud rate on the display and thus start the master simulator if no other master is active.
-
Page 37: Data Import Into The Pc
BC-600-PB Data Import into the PC Data Import into the PC Quick Tests and Trend logs stored in the test tool can be imported into the PC software. To do this, start the PROFIBUS Diagnostics Suite. If a PROFIBUS Tester is connected to the PC via USB and contains stored test data, an additional “Import Test Data from Tool”…
-
Page 38: Firmware Update
Firmware Update Manual 10 Firmware Update Firmware updates are made available as required. They are provided with the updates to the PC software (see page 16) and allow access to new or improved functionality. How to update the firmware is described in detail in the separate “PROFIBUS Diagnostics Suite –…
-
Page 39: Maintenance And Servicing
BC-600-PB Maintenance and Servicing 11 Maintenance and Servicing The PROFIBUS Tester 4 is maintenance-free and does not require calibration. Repairs may only be carried out by the device manufacturer. All returns must be made in the supplied carrying case. Please also include a brief fault description and a phone number at which we can contact you should we need further details.
-
Page 40: Troubleshooting
PROFIBUS. Remedy: • Manually set the baud rate and repeat the test. If you need to contact Softing’s support team, you will find the contact data on the back cover of the manual. Page 40 © 2013…
-
Page 41: Specifications
BC-600-PB Specifications 13 Specifications Power supply Via external AC adapter 100 V .. 240 VAC 50/60 Hz (galvanically isolated) or direct connection to 24 VDC ±20%, approx. 0.5 A (without galvanic isolation) PROFIBUS D-sub connector (female), 9-pin, RS485 (DP) switchable power supply for ext. bus termination…
-
Page 42: General Notes
EN 61326-1 (Measurement, Control and Laboratory Equipment Product Standard) A Declaration of Conformity in compliance with the above standards has been made and can be inspected at Softing AG on request. NOTE: For compliance with the legal EMC requirements, the other components (PROFIBUS devices, AC adapter, etc.) must also meet these requirements.
-
Page 44
Softing industrial.softing.com Industrial Automation GmbH Tel. +49 89 45656-326 (Support) Richard-Reitzner-Allee 6 Tel. +49 89 45656–340 (Sales) 85540 Haar Fax +49 89 45656–488 Germany Email: support.automation@softing.com…
Introduction
1
Introduction
1.1
General
The PROFIBUS Tester 4 is a powerful tool that allows full testing of the bus
physics and bus communication on PROFIBUS DP segments.
Using the integrated master simulator, you can also test the bus physics if the
PLC is currently not in operation, or individually check «suspicious» bus
stations.
The tool is powered either through an external AC adapter, by direct
connection to 24 VDC or through an optional portable power supply unit.
1.2
Test Functions
The PROFIBUS Tester 4 automatically detects the baud rate or open circuit
voltage as soon as you connect it to a PROFIBUS DP segment.
You can then choose between two modes of operation for bus testing
depending on if you run it in stand-alone mode, or connect the PROFIBUS
Tester 4 to a PC or notebook. If required the master simulator can be enabled
in both modes if no other master is active.
1.2.1
Stand-alone mode of operation
In the stand-alone mode three test functions with simultaneous analysis of bus
physics and bus communication are available:
1. The Live Status shows the bus status and the details of the analysis
in real-time on the display.
2. To evaluate the bus health up to ten Quick Tests can be executed,
stored internally and imported by the PC software then.
3. To locate the causes of sporadic bus faults the long-term Trend logs
data for up to 41 days and stores them internally for later import by the
PC software.
Page 6
Manual
© 2013
- Обязательно представиться на русском языке кириллицей (заполнить поле «Имя»).
- Фиктивные имена мы не приветствуем. Ивановых и Пупкиных здесь уже достаточно.
- Не писать свой вопрос в первую попавшуюся тему — вместо этого создать новую тему.
- За поиск, предложение и обсуждение пиратского ПО и средств взлома — бан без предупреждения.
- Рекламу и частные объявления «куплю/продам/есть халтура» мы не размещаем ни на каких условиях.
- Перед тем как что-то написать — читать здесь и здесь.
-
vitiv
- здесь недавно
- Сообщения: 15
- Зарегистрирован: 14 фев 2016, 17:31
- Имя: Бабич Виталий Иванович
- Благодарил (а): 1 раз
Выбор тестера шины Profibus DP/PA
Сообщение
vitiv » 18 фев 2016, 16:49
Здравствуйте!
Помогите с выбором тестеров для шины Profibus.
Пытался найти информацию на данном форуме и в интернете но глухо. Для меня тема новая, на тестеры деньги выделяют и купить нужно обязательно, хотелось-бы сделать правильный выбор.
Планируется следующая конфигурация: контроллер Siemens S7 315 2PN/DP с подключенными по Profibus DP пятью коплерами FDC-157-0. К коплерам подключены по Profibus PA по 24 температурных датчика. Длина одной такой ветки Profibus PA около 450м.
Уже сейчас на стадии предварительной проверки выбранной конфигурации возникали проблемы со связью (спасибо данному форуму за информацию о том, что кабель Profibus DP между соседними устройствами должен быть не менее одного метра длиной ).
Какими тестерами стоит обзавестись, чтобы в дальнейшем легко решать возможные проблемы.
Пока выбор пал на следующие модели:
— Softing Profibus PA Tester BC-230-PB
— Клещи Softing PB-LSZ-CHB3
— Procentec Profibus Troubleshooting Toolkit Ultra Plus 37021
Буду рад услышать кто чем пользуется при наладке сети Profibus, отзывы, мнения, советы.
-
Serex
- эксперт
- Сообщения: 1970
- Зарегистрирован: 15 авг 2011, 21:36
- Имя: Пупков Сергей Викторович
- Страна: Россия
- город/регион: Москва
- Благодарил (а): 84 раза
- Поблагодарили: 123 раза
Выбор тестера шины Profibus DP/PA
Сообщение
Serex » 18 фев 2016, 19:26
Если не работает, то откидываешь все слэйвы, и подключаешь по одному, начиная с ближайшего по проводу. Смотришь обмен, как упало, там и бяка.
vitiv писал(а): кабель Profibus DP между соседними устройствами должен быть не менее одного метра длиной
Впервые слышу!. Были куски меньшего размера, все работает. Это может про коаксиальный кабель какой-нибудь фраза, там да, есть ограничения.
-
vitiv
- здесь недавно
- Сообщения: 15
- Зарегистрирован: 14 фев 2016, 17:31
- Имя: Бабич Виталий Иванович
- Благодарил (а): 1 раз
Выбор тестера шины Profibus DP/PA
Сообщение
vitiv » 18 фев 2016, 20:10
Про длину кабеля на форуме вот здесь прочитал. А подтверждение вот здесь нашел.
А тестер все-равно нужен, бегать от здания до датчиков по 400 метров быстро устану
-
VADR
- администратор
- Сообщения: 4385
- Зарегистрирован: 25 июл 2008, 07:12
- Имя: Диев Александр Васильевич
- Страна: Россия
- город/регион: г. Сегежа, Карелия
- Благодарил (а): 167 раз
- Поблагодарили: 289 раз
Выбор тестера шины Profibus DP/PA
Сообщение
VADR » 30 сен 2016, 00:10
Подниму тему.
Не далее, чем на днях, столкнулся с проблемой в сети Profibus DP. Разрулить получилось, но фактически вслепую, и проблема оказалась там, где я и предположить не мог. И думаю, очень мне помог бы в этом деле хороший тестер шины. А потому и вопросы:
1. Есть ли у кого-нибудь в эксплуатации такой прибор, хорошо зарекомендовавший себя в работе?
2. Кто-нибудь имеет опыт использования приборов типа Softing BC-600-PB (PB-T4)?
3. Что думаете о применении стационарных устройств, постоянно следящих за состоянием сети, типа PROFIBUS Inspektor BC-502?
Повторное использование кода не отменяет повторного использования мозга при его повторном использовании.
-
erv_asutp
- осмотрелся
- Сообщения: 125
- Зарегистрирован: 25 авг 2015, 11:55
- Имя: Ефименко Роман Владимирович
- Страна: Россия
- город/регион: Москва
- Благодарил (а): 1 раз
- Поблагодарили: 14 раз
Выбор тестера шины Profibus DP/PA
Сообщение
erv_asutp » 30 сен 2016, 08:38
Если предполагается разветвленная сеть или с длинными сегментами, или с переходами на подвижные объекты — всегда ставлю диагностируемые повторители типа 6ES7 972-0AB01-0XA0. Ни разу не подводили, а выручали очень часто. Можно, думаю, отнести к стационарным устройствам))
Тестером тоже пользовался, не помню уж как называется. Да, реально помогают, причем уже начиная со стадии монтажа, а для поиска неисправности вообще незаменим.
-
vitiv
- здесь недавно
- Сообщения: 15
- Зарегистрирован: 14 фев 2016, 17:31
- Имя: Бабич Виталий Иванович
- Благодарил (а): 1 раз
Выбор тестера шины Profibus DP/PA
Сообщение
vitiv » 30 сен 2016, 10:29
Прибор уже есть, выбрал PROFIBUS Tester 5 (BC-700-PB). Но в реальных условиях еще не тестировал. В офисе проверил работоспособность на небольшой сети Profibus DP, а в поле в скором времени (месяц, два) планируется проверка проложенной сети с датчиками Profibus PA. Для этого был докуплен к тестеру BC-700-H1 adapter. Сейчас прибор на руках, но нет доступа к Profibus сетям. Сейчас могу ответить на какие-то вопросы по тестеру, а позже и по самому тестированию.
-
VADR
- администратор
- Сообщения: 4385
- Зарегистрирован: 25 июл 2008, 07:12
- Имя: Диев Александр Васильевич
- Страна: Россия
- город/регион: г. Сегежа, Карелия
- Благодарил (а): 167 раз
- Поблагодарили: 289 раз
Выбор тестера шины Profibus DP/PA
Сообщение
VADR » 30 сен 2016, 17:41
erv_asutp писал(а): всегда ставлю диагностируемые повторители типа 6ES7 972-0AB01-0XA0. Ни разу не подводили, а выручали очень часто. Можно, думаю, отнести к стационарным устройствам
Так оно, судя по описанию, и есть стационарное устройство. А если коротко, не расписывая все функции, какую информацию там можно собирать по каждой линии? Судя по тому, что я там бегло вычитал, какую-то информацию он выдаёт мастеру в случае проблем, но только если контроллер 400-й серии. У меня 300-я, так что это не мой случай.
Отправлено спустя 2 минуты 42 секунды:
vitiv писал(а): Прибор уже есть, выбрал PROFIBUS Tester 5 (BC-700-PB). Но в реальных условиях еще не тестировал. В офисе проверил работоспособность на небольшой сети Profibus DP, а в поле в скором времени (месяц, два) планируется проверка проложенной сети с датчиками Profibus PA. Для этого был докуплен к тестеру BC-700-H1 adapter. Сейчас прибор на руках, но нет доступа к Profibus сетям. Сейчас могу ответить на какие-то вопросы по тестеру, а позже и по самому тестированию.
Там, где экспериментировали — что проверяли? Длины сегментов, помехи, повреждения кабеля, ошибки устройств — такую информацию он способен выдать?
Повторное использование кода не отменяет повторного использования мозга при его повторном использовании.
-
vitiv
- здесь недавно
- Сообщения: 15
- Зарегистрирован: 14 фев 2016, 17:31
- Имя: Бабич Виталий Иванович
- Благодарил (а): 1 раз
Выбор тестера шины Profibus DP/PA
Сообщение
vitiv » 30 сен 2016, 18:07
Проверял длины сегментов и уровень сигнала на каждом из узлов (в моём случае на каждом линке). Т.к. сеть была рабочая повреждений кабеля не проверял, но по описанию тестера, обрывы должен показывать.
-
VADR
- администратор
- Сообщения: 4385
- Зарегистрирован: 25 июл 2008, 07:12
- Имя: Диев Александр Васильевич
- Страна: Россия
- город/регион: г. Сегежа, Карелия
- Благодарил (а): 167 раз
- Поблагодарили: 289 раз
Выбор тестера шины Profibus DP/PA
Сообщение
VADR » 02 окт 2016, 21:25
апну тему, а то ушла из новых за выходные…
Повторное использование кода не отменяет повторного использования мозга при его повторном использовании.
-
erv_asutp
- осмотрелся
- Сообщения: 125
- Зарегистрирован: 25 авг 2015, 11:55
- Имя: Ефименко Роман Владимирович
- Страна: Россия
- город/регион: Москва
- Благодарил (а): 1 раз
- Поблагодарили: 14 раз
Выбор тестера шины Profibus DP/PA
Сообщение
erv_asutp » 07 окт 2016, 13:55
Кратко так:
Определение расстояний до ведомых устройств.
Индикация поврежденного участка сети и расстояния до места повреждения (обрыв, замыкание на экран, замыкание между жилами).
Светодиодная индикация повреждения линии связи и активного состояния сети.
Графическое отображение места повреждения в среде STEP 7 или COM PROFIBUS.
По поводу мастера даже не могу ничего сказать. Где вы прочитали, что только с S7-400? Работал и с 414, и с 414Н и с 315-2DP, проблем никогда не возникало.
-
geka
- Сообщения: 1
- Зарегистрирован: 15 фев 2017, 14:34
- Имя: Евгений
- Страна: РФ
- город/регион: Московская область
Выбор тестера шины Profibus DP/PA
Сообщение
geka » 16 фев 2017, 15:55
vitiv писал(а): vitiv » 30 сен 2016, 18:07
Проверял длины сегментов и уровень сигнала на каждом из узлов (в моём случае на каждом линке). Т.к. сеть была рабочая повреждений кабеля не проверял, но по описанию тестера, обрывы должен показывать.
Добрый день. Что можете сказать о работе с тестером 5 на сетях Profibus-DP , Profibus-PA на основании приобретенного опыта с сентября месяца? Так ли он необходим в работе? Очень важно. У нас ребром стоит вопрос о приобретении или нет этого прибора для проверки монтажа и наладки сети. С уважением.
-
vitiv
- здесь недавно
- Сообщения: 15
- Зарегистрирован: 14 фев 2016, 17:31
- Имя: Бабич Виталий Иванович
- Благодарил (а): 1 раз
Выбор тестера шины Profibus DP/PA
Сообщение
vitiv » 17 фев 2017, 10:05
До Profibus DP еще руки не дошли. В сети Profibus PA с помощью тестера определял причину недоступности датчика (Отключал от сети датчик, на его место садил тестер, если тестер сеть видит, проблема в датчике, иначе в контактах в месте соединения. Для соединения используем тройники Split Connect, а их разбирать собирать рекомендуют не более 4-х раз). При расстоянии линии около 400 м (в моем случае), после перемонтажа тройника тестер позволит сразу проверить состояние сети, а не бежать 400 м к контроллеру и обратно. Т.е. на данный момент тестер позволяет не бегать туда сюда и в принципе (если бегать) без него можно было бы обойтись. Но мы еще до конца сеть не наладили, поэтому более точно сказать, так ли уж нужен тестер, можно будет позже. Причем руки не дошли и до ПО идущего с тестером, которое должно давать больше информации и возможностей чем сам тестер.
-
besogon
- здесь недавно
- Сообщения: 6
- Зарегистрирован: 23 янв 2017, 08:36
- Имя: besogon
- Страна: Россия
Выбор тестера шины Profibus DP/PA
Сообщение
besogon » 10 мар 2017, 07:12
Доброе утро.
Работаем с тестером 5 (BC-700-PB) в сетях profibus dp. Может кто подскажет: в режиме «master simulator» возможно настроить получение ответа от slaves (simocode pro v, altivar 61/71)? GSD файлы скачаны, тестер определяет устройства вплоть до версии. Но хотелось бы получать ответы от slaves, по аналогии с обменом PLC — slaves. Или это в принципе невозможно? Спасибо.
Вернуться в «Интерфейсы, протоколы, связь»
Перейти
- Работа форума
- База знаний (Knowledge Exchange)
- ↳ Eplan Electric P8
- ↳ Общий F.A.Q.
- ↳ Общие вопросы
- ↳ Новости
- ↳ Ошибки
- ↳ Проект
- ↳ Изделия
- ↳ Устройства
- ↳ Соединения
- ↳ Кабели
- ↳ Клеммы
- ↳ ПЛК
- ↳ Компоновка 2D
- ↳ Макросы
- ↳ Eplan API
- ↳ Сценарии (Только готовые решения)
- ↳ Внешняя обработка
- ↳ ProPanel
- ↳ Инструкции ProPanel (Только готовые решения)
- ↳ Прочие направления Eplan
- ↳ FieldSys (Топология)
- ↳ Preplanning
- ↳ Harness proD
- ↳ EEC One
- ↳ Advantech
- ↳ F.A.Q., Инструкции
- ↳ Allen Bradley
- ↳ Общие вопросы
- ↳ ПЛК
- ↳ Операторские панели
- ↳ B&R Automation
- ↳ F.A.Q.
- ↳ Danfoss
- ↳ DEIF A/S
- ↳ Общие вопросы
- ↳ UNI-LINE
- ↳ MULTI-LINE
- ↳ MULTI-LINE 300
- ↳ Emerson
- ↳ Общие вопросы
- ↳ КИП и регуляторы
- ↳ DeltaV
- ↳ ОВЕН
- ↳ Прософт-Системы
- ↳ Общие вопросы
- ↳ ПЛК REGUL
- ↳ Schneider Electric
- ↳ Общие вопросы
- ↳ ПЛК
- ↳ Панели оператора
- ↳ SCADA
- ↳ Электротехника
- ↳ Приводная техника
- ↳ SIEMENS
- ↳ Общие вопросы
- ↳ LOGO!
- ↳ ПЛК SIMATIC (S7-200, S7-1200, S7-300, S7-400, S7-1500, ET200)
- ↳ Simatic Step7
- ↳ Simatic TIA Portal
- ↳ Simatic PCS 7
- ↳ Операторские панели
- ↳ WinCC
- ↳ Приводная техника (Sinamics, Micromaster, Masterdrive, Simoreg, Simotics)
- ↳ SmartGen
- ↳ Общие вопросы
- ↳ Промышленные (береговые) контроллеры
- ↳ Морские контроллеры и устройства
- ↳ WEINTEK (операторские панели)
- ↳ F.A.Q., Инструкции
- ↳ Архив
- ↳ Микроконтроллеры и электроника
- ↳ Arduino
- ↳ Raspberry
- ↳ Другие микроконтроллеры
- ↳ Электроника
- Общие вопросы АСУТП
- ↳ Общие вопросы
- ↳ Вопросы от студентов
- ↳ Литература
- ↳ Новости и отчётность
- ↳ Нормативы, ГОСТы, стандарты
- ↳ Информационная безопасность
- ↳ Проектирование и САПР
- ↳ Системная интеграция
- ↳ Разбор полетов
- ↳ Работа
- ↳ Заготовки для базы знаний
- ↳ Производство и технология
- ↳ MES — Системы автоматизации управления производством
- ↳ Метрология, КИП и датчики
- ↳ Исполнительные устройства, регуляторы
- ↳ Средний уровень автоматизации (управляющий)
- ↳ Алгоритмы
- ↳ Операторские панели
- ↳ Верхний уровень автоматизации (отображение)
- ↳ GE iFix
- ↳ Wonderware Intouch
- ↳ MasterScada
- ↳ SCADA+
- ↳ Альфа платформа
- ↳ Интерфейсы, протоколы, связь
- ↳ Радиосвязь
- ↳ Полезное ПО
- ↳ Электротехника, энергетика и электропривод
- ↳ Генераторы, электростанции и силовые агрегаты
- ↳ Теплотехника
- ↳ Подбор аналогов
- F.A.Q. (краткая выжимка из некоторых сообщений форума)
- ↳ Документация (вариант 1)
- ↳ Документация (вариант 2)
- ↳ Электротехника и электроэнергетика
- ↳ F.A.Q. по программируемым логическим контроллерам (PLC)
- ↳ Обсуждение F.A.Q. по PLC
- ↳ F.A.Q. по выбору PLC
- ↳ F.A.Q. по аппаратной части PLC
- ↳ F.A.Q. по языкам программирования
- ↳ F.A.Q. по структуре программ
- ↳ F.A.Q. по взаимодействию PLC с HMI
- О жизни
- ↳ Для дома, для семьи
- ↳ Комната смеха
- ↳ Электродвижение
Manual PROFIBUS Tester 4 BC-600-PB FW version 1.13 (rev. 17) Revision 2013-05-31 © Copyright 2013 Softing Industrial Automation GmbH No part of this manual may be reproduced, photocopied, stored on a retrieval system, transmitted, processed or translated without the express prior written consent. Contents Introduction 1 1.1 General 1.2 Test Functions 1.2.1 Stand-alone mode of operation 1.2.2 PC mode of operation 2 Delivery Scope 3 Optional Accessories 3.1 D-sub adapter cable for testing live systems 3.2 Adapter Set for M12 Connection Technology 3.3 Fieldbus Shield Digital Leakage Current Clamp 3.4 Portable Power Supply 3.5 Service Interface for PROFIBUS DP 3.5.1 Connection Type D-sub 3.5.2 Connection Type M12 4 Connectors and Controls 5 Power Supply and Auto Power On 5.1 Power-Up Behaviour without USB Connection 5.2 Power-Up Behaviour when USB Connected 6 Software Installation 6.1 Connection to a PC 7 Connection to PROFIBUS 7.1 Basics 7.1.1 Warning notice for testing a live bus 7.1.2 Connection types 7.1.3 Adapter cable 7.1.4 Strain relief 7.1.5 Test locations 7.2 Simple Connection for Tests During System Shutdown 7.3 Connection for Testing a Live Bus 7.3.1 Connection via D-sub connector with service socket 7.3.2 Direct cable connection 7.3.3 Connection via M12 connector 6 6 6 6 7 8 9 9 9 10 10 11 11 12 13 14 14 15 16 16 16 16 16 17 17 18 18 19 20 21 22 23 7.4 Master Simulator and Topology Scan 7.4.1 Special case: Active devices at both ends of the bus 8 Display and Control in Stand-Alone Mode 8.1 Main Display 8.2 Operating Concept 8.3 Functions 8.3.1 Live Status function 8.3.1.1 Bus status summary 8.3.1.2 Segment status 1 8.3.1.3 Segment status 2 8.3.1.4 Station status 8.3.2 Quick Test function 8.3.3 Trend function 8.3.4 Master Simulator function 8.3.5 Settings and help functions 9 Data Import into the PC 10 Firmware Update 11 Maintenance and Servicing 12 Troubleshooting 13 Specifications 14 General Notes 14.1 Lithium Battery 14.2 CE Conformity 23 25 26 26 28 29 29 29 31 32 33 34 35 36 36 37 38 39 40 41 42 42 42 Introduction 1 Manual Introduction 1.1 General The PROFIBUS Tester 4 is a powerful tool that allows full testing of the bus physics and bus communication on PROFIBUS DP segments. Using the integrated master simulator, you can also test the bus physics if the PLC is currently not in operation, or individually check “suspicious” bus stations. The tool is powered either through an external AC adapter, by direct connection to 24 VDC or through an optional portable power supply unit. 1.2 Test Functions The PROFIBUS Tester 4 automatically detects the baud rate or open circuit voltage as soon as you connect it to a PROFIBUS DP segment. You can then choose between two modes of operation for bus testing depending on if you run it in stand-alone mode, or connect the PROFIBUS Tester 4 to a PC or notebook. If required the master simulator can be enabled in both modes if no other master is active. 1.2.1 Stand-alone mode of operation In the stand-alone mode three test functions with simultaneous analysis of bus physics and bus communication are available: 1. The Live Status shows the bus status and the details of the analysis in real-time on the display. 2. To evaluate the bus health up to ten Quick Tests can be executed, stored internally and imported by the PC software then. 3. To locate the causes of sporadic bus faults the long-term Trend logs data for up to 41 days and stores them internally for later import by the PC software. Page 6 © 2013 BC-600-PB 1.2.2 Introduction PC mode of operation The PC software provides many additional features for performing, analyzing and managing bus tests. Quick Tests and Trends stored in the tool can be imported. In the PC mode four main functions are available. Two of them provide complex functionality that only experts need and that are accessed separately from the standard functionality. Standard functions: 1. The Network Status is a collection of information and test data relating to a PROFIBUS network. It provides the basis for a comprehensive evaluation of the bus health. o o o o Quick test and user-controlled test with simultaneous analysis of bus physics and bus communication Topology scan Test report Master simulator 2. If sporadic faults occur in a PROFIBUS installation, the quality indexes and critical protocol events should be monitored with the long-term Trend over a prolonged period to locate the causes of bus problems. Expert functions: 3. The function Frames enables the classic frame analysis. 4. The Oscilloscope permits the detail analysis of signal waveforms. Softing Page 7 Delivery Scope 2 Manual Delivery Scope The PROFIBUS Tester 4 comes in a carrying case comprising: • • • • • • • • Test tool with RS485 interface Wide-range power supply with European and US mains power cables Connecting cable for direct power supply with 24 VDC RS485 D-sub adapter cable BC-600-PB-CB-DSUB-2 “Standard” (cable petrol blue, light connector) for PROFIBUS DP USB cable, 3 m Terminal block for trigger input/output CD-ROM with driver software, PC software and detailed integrated help system in English and German PROFIBUS Tester 4 user manual and Getting Started manual for the PROFIBUS Diagnostics Suite PC software Fig. 1: BC-600-PB with carrying case Page 8 © 2013 BC-600-PB 3 3.1 Optional Accessories Optional Accessories D-sub adapter cable for testing live systems This D-sub adapter cable is optimized for reduced influence on live PROFIBUS DP segment operation. Thereby it is most suitable for testing of running plants. The risk of critical influences on bus operation which can cause a plant standstill is significantly reduced. Attention: Using this cable it is not possible to use the both active functions master simulator and topology detection (see page 23). Fig. 2: D-sub adapter cable with reduced influence on bus operation Softing Order No.: BC-600-PB-CB-DSUB-1 3.2 Adapter Set for M12 Connection Technology Using the M12 adapter set, you can connect the PROFIBUS Tester 4 to field devices with M12 connectors. The set comprises an M12 adapter cable with special pin layout and an M12 terminating resistor that you can screw on, if required. Fig. 3: Special adapter set for M12 Softing Order No.: BC-600-PB-CB-M12 Softing Page 9 Optional Accessories 3.3 Manual Fieldbus Shield Digital Leakage Current Clamp When routing PROFIBUS cables in high-interference environments, electromagnetic interference can affect the signal quality. By measuring the shield currents with the digital leakage current clamp, you can locate EMC problem areas and take appropriate countermeasures. The digital leakage current clamp is supplied in a handy case, including measuring cables. There is also an empty compartment for the fieldbus shield digital leakage current clamp in the carrying case of the BC-600-PB. Fig. 4: Fieldbus shield digital leakage current clamp Softing Order No.: PB-LSZ-CHB3 3.4 Portable Power Supply The portable power supply unit allows up to 4 hours of portable operation. The power supply kit also includes a charger and a carrying case. Attention: Mains connector type of charger station available for Europe only. Fig. 5: Portable power supply Softing Order No.: BC-MOST-PB Page 10 © 2013 BC-600-PB 3.5 Optional Accessories Service Interface for PROFIBUS DP 3.5.1 Connection Type D-sub The D-sub service interface provides a PROFIBUS access point for testing if the existing D-sub connectors have no service socket or if the bus stations are connected via a terminal block. The service interface can power the terminating resistor of the D-sub connector. You can thus use it as an active bus termination at the beginning or end of the bus. If the PLC allows dropping and adding bus stations on the live bus, you will need this external bus termination to be able to exchange the first and last bus stations without causing problems on the bus. The compact unit is rail mounted like a terminal block and powered by an external 24 VDC power supply. The package includes an 90° angled PROFIBUS connector with a switchable terminating resistor. Fig. 6: D-sub service interface for testing a live bus Softing Order No.: BC-PBMB-PB-S Softing Page 11 Optional Accessories 3.5.2 Manual Connection Type M12 The M12 service interface comprises an IP68 rated T piece, an end cap for the service output of the T piece, and a 1m PROFIBUS DP cable fitted with a male/female M12 connector on each end. Fig. 7: M12 service interface for testing a live bus Softing Order No.: BC-M12DP-PB Page 12 © 2013 BC-600-PB 4 Connectors and Controls Connectors and Controls RS485 Connection to PROFIBUS DP Display Status display & operation Function key 2 Detail selection Funktionstaste 3 Start Function key 1 Function selection Funktionstaste 4 Back/Cancel Power Connection to power supply 24 VDC USB Connection to notebook/PC Status LED Trigger input Status LED Trigger Output Detail view: Terminal block for trigger input/output Fig. 8: Connectors and status displays on the BC-600-PB Softing Page 13 Power Supply and Auto Power On 5 Manual Power Supply and Auto Power On The tool is powered with 24 VDC either through the external AC adapter or by using the single-ended cable for direct 24 VDC power supply. Both are included in delivery. Attention: Before being connected to the AC mains power, the PROFIBUS Tester 4 and the AC adapter must be acclimated to room temperature to avoid condensation. This may take up to 60 minutes. The tool switches on automatically when you connect it to a power supply. The display lights up and self-test starts. Attention: When the tool is connected directly to 24 VDC, there is no galvanic isolation to the external power supply. Insufficient potential equalization between the power supply and the PROFIBUS will lead to equalizing currents which can falsify the test results and, in the worst case, even destroy the PROFIBUS Tester 4 and part of the bus installation. In these cases, use of the supplied AC adapter is mandatory for operating the PROFIBUS Tester 4. On completion of initial setup, the PROFIBUS Tester 4 displays the following dialog in English: You can now select the desired display language. The following languages are available: German, English, French, Italian, Polish and Spanish. 5.1 Power-Up Behaviour without USB Connection The PROFIBUS Tester 4 starts up in stand-alone mode in this case (see page 26) and is immediately ready for testing. Page 14 © 2013 BC-600-PB 5.2 Power Supply and Auto Power On Power-Up Behaviour when USB Connected Attention: The “PROFIBUS Diagnostics Suite” PC software also includes the required USB driver. You therefore need to install the software first before connecting the test tool to the PC or notebook. On successful completion of the self-test, the PROFIBUS Tester 4 displays: Fig. 9: Power-up display when USB connected When you start the PROFIBUS Diagnostics Suite control and evaluation software on your computer and select the PROFIBUS Tester and a network for testing in its user interface, the test tool switches to PC mode. The display shows: Fig. 10: Display at testing with PC software While in PC mode, you can only display readings and operate the tool by using the control and evaluation software on the computer. At this point, you can also start a firmware update instead of using the control and evaluation software. See page 38. Softing Page 15 Software Installation 6 Manual Software Installation The “PROFIBUS Diagnostics Suite” PC software is provided on the included CD-ROM. You need administrator privileges to install the software. If the CDROM does not start automatically when inserted, please run the “start.exe” file in the main directory. Future updates can be downloaded from our web site at industrial.softing.com. Attention: The “PROFIBUS Diagnostic Suite” PC software also includes the required USB driver. You therefore need to install the software first before connecting the test tool to the PC or notebook. The installation and basic use of the PC software is described in the separate PROFIBUS Diagnostics Suite – Getting Started manual. 6.1 Connection to a PC Use the included USB cable to connect the tool to a PC or notebook. Power is also supplied from the USB interface. Attention: It is recommended to connect the unit directly to a USB port on the PC or notebook. When you use external USB hubs or notebook docking stations for connection, problems can occur. 7 Connection to PROFIBUS 7.1 7.1.1 Basics Warning notice for testing a live bus Attention: When you connect a test tool, side effects on the system under test are generally unavoidable. If the PROFIBUS is already disturbed to a certain degree or if Simatic Diagnostic Repeaters are used, the operation of the PROFIBUS might nevertheless be affected occasionally. Compliance with the connection notes is mandatory! Page 16 © 2013 BC-600-PB 7.1.2 Connection to PROFIBUS Connection types There are several ways to connect a bus station to a PROFIBUS network: • • Using connectors o D-sub connectors, most of which have an integrated terminating resistor and, optionally, an additional service socket o M12 connectors for environments requiring increased IP ratings o Special vendor-specific hybrid connectors; they are used in combination with special cables to supply power via the bus Using terminals for direct connection Due to the typical daisy-chain topology, the connection points of the bus stations are the only possible points for connecting the test tool in most cases. 7.1.3 Adapter cable The PROFIBUS Tester 4 is supplied with the D-sub adapter cable BC-600-PBCB-DSUB-2 „Standard“ (light connector). For testing on live systems the optional D-sub adapter cable BC-600-PB-CB-DSUB-2 is recommended. An M12 adapter set is optionally available, see on page 9. Attention: Use only the short original cables with special pin layout to connect the unit to a PROFIBUS network. Do not cascade more than two D-sub connectors with service sockets at the same time: Fig. 11: Unallowed cascading of D-sub connectors Active connection cables with integrated repeaters, such as Softing's BC-131PB, cannot be used for testing. Softing Page 17 Connection to PROFIBUS 7.1.4 Manual Strain relief Attention: When you connect the PROFIBUS Tester 4, its weight can place a high mechanical stress on the connectors and the bus station. Ensure proper strain relief by using suitable supports, cable ties, etc. When this is not possible, you need to select a different connection point to avoid damage. Fig. 12: Strain relief fittings 7.1.5 Test locations The PROFIBUS Tester 4 can basically carry out tests anywhere on a physical PROFIBUS segment. Please note that the use of repeaters creates separate physical segments that each need to be measured individually. For the best and most informative results, perform the tests at the beginning and end of each physical segment. If these test results indicate problems that cannot be clearly classified right away, you should carry out one or more additional tests at the centre. Page 18 © 2013 BC-600-PB 7.2 Connection to PROFIBUS Simple Connection for Tests During System Shutdown If all bus stations provide D-sub connectors with an additional service socket, you can simply plug in the PROFIBUS Tester 4 at that socket (see figure below). If a D-sub connector does not provide a service socket, you can plug in the D-sub adapter cable underneath. The only thing you need to keep in mind is that you should never cascade more than two D-sub connectors (see page 17). When using M12 connection technology, the M12 adapter cable is “looped” into the bus. It is essential to ensure proper termination at the beginning and end of the bus by using the terminating resistor provided with the M12 adapter set. Attention: All these simple connection types will divide the bus. You therefore need to shut down the PLC and all the devices connected to the PROFIBUS; in other words, you need to shut down the whole installation. Remote I/O PLC Remote I/O Remote I/O D-sub Connection points M12 Termination at begin and end of bus! or Fig. 13: Connection points at system shutdown Softing Page 19 Connection to PROFIBUS 7.3 Manual Connection for Testing a Live Bus To test a live PROFIBUS with the PROFIBUS Tester 4 during operation, appropriate connection possibilities have to be provided. If no suitable connection points are available in the existing installation, it is recommended to install them during system shutdown. This will make future maintenance work much easier. Attention: When installing additional connection points, you divide the bus. Before doing so, you therefore need to shut down the PLC and all the devices connected to the PROFIBUS; in other words, you need to shut down the whole installation. Attention: For testing on live systems the optional D-sub adapter cable BC-600-PB-CB-DSUB-1 with reduced influence on bus operation is highly recommended! See page 9. Page 20 © 2013 BC-600-PB 7.3.1 Connection to PROFIBUS Connection via D-sub connector with service socket If all bus stations provide D-sub connectors with an additional service socket, you can simply plug in the PROFIBUS Tester 4 at that socket (see figure below). PLC D-sub Remote I/O MPI Operator Panel Remote I/O Connection points Fig. 14: Connection points for the D-sub adapter cable Softing Page 21 Connection to PROFIBUS 7.3.2 Manual Direct cable connection To test a live PROFIBUS, you will need additional D-sub service interface of the type BC-PBMB-PB-S (see page 11). FC Diagnostic repeater PLC PBMB D-sub FC PBMB PBMB Connection points Fig. 15: Service interface provide connection points at direct cable connection Page 22 © 2013 BC-600-PB 7.3.3 Connection to PROFIBUS Connection via M12 connector Tests on a live PROFIBUS are only allowed on bus segments providing D-sub connection technology. Only D-sub connectors with service socket can be used as connection points for the test tool. For this reason, tests can often only be performed at a bus end. PLC D-sub Remote I/O Remote I/O Remote I/O Connection point Fig. 16: Connection points for the M12 adapter cable 7.4 Master Simulator and Topology Scan The master simulator allows checking the bus cabling and the station addresses during installation and commissioning, when the PLC (master) is not in operation yet. In addition, you can use this mode to check individual “suspicious” bus stations that have been disconnected from the bus. Softing Page 23 Connection to PROFIBUS Manual The topology scan determines the sequence and distances of all passive bus stations (slaves). This feature requires correct bus cabling, a very good signal quality, and a connection point located directly at the beginning or end of the bus. Both features can only be used during shutdown of the installation. The D-sub cable BC-600-PB-CB-DSUB-2 which is included in the standard scope of supply must be used. As long as communication is detected on the bus, i.e. at least one device is an active master, the functions are disabled. If necessary, disconnect every single active device (PLC, MPI and, if necessary, diagnostic repeaters) from the power supply or the bus. If an active device is at the end of the bus you want to test, its PROFIBUS connector needs to be unplugged and connected directly to the PROFIBUS Tester 4. The bus termination in the device connector will then be powered by the PROFIBUS Tester 4. PLC MPI Operator Panel Remote I/O Remote I/O Disconnect from bus w/o adaptor cable Connection points D-sub D-sub cable „Standard“ BC-600-PB-CB-DSUB-2 Fig. 17: Connection points for topology scan Page 24 © 2013 BC-600-PB Connection to PROFIBUS Attention: Bus stations must only be disconnected from the power supply or the bus during shutdown of the installation. Attention: The two functions can be started also when the PROFIBUS Tester 4 is disconnected from the bus. If you then connect the PROFIBUS Tester 4 to a live bus despite the yellow bus status bar indicated by the PC software, this can cause bus communication problems or a shutdown of the installation. 7.4.1 Special case: Active devices at both ends of the bus On the very rare occasion when there is an active device at each end of the bus, do the following: 1. When using D-sub connection: • Additionally switch on the terminating resistor in the D-sub connector of the last slave. The outgoing cable to the active device at the bus end has to be connected to the outgoing connector (marked with “OUT”, an outgoing arrow, or “A2/B2”). Fig. 18: Checking the connection direction at the D-sub connector 2. When using M12 connection: • Softing The cable from the bus start or test tool has to be connected to the incoming M12 connector of the last slave. A bus termination is required at the outgoing M12 connector of the last slave. Page 25 Display and Control in Stand-Alone Mode 8 Manual Display and Control in Stand-Alone Mode The PROFIBUS Tester 4 always starts in stand-alone mode unless it is USB connected to a PC or notebook. The readings are shown on the display. You can control the tool with the four function keys. When you establish a USB connection during stand-alone mode while a test is running, the test will be aborted and the tool will be reset (restart). The display briefly shows: “Changing operating mode – Please wait …”. 8.1 Main Display The baud rate of a connected PROFIBUS network is detected and displayed automatically: Fig. 19: Main display - example of a live PROFIBUS at 1.5 Mbit/s Page 26 © 2013 BC-600-PB Display and Control in Stand-Alone Mode The PROFIBUS status is shown in line 2. The following displays are possible: 3. The PROFIBUS is not connected: • Display: “DP n/a” 4. The PROFIBUS is connected, but no master is active: • Display of the static RS485 bus voltage, e.g. “DP 1015 mV stat.” 5. The PROFIBUS is connected and one or more masters are active: • Display of the detected baud rate, e.g. “DP 1.5 Mbit/s” The status of the integrated master simulator is shown in line 3. The following displays are possible: 1. The master simulator is disabled: • The display remains blank. 2. The master simulator has been enabled manually (see page 36): • Display: “M.Sim. ON” The only control on the main display is the down arrow key with which you can select the individual functions. Softing Page 27 Display and Control in Stand-Alone Mode 8.2 Manual Operating Concept Fig. 20: Display control with the four function keys Page 28 © 2013 BC-600-PB 8.3 Display and Control in Stand-Alone Mode Functions 8.3.1 Live Status function The Live Status function very quickly gives you an overview of the bus status. Even transient disturbances during the test are reliably detected. Once you start the function, the tool determines and continuously updates the status for the segment and for each bus station. 8.3.1.1 Bus status summary Fig. 21: Live Status with bus status summary Line 1 shows the overall bus status. It results from the substatus for bus communication and the substatus for bus physics, which are displayed in lines 2 and 3. Bus communication: 1. “Error” • • 2. Bus stations were dropped or added during the test Configuration errors or parameter errors occurred (the actual structure of modular slaves differs from the configuration stored in the PLC, or an incorrect GSD file was used) „Warning“ • • Frame errors, retries or diagnostics occurred during the test One or more bus stations have not been configured in the PLC 3. „OK“ • Softing No critical states or events Page 29 Display and Control in Stand-Alone Mode Manual Bus physics: 1. “Error” • 2. One or more bus stations failed to respond during the last physical test cycle „Warning“ • 3. One or more quality indexes* are below the user-defined limit value (default: 2500) „OK“ • All quality index* results are above the limit value * .. See the “Interpretation of the signal quality test results” chapter in the PROFIBUS Diagnostics Suite manual. Page 30 © 2013 BC-600-PB 8.3.1.2 Display and Control in Stand-Alone Mode Segment status 1 Fig. 22: Live Status with segment status 1 To the right of “DP Segm.” in line 1, the display shows changes in the live list (added and dropped bus stations). The following displays are possible: 1. The number of bus stations has not changed during the test: • No display of live list changes 2. One or more bus stations have been added during the test: • “+” display 3. One or more bus stations have been dropped during the test: • “-” display 4. One or more bus stations have been added and one or more dropped during the test: • “+ -” display The live list should usually not change when a PROFIBUS system is stable. In line 2, you see the number of masters (M) and slaves (S). For the slaves, the first figure indicates the number of slaves addressed by the master(s). If not all slaves respond, the number of slaves that failed to respond is indicated after a “-” sign. Line 3 indicates the token rotation time. Note: The token rotation time does not necessarily equal the bus cycle time. Softing Page 31 Display and Control in Stand-Alone Mode 8.3.1.3 Manual Segment status 2 Fig. 23: Live Status with segment status 2 Line 1 is the same as for segment status 1. In line 2 you see, on the left, the number of retries on the entire segment and, on the right, the worst quality index of all bus stations. Line 3 shows, on the left, the number of frame errors on the entire segment and, on the right, the best quality index of all bus stations. Page 32 © 2013 BC-600-PB 8.3.1.4 Display and Control in Stand-Alone Mode Station status This function displays the station status for each bus station, i.e. for all masters and all slaves. Fig. 24: Live Status with station status of a master Fig. 25: Live Status with station status of a slave The PROFIBUS address of the bus station is displayed right after “DP#” on the left of line 1. The letter in the middle indicates whether the device is a master (M) or slave (S). If the letter is enclosed in square brackets, the BC-600-PB was able to determine the address of the PROFIBUS device to which it is connected. In the above example, the test tool is connected to the device with the address 11 (see Fehler! Verweisquelle konnte nicht gefunden werden.). On the right, you see the live list changes (see page 31) for this bus station. Line 2 shows the number of retries on the left, and the worst quality index of this bus station on the right. Line 3 indicates the number of diagnostics on the left, and the best quality index of this bus station on the right. Note: The update rate for the live status substantially depends on the number of bus stations and the signal quality. Softing Page 33 Display and Control in Stand-Alone Mode 8.3.2 Manual Quick Test function The Quick Test allows full testing of bus physics and bus communication. The test data is stored in the tool. It can subsequently be imported by the PROFIBUS Diagnostics Suite software application. To start the function, choose one of 10 internal memory locations. The display indicates if the selected memory location is allocated or free. If you select an allocated memory location, the previous test data will be overwritten. Fig. 26: Quick test completed The duration of a Quick Test depends on the baud rate, the number of slaves and the current bus communication. It can take only a few seconds or up to three minutes. On completion of the test, press the acknowledgment key to cancel the status display. Page 34 © 2013 BC-600-PB 8.3.3 Display and Control in Stand-Alone Mode Trend function Trend logging is used for detecting rare or sporadic faults over a prolonged period of time. The function monitors both the bus physics and critical events in the bus communication. The PROFIBUS Tester 4 can automatically test the bus in stand-alone mode from within the control cabinet for up to 41 days. The test data is stored in the tool. It can subsequently be imported by the PROFIBUS Diagnostics Suite software application. Before you start the function, choose a test interval. When you select “Auto” the tool automatically determines the optimum interval. The Trend Test runs until manually stopped with the “x” key. Fig. 27: Trend running for 23 h and 52 min. The test is aborted automatically when the power supply is interrupted (all data logged so far is retained in memory) or when the maximum logging time of 999 hours and 59 minutes is reached. Softing Page 35 Display and Control in Stand-Alone Mode 8.3.4 Manual Master Simulator function The master simulator is disabled by default when you switch on the tool. You can only select a baud rate on the display and thus start the master simulator if no other master is active. 8.3.5 Settings and help functions The following options are available: • Settings/Delete all internal memory locations: Deletes all quick tests and trend recordings • Settings/Current language: Toggles between English, German, French, Italian, Polish and Spanish (all w/o national specific characters) • Settings/Limit signal quality: Sets the limit value in increments of 100 (default: 2500) • Settings/Time-out signal quality: Sets the time-out value in increments of 5 (default: 5 seconds) • HW Information: Displays on two screens the firmware and FPGA versions and the date and time of the last factory calibration. • Help: Briefly describes the functionality of the four function keys. Page 36 © 2013 BC-600-PB 9 Data Import into the PC Data Import into the PC Quick Tests and Trend logs stored in the test tool can be imported into the PC software. To do this, start the PROFIBUS Diagnostics Suite. If a PROFIBUS Tester is connected to the PC via USB and contains stored test data, an additional “Import Test Data from Tool” dialog box appears automatically. Fig. 28: Importing test data For ALL the stored data, you need to fully select the action to be performed, the network/project, and the test location to which you want to store the data. The default action “Import & Delete“ deletes the test data in the tool after the import is complete. This frees the allocated memory locations for new tests. The imported Quick Tests and Trend logs are fully compatible with the test data that can be acquired using the PC software. Softing Page 37 Firmware Update Manual 10 Firmware Update Firmware updates are made available as required. They are provided with the updates to the PC software (see page 16) and allow access to new or improved functionality. How to update the firmware is described in detail in the separate “PROFIBUS Diagnostics Suite – Getting Started” manual. Page 38 © 2013 BC-600-PB Maintenance and Servicing 11 Maintenance and Servicing The PROFIBUS Tester 4 is maintenance-free and does not require calibration. Repairs may only be carried out by the device manufacturer. All returns must be made in the supplied carrying case. Please also include a brief fault description and a phone number at which we can contact you should we need further details. In case of returns within the warranty period, please also enclose a copy of the invoice or delivery note. Softing Page 39 Troubleshooting Manual 12 Troubleshooting Problem The display of the PROFIBUS Tester 4 remains blank. The display shows the following error message: “USB ERROR - Refer to manual or disconn. for standalone mode”. The baud rate is not detected automatically on a live PROFIBUS. Causes and remedies Possible cause: • The PROFIBUS Tester 4 always needs an additional external power supply. Remedy: • Use the supplied external AC adapter to connect the tool to the mains power supply. • When connected directly to a 24 VDC power supply: check the voltage at the terminals Alternative cause: • The tool is defective. Remedy: • Return the tool for servicing (see page 39) Possible cause: • This error message can be caused by poor physical connection via USB (“loose” contact). Remedy: • Check the USB cable and connector. Possible cause: • Massive disturbances in the bus physics. Remedy: • Manually set the baud rate and repeat the test. If you need to contact Softing's support team, you will find the contact data on the back cover of the manual. Page 40 © 2013 BC-600-PB Specifications 13 Specifications Power supply RS485 (DP) Via external AC adapter 100 V .. 240 VAC 50/60 Hz (galvanically isolated) or direct connection to 24 VDC ±20%, approx. 0.5 A (without galvanic isolation) PROFIBUS D-sub connector (female), 9-pin, switchable power supply for ext. bus termination Protocol and frame analysis: PROFIBUS DP and DPV1, automatic baud rate detection 9.6 kbit/s .. 12 Mbit/s Signal analysis: PROFIBUS DP, DPV1, FMS and MPI; signal quality index 0 .. 5000 determined from signal waveform as well as signal/noise ratio and rise time; signal sampling with 8/16 samples per bit Oscillogram display: Test range ±5V at 10mV resolution (differential), 0V…15V at 15mV resolution (A or B to DGND) sampling rate: up to 384 MSamples/s, for signal details: 2,400 sampled points, for oscillogram analysis: 8,192 sampled points Topology scan: Active, maximum distance 230 m, accuracy ±2 m USB Trigger Internal memory capacity V 2.0, high speed 480 Mbit/s, galvanically isolated IN : L=0 .. 0.8 V; H=2.4 .. 24 V; pulse > 10 μs, active high OUT: approx. 5 V, active low (connection to storage oscilloscope) 10 memory locations for Quick Tests, 1 Trend log, max. 41 days Dimensions Weight HxWxD: 35 x 170 x 110 mm Test tool without cable: approx. 0.45 kg, complete with carrying case, without accessories: approx. 3.9 kg Protection class Permissible ambient conditions IP 20 Operating temperature 0 .. 50 °C Storage temperature -20 .. 70 °C, Air humidity 10 .. 90% without condensation Conformity Operation CE, FCC, VCCI Via four-line display and four function keys or via PC/notebook. Localization of the display: DE+EN+FR+IT+PL+ES (without national specific characters) PC operating software PROFIBUS Diagnostic Suite, see separate manual Softing Page 41 General Notes Manual 14 General Notes 14.1 Lithium Battery Warning! This product contains a lithium backup battery. The lithium content is not more than 1 g. The battery has been successfully tested by the manufacturer in accordance with the UN Manual of Test and Criteria (test procedures of Part III, Sub-Section 38.3). Improper handling of lithium batteries can cause the batteries to ignite or explode and pose a burn hazard to users. If the product is properly handled, this battery does not need to be replaced during the lifetime of the product. Therefore, opening the product is unnecessary and not permitted. The product must only be operated within the specified temperature range. Do not expose to heat above this temperature range and keep away from open fire. Store in a dry place. 14.2 CE Conformity This product complies with the requirements of the EC Directives 2004/108/EC Electromagnetic Compatibility (EMC directive) Emission: EN 61000-6-4 Generic Emission Standard (industrial environments) EN 55011 Group 1 Class A (ISM Product Standard) EN 55022 Class A (ITE Product Standard) Immunity: EN 61000-6-2 Generic Immunity Standard (industrial environments) EN 61326-1 (Measurement, Control and Laboratory Equipment Product Standard) A Declaration of Conformity in compliance with the above standards has been made and can be inspected at Softing AG on request. NOTE: For compliance with the legal EMC requirements, the other components (PROFIBUS devices, AC adapter, etc.) must also meet these requirements. To meet the EMC conditions, the product must be installed and connected in accordance with the installation instructions. Warning! This is a Class A product. In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures. Page 42 © 2013 Softing Industrial Automation GmbH Richard-Reitzner-Allee 6 85540 Haar Germany industrial.softing.com Tel. +49 89 45656-326 (Support) Tel. +49 89 45656–340 (Sales) Fax +49 89 45656–488 Email: [email protected]
Detail Specifications: 1332/1332631-bc600pb.pdf file (14 Dec 2022) |
Accompanying Data:
Softing BC-600-PB Test Equipment PDF Manual (Updated: Wednesday 14th of December 2022 05:26:59 AM)
Rating: 4.8 (rated by 10 users)
Compatible devices: WX4500-FA, CableMaster CM800, CableMaster CM600, PROFIBUS Tester 5, WireXpert WX-4500, NetXpert XG, Wire Xpert WX Series, CableMaster.
Recommended Documentation:
Text Version of Manual
(Ocr-Read Summary of Contents, UPD: 14 December 2022)
-
29, BC-600-PB Display and Control in Stand-Alone Mode Softing Page 29 8.3 Functions 8.3.1 Live Status function The Live Status function very quickly gives you an overview of the bus status. Even transient disturbances during the test are reliably detected. Once you start the function, the tool determines and continuously updates the status for the seg…
-
44, Softing BC-600-PB Softing industrial.softing.com Industrial Automation GmbH Tel. +49 89 45656-326 (Support) Richard-Reitzner-Allee 6 Tel. +49 89 45656–340 (Sales) 85540 Haar Fax +49 89 45656–488 Germany Email: [email protected]
… -
14, Power Supply and Auto Power On Manual Page 14 © 2013 5 Power Supply and Auto Power On The tool is powered with 24 VDC either through the external AC adapter or by using the single-ended cable for direct 24 VDC power supply. Both are included in delivery. Attention: Before being connected to the AC mains power, the PROFIBUS Tester 4 and the AC ada…
-
20, Connection to PROFIBUS Manual Page 20 © 2013 7.3 Connection for Testing a Live Bus To test a live PROFIBUS with the PROFIBUS Tester 4 during operation, appropriate connection possibilities have to be provided. If no suitable connection points are available in the existing installation, it is recommended to install them during system shutdown. This w…
-
13, BC-600-PB Connectors and Controls Softing Page 13 4 Connectors and Controls RS485 Connection to PROFIBUS DP Display Status display & operation Function key 2 Funktionstaste 3 Detail selection Start Function key 1 Funktionstaste 4 Function selection Back/Cancel Power USB Connection to Connection to notebook/PC power supply Status LED 24 VDC Trigger input Status LED T…
-
9, BC-600-PB Optional Accessories Softing Page 9 3 Optional Accessories 3.1 D-sub adapter cable for testing live systems This D-sub adapter cable is optimized for reduced influence on live PROFIBUS DP segment operation. Thereby it is most suitable for testing of running plants. The risk of critical influences on bus operation which can cause a plant standstill is si…
-
10, Softing BC-600-PB Optional Accessories Manual Page 10 © 2013 3.3 Fieldbus Shield Digital Leakage Current Clamp When routing PROFIBUS cables in high-interference environments, electromagnetic interference can affect the signal quality. By measuring the shield currents with the digital leakage current clamp, you can locate EMC problem areas and take appropriate countermeasures. The digital l…
-
23, BC-600-PB Connection to PROFIBUS Softing Page 23 7.3.3 Connection via M12 connector Tests on a live PROFIBUS are only allowed on bus segments providing D-sub connection technology. Only D-sub connectors with service socket can be used as connection points for the test tool. For this reason, tests can often only be performed at a bus end. D-sub Con…
-
27, BC-600-PB Display and Control in Stand-Alone Mode Softing Page 27 The PROFIBUS status is shown in line 2. The following displays are possible: 3. The PROFIBUS is not connected: • Display: “DP n/a” 4. The PROFIBUS is connected, but no master is active: • Display of the static RS485 bus voltage, e.g. “DP 1015 mV stat.” 5. The PROFIBUS is conn…
Recommended Instructions:
DH24PB, RHB630, ThinkSERVER TS130, New Jersey MP68
-
OMHACM415250OPERATINGMANUALforACLOADBANKtypeHACM415250Xissue1SerialNo.M372051 …
HACM415250X 14
-
1PROBLEMS?Before returning it to the shop, call us on 0800 195 0088 (+44 1628 778885 outsidethe UK) Mon-Sat 9am-5pm.We can resolve most issueson the phone in a coupleof minutes!WARNING: AlcoSense is a sensitive measurement device. Performing a breath test less than 10 minutes after drinking risks blowing high levels of alcohol directly from your mouth into the system which could …
Ultra 15
-
Operation and Instruction Manual REV A . Koehler Instrument Company, Inc. 1595 Sycamore Avenue • Bohemia, New York 11716-1796 • USA Toll Free: 1-800-878-9070 (US only) • Tel: +1 631 589 3800 • Fax: +1 631 589 3815 http://www.koehlerinstrument.com • e-mail: [email protected] Petroleum Testing & Analysis Instrumentation • Custom Design & Ma …
K41091 20
Additional Information:
Popular Right Now:
Operating Impressions, Questions and Answers:
Table of Contents for Softing BC-600-PB:
-
Optional Accessories Manual Page 12 © 2013 3.5.2 Connection Type M12 The M12 service interface comprises an IP68 rated T piece, an end cap for the service output of the T piece, and a 1m PROFIBUS DP cable fitted with a male/female M12 connector on each end. Fig. 7: M12 service interface for testing a live bus Softing Order No.: BC-M12DP-PB
-
Display and Control in Stand-Alone Mode Manual Page 34 © 2013 8.3.2 Quick Test function The Quick Test allows full testing of bus physics and bus communication. The test data is stored in the tool. It can subsequently be imported by the PROFIBUS Diagnostics Suite software application. To start the function, choose one of 10 internal memory locations. The display indicates if the selected memory location is allocated or free. If you select an allocated memory location, th
-
BC-600-PB Optional Accessories Softing Page 11 3.5 Service Interface for PROFIBUS DP 3.5.1 Connection Type D-sub The D-sub service interface provides a PROFIBUS access point for testing if the existing D-sub connectors have no service socket or if the bus stations are connected via a terminal block. The service interface can power the terminating resistor of the D-sub conn
-
Connection to PROFIBUS Manual Page 20 © 2013 7.3 Connection for Testing a Live Bus To test a live PROFIBUS with the PROFIBUS Tester 4 during operation, appropriate connection possibilities have to be provided. If no suitable connection points are available in the existing installation, it is recommended to install them during system shutdown. This will make future maintenance work much easier. Attention: When installing additional connection points, you divide the bus. Before doing so, you therefore need to shut dow
-
BC-600-PB Connection to PROFIBUS Softing Page 21 7.3.1 Connection via D-sub connector with service socket If all bus stations provide D-sub connectors with an additional service socket, you can simply plug in the PROFIBUS Tester 4 at that socket (see figure below). MPI Operator Panel Remote I/O Remote I/O D-sub Connection points PLC Fig. 14: Connection points for the D-sub adapter cable
-
Delivery Scope Manual Page 8 © 2013 2 Delivery Scope The PROFIBUS Tester 4 comes in a carrying case comprising: • Test tool with RS485 interface • Wide-range power supply with European and US mains power cables • Connecting cable for direct power supply with 24 VDC • RS485 D-sub adapter cable BC-600-PB-CB-DSUB-2 “Standard” (cable petrol blue, light connector) for PROFIBUS DP • USB cable, 3 m •
-
BC-600-PB Display and Control in Stand-Alone Mode Softing Page 29 8.3 Functions 8.3.1 Live Status function The Live Status function very quickly gives you an overview of the bus status. Even transient disturbances during the test are reliably detected. Once you start the function, the tool determines and continuously updates the status for the segment and for each bus station. 8.3.1.1 Bus status summary Fig. 21: Live Status with bus status summary Lin
-
BC-600-PB Connection to PROFIBUS Softing Page 23 7.3.3 Connection via M12 connector Tests on a live PROFIBUS are only allowed on bus segments providing D-sub connection technology. Only D-sub connectors with service socket can be used as connection points for the test tool. For this reason, tests can often only be performed at a bus end. D-sub Connection point PLC Remote I/O Remote I/O Remote I/O Fig. 16: Connection points for the M12 adapter cable 7.4 Master Simulator and Topology Scan The master simulator
-
BC-600-PB Power Supply and Auto Power On Softing Page 15 5.2 Power-Up Behaviour when USB Connected Attention: The “PROFIBUS Diagnostics Suite” PC software also includes the required USB driver. You therefore need to install the software first before connecting the test tool to the PC or notebook. On successful completion of the self-test, the PROFIBUS Tester 4 displays: Fig. 9: Power-up display when
-
BC-600-PB Connection to PROFIBUS Softing Page 17 7.1.2 Connection types There are several ways to connect a bus station to a PROFIBUS network: • Using connectors o D-sub connectors, most of which have an integrated terminating resistor and, optionally, an additional service socket o M12 connectors for environments requiring increased IP ratings o Special vendor-specific hybrid connectors; they are used in combination with special cables to supply power via the bus
-
BC-600-PB Specifications Softing Page 41 13 Specifications Power supply Via external AC adapter 100 V .. 240 VAC 50/60 Hz (galvanically isolated) or direct connection to 24 VDC ±20%, approx. 0.5 A (without galvanic isolation) RS485 (DP) PROFIBUS D-sub connector (female), 9-pin, switchable power supply for ext. bus termination Protocol and frame analysis: PROFIBUS DP and DPV1, automatic baud rate detection 9.6 kbit/
-
Power Supply and Auto Power On Manual Page 14 © 2013 5 Power Supply and Auto Power On The tool is powered with 24 VDC either through the external AC adapter or by using the single-ended cable for direct 24 VDC power supply. Both are included in delivery. Attention: Before being connected to the AC mains power, the PROFIBUS Tester 4 and the AC adapter must be acclimated to room temperature to avoid condensation. This may take up to 60 minutes. The tool switches on automatically when you connect it to a power supply. The displa
-
Display and Control in Stand-Alone Mode Manual Page 32 © 2013 8.3.1.3 Segment status 2 Fig. 23: Live Status with segment status 2 Line 1 is the same as for segment status 1. In line 2 you see, on the left, the number of retries on the entire segment and, on the right, the worst quality index of all bus stations. Line 3 shows, on the left, the number of frame errors on the entire segment and, on the right, the best quality in
-
Firmware Update Manual Page 38 © 2013 10 Firmware Update Firmware updates are made available as required. They are provided with the updates to the PC software (see page 16 ) and allow access to new or improved functionality. How to update the firmware is described in detail in the separate “PROFIBUS Diagnostics Suite – Getting Started” manual.
-
BC-600-PB Optional Accessories Softing Page 9 3 Optional Accessories 3.1 D-sub adapter cable for testing live systems This D-sub adapter cable is optimized for reduced influence on live PROFIBUS DP segment operation. Thereby it is most suitable for testing of running plants. The risk of critical influences on bus operation which can cause a plant standstill is significantly reduced. Attention: Using this cable it is not possible to use the bot
Questions, Opinions and Exploitation Impressions:
You can ask a question, express your opinion or share our experience of Softing BC-600-PB device using right now.
Содержание
- Неисправности Profibus и их устранение
- Пути решения проблемы
- Перепутанные провода
- Полезные советы
- Разрывы проводов
- Полезные советы
- Короткое замыкание на линиях А-В — Короткое замыкание экрана А/В
- Полезные советы.
- Длина сегмента Profibus
- Полезные советы.
- Отсутствующая или избыточная терминация
- Полезные советы
- Диагностика сети PROFIBUS Indu-Sol
- Диагностика качества передачи данных в PROFIBUS
- Форум АСУТП
- ProfiBUS — дилетантский вопрос
- ProfiBUS — дилетантский вопрос
Неисправности Profibus и их устранение
Если вы программист, то вы знаете что такое Profibus, если нет, то пора узнать, тем более если у вас появились такие проблемы.
Profibus (с англ. Process Field Bus — шина полевого уровня) — открытая промышленная сеть, прототип которой был разработан компанией Siemens для своих промышленных контроллеров Simatic. На основе этого прототипа Организация пользователей Profibus разработала международные стандарты, принятые затем некоторыми национальными комитетами по стандартизации.
Ну или простыми словами, если вы видели фиолетовый провод с двумя проводами, то это он 😉
Profibus (с англ. Process Field Bus — шина полевого уровня)
Существует несколько вариантов, которые могут произойти:
Короткое замыкание на линиях А-В
Короткое замыкание экрана А/В
Отсутствующая или избыточная терминация
Пути решения проблемы
Перепутанные провода
У Profibus коннекторов в разъем А подключается зеленый провод, в разъем В подключается красный провод. Также правильно, чтобы было подключение А1,В1 — вход, а А2,В2 — выход.
Правильное подключение Profibus
Как исправить перепутанные провода. Просто проверить подключение.
Полезные советы
Разрывы проводов
Кабель Profibus может быть как многожильным, так и монолитным. Как и у обычных проводов
P.S. Многожильный кабель очень неудобно вставлять в коннекторы.
Из чего состоит кабель Profibus
Монолит медный кабель может через время сломаться. Часто при разделке кабеля можно повредить медь и при укладке в коннектор бывало кабель ломался.
Полезные советы
Короткое замыкание на линиях А-В — Короткое замыкание экрана А/В
Начнем с понятия КЗ.
Короткое замыкание (КЗ) — электрическое соединение двух точек электрической цепи с различными значениями потенциала, не предусмотренное конструкцией устройства и нарушающее его нормальную работу.
При замыкании линий A-B, или замыкании одной из линий на экран происходит перезагрузка контроллера, так и выход одной линии по сети из строя.
Полезные советы.
Если у вас есть схема сети профибас, то в онлайне Hardware Step 7 можно увидеть какие станции отключены. Сопоставив со схемой можно определить в каком месте проблема.
Также можно также определить номера станций, которые активны, а которые нет используя «Set PG/PC interface». Во вкладке «Properties» можно увидеть с галочкой — активные модули, а модули неактивные будут просто без галочки, пустое белое поле.
Длина сегмента Profibus
Максимальная длина сети Profibus зависит от скорости. Скорость передачи и соответствующая длинна сегмента
Таблица зависимости скорости Profibus от длины сегмента
Соответственно, чтобы сигнал доходил без потерь необходимо соблюдать данные скорости и метраж.
Полезные советы.
Если в процессе работы у вас теряются части данных, то необходимо в Hardware SIEMENS поменять скорость, на более низкую.
Также для усиления сигнала можно поставить Repeater. Repeater служит для усиления сигналов данных, передаваемых по кабелям шины, и для объединения сегментов шины.
Отсутствующая или избыточная терминация
Тут все просто, необходимо проверить терминальные резисторы на коннекторах. Если расстояние маленькое, то контроллеру все равно на резисторы, однако при больших расстояниях теряется сигнал.
Полезные советы
Главное правило — начальные и конечные точки — не забудь включить резистор. Волновое сопротивление кабеля должно быть равно нагрузочному резистору в начале и в конце сегмента.
Имеем один кусок кабеля, на концах которого висят два приёмника-передатчика, эти величины должны друг другу соответствовать. Однако на деле их количество может быть значительно больше двух, что изменит волновое сопротивление кабеля. Поэтому нельзя в общем случае гарантировать равенство волнового сопротивления и нагрузочного резистора, а можно лишь пытаться обеспечить примерное их соответствие, что и делается установкой 220 Ом.
Про отсутствующую терминацию я более подробно расскажу в следующей статье.
Источник
Диагностика сети PROFIBUS Indu-Sol
Диагностика сети PROFIBUS Indu-Sol
PROFIBUS (Process Field Bus) – это промышленная сеть полевого уровня, отвечает требованиям европейских норм EN5017-2 и международного стандарта IEC 61158. Данный стандарт используется для организации связи между программируемыми контроллерами и станциями распределенного ввода-вывода, а также устройствами человеко-машинного интерфейса и другими приборами полевого уровня. PROFIBUS позволяет выполнять конфигурирование, диагностирование и отладку системы автоматизации.
PROFIBUS поддерживает следующие протоколы передачи:
– PROFIBUS-DP (Profibus for Decentralized Peripherals – «Profibus для децентрализованной периферии») – протокол ориентирован на организацию связи между контроллерами и устройствами распределенного ввода-вывода, а также другими приборами полевого уровня. Он обеспечивает наиболее быстрый циклический обмен небольшими объемами данных.
– PROFIBUS-FMS (Fieldbus Message Specification – спецификация сообщений шины полевого уровня) – протокол для обмена данными между сетевыми контроллерами, контролерами и компьютерами на регистровом уровне. Предоставляет большую гибкость при передаче больших объемов данных, но проигрывает протоколу DP в популярности вследствие своей сложности.
PROFIBUS FMS и DP используют один и тот же физический уровень, основанный на интерфейсе RS-485 и могут работать в общей сети.
– PROFIBUS-PA (Profibus for Process Automation – «для автоматизации технологических процессов») – протокол использует физический уровень на основе стандарта IEC 1158-2, который обеспечивает питание всех сетевых компонентов через экранированную витую пару и не совместим с RS-485. Подключение к сети PROFIBUS-DP осуществляется через модули сопряжения DP/PA Coupler или блоки DP/PA Link. Особенностью PROFIBUS-PA является возможность работы во взрывоопасной зоне.
Особые требования предъявлены к сетевому кабелю. Он имеет волновое сопротивление от 135 до 165 Ом при погонной емкости не более 30 пФ/м, площадь поперечного сечения проводников более 0,34 кв. мм. и погонное сопротивление не более 110 Ом/км. Кабель должен иметь одну или две витые пары с медным экраном в виде оплетки или фольги. (см. Каталог Продукции)
В местах соединений для шины PROFIBUS рекомендуется разъемы D-sub (DB-9) с 9-ю контактами. При необходимости иметь степень защиты IP65/67 рекомендуется использовать цилиндрический коннектор типа M12 (IEC 947-5-2)(см. Каталог Продукции).
Диагностика качества передачи данных в PROFIBUS
Хорошая скорость передачи, большая длина соединения и широкие возможности по обработке данных превращают PROFIBUS в одну из лучших шин, предназначенных для систем управления многими технологическими процессами и интенсивной обработки информации. Но чтобы обеспечить стабильность функционирования оборудования и производственного процесса в целом, состояние всех компонентов системы следует контролировать.
Причинами изменений в сети PROFIBUS могут быть запланированное и незапланированное вмешательство во время технического обслуживания или сборочных работ, а так же постоянное изнашивание (старение) электрокомпонентов и кабелей сети PROFIBUS.
Тестирование кабеля является обязательным условием для передачи чистого сигнала в сети PROFIBUS.
Тестер кабеля PROFtest II – идеальный инструмент для измерения характеристик кабеля, проверки правильной проводки во время ввода в эксплуатацию, ремонта и обслуживания сети PROFIBUS.
Прибор прост в обращении и с подробной текстовой индикацией на дисплее.
Все результаты измерений хранятся на устройстве и могут быть распечатаны через ПК в виде журнала.
- кейс пластиковый транспортировочный
- тестер PROFtest II XL
- устройство зарядное плюс две батареи
- основные адаптеры для подключения к сети PROFIBUS
- инструкция по эксплуатации
Тестер кабеля PROFtest II XL
Заказной номер – 110010005
Тестер PB-Q ONE – это простое в использовании и мощное измерительное устройство для всестороннего контроля основных компонентов сети PROFIBUS. Тестер определяет и оценивает состояние физической и логической передачи данных в сети.
Интегрированный мастер-симулятор позволяет тестировать качество связи без использования контроллера. Это используется при проведении предварительной проверки собранной системы и её компонентов на этапе ввода в эксплуатацию с занесением данных измерений в отчет приемки, а так же при проведении плановой проверки и устранения неполадок в существующих сетях PROFIBUS.
Устройство подключается к ПК или ноутбуку через USB-интерфейс, который также обеспечивает питание. Все измеренния и результаты теста можно показать и внести в журнал на ПК через установленное программное обеспечение «Indu-Sol Suite». Программа проста в использовании.
Тестер сети PB-Q ONE
Заказной номер – 110010050
PROFIBUS-INspektor® NT — диагностический прибор, который охватывает вашу сеть PROFIBUS со всеми активными устройствами внутри нее и передает информацию с помощью встроенного веб-интерфейса.
Все что нужно для просмотра на экране текущего состояния сети и истории прошлых событий – это итернет-браузер (например Internet Explorer).
PROFIBUS-INspektor® NT позволяет проводить для каждого устройства сети всесторонний анализ всех значимых событий, таких как:
- ошибки телеграмм
- повторения телеграмм
- данные диагностики устройства
- перезапуски
- время цикла передачи данных,
а также выводить на экран для удобного просмотра:
- журнал событий
- жизненный цикл вашей сети и текущее состояние полевой шины
- топологию устройств с отображением статуса для быстрой локализации ошибок
- автоматически сформированный отчет по проверке системы со всеми важными сведениями о событиях
- данные в режиме отчета о приемке для быстрого обзора сети
Как пассивный регистратор данных, PROFIBUS-INspektor® NT отслеживает трафик логических данных и выдает сигнал тревоги при любых негативных аномалиях в системе посредством:
- уведомления по электронной почте
- светодиодного дисплея
- контактного переключателя
- отправки сигнала по протоколу SNMP
PROFIBUS-INspektor® NT
Заказной номер – 124010020
Комплект поставки StarterKIT:
- кейс пластиковый транспортировочный
- PROFIBUS-INspektor® NT
- кабель активный APKA II
- кабель соединительный
- кабель переходной
- инструкция по эксплуатации
PROFIBUS-INspektor® NT StarterKIT
Заказной номер – 124010021
EmCheck® LSMZ I является идеальным инструментом для измерения тока утечки в кабеле и наводимых токов на его экране в частотном диапазоне 50/60 Гц или 5 Гц — 1 кГц.
Измерения могут быть проведены в диапазоне между 30 мкА и 100 А. Для измерения экранных токов на кабеле больше подходит нижняя граница диапазона.
Измеритель EmCheck® LSMZ I используется для обнаружения неисправностей изоляции кабеля. Благодаря функции удержания можно проводить длительные измерения, по обнаружению максимального тока в кабеле. Также измеритель имеет функции мультиметра.
EmCheck® LSMZ I
Заказной номер – 122010005
Купить оборудование в компании «Комплексные решения»: направьте запрос на info@com-sol.ru | через форму сайта либо звоните нам по тел +7 (495) 902-51-12!
NEW! Услуги по измерениям в сети PROFIBUS Проведение работ по оценке качества и стабильности промышленных сетей передачи данных PROFIBUS во время ремонта и обслуживания сети. Проверка правильной проводки при вводе в эксплуатацию новой сети PROFIBUS. Источник Форум АСУТПКлуб специалистов в области промышленной автоматизации
ProfiBUS — дилетантский вопросProfiBUS — дилетантский вопросСообщение Jackson » 11 ноя 2013, 19:32 Коллеги, прошу помощи в довольно дилетантском вопросе. Я тут играю роль только передатчика — коллеги коллег спросили. Мопед, в общем, не мой. Имеется сеть ProfiBUS DP, мастер, слейвы. Периодически пропадает связь со всеми слейвами сразу, то есть все они перестают отвечать на запросы. 2) какие существуют средства диагностики таких проблем? На модбасе всё просто — есть модбас-симуляторы. Как обстоит дело с Профибасом в этом смысле? Источник Adblock |
Уважаемые Партнёры!
Настоящим извещаем вас о том, что коллектив команды «ЕвроИндустрия»
будет находиться на летних каникулах в период с 03.07.2023 по 16.07.2023 включительно.
По всем вопросам вы можете связаться со старшим дежурными менеджером: +7(812)200-75-15 доб 018 /
sale18@ei.spb.ru.
Цена:
уточните у менеджера
Производитель:
уточните у менеджера
Срок поставки:
уточните у менеджера
Доставка по всей территории РФ.
По любым вопросам поставки Вы можете обращаться к нашим менеджерам по телефону +7(812)200-75-15 или по электронной почте info@ei.spb.ru
Для оформления заявки на поставку оборудования и запчастей добавьте товар в корзину и оформите заказ.
Уважаемые Клиенты!
Мы продолжаем поставлять импортное оборудование для Вас даже в это непростое геополитическое время. Несмотря на уход многих дилеров и европейских производителей с российского рынка, нашей компанией налажены разнообразные каналы закупок и логистических маршрутов.
Сообщаю, что наша команда готова обеспечить Вам поставки всех необходимых Брендов по налаженным каналам параллельного импорта.
Так же если Вы столкнулись со сложностями доставки номенклатуры из Европы, мы готовы оказать поддержку и сопровождение, получение разрешения путём включения данной номенклатуры в приказ №1532 от 19 Апреля 2022 г. Минпромторга России.
В связи со сложной внешней экономической ситуацией себестоимость доставки и логистических затрат выросла в разы. Минимальная сумма заказа — 400 000 рублей.
С уважением, Деева Любовь, Генеральный Директор ООО «ЕвроИндустрия»