Operating Instructions
Proline Promass E 100
Coriolis flowmeter
Modbus RS485
Solutions
Services
Related Manuals for Endress+Hauser Proline Promass E 100
Summary of Contents for Endress+Hauser Proline Promass E 100
-
Page 1
Products Solutions Services BA01711D/06/EN/03.21 71506065 2021-01-01 Valid as of version 01.03.zz (Device firmware) Operating Instructions Proline Promass E 100 Coriolis flowmeter Modbus RS485… -
Page 2
• The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser Sales Center will supply you with current information and updates to these instructions. Endress+Hauser… -
Page 3: Table Of Contents
Proline Promass E 100 Modbus RS485 Table of contents Table of contents 6.1.2 Environmental and process About this document ….5 requirements ….
-
Page 4
10.3.3 Configuring communication 13.3 Endress+Hauser services ….77 interface ….. . 53 10.3.4 Configuring the low flow cut off . -
Page 5: About This Document
Proline Promass E 100 Modbus RS485 About this document About this document Document function These Operating Instructions contain all the information that is required in various phases of the life cycle of the device: from product identification, incoming acceptance and storage, to mounting, connection, operation and commissioning through to troubleshooting, maintenance and disposal.
-
Page 6: Symbols For Certain Types Of Information
• W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Detailed list of the individual documents along with the documentation code →…
-
Page 7: Standard Documentation
Proline Promass E 100 Modbus RS485 About this document 1.3.1 Standard documentation Document type Purpose and content of the document Technical Information Planning aid for your device The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
-
Page 8: Safety Instructions
Safety instructions Proline Promass E 100 Modbus RS485 Safety instructions Requirements for the personnel The personnel for installation, commissioning, diagnostics and maintenance must fulfill the following requirements: ‣ Trained, qualified specialists must have a relevant qualification for this specific function and task.
-
Page 9: Workplace Safety
Verification for borderline cases: ‣ For special fluids and fluids for cleaning, Endress+Hauser is glad to provide assistance in verifying the corrosion resistance of fluid-wetted materials, but does not accept any warranty or liability as minute changes in the temperature, concentration or level of contamination in the process can alter the corrosion resistance properties.
-
Page 10: Product Safety
It meets general safety standards and legal requirements. It also complies with the EU directives listed in the device-specific EU Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
-
Page 11: Product Description
Proline Promass E 100 Modbus RS485 Product description Product description The device consists of a transmitter and a sensor. The Safety Barrier Promass 100 is part of the scope of supply and must be implemented to operate the device. The device is available as a compact version: The transmitter and sensor form a mechanical unit.
-
Page 12: Incoming Acceptance And Product
Is the envelope present with accompanying documents? • If one of the conditions is not satisfied, contact your Endress+Hauser Sales Center. • Depending on the device version, the CD-ROM might not be part of the delivery! The Technical Documentation is available via the Internet or via the Endress+Hauser Operations App, see the «Product identification»…
-
Page 13: Transmitter Nameplate
7 sections • The W@M Device Viewer: enter the serial number from the nameplate (www.endress.com/deviceviewer) • The Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2-D matrix code (QR code) on the nameplate. 4.2.1…
-
Page 14
Incoming acceptance and product identification Proline Promass E 100 Modbus RS485 Date: A0029207 4 Example of a sensor nameplate, part 2 Approval information for explosion protection, Pressure Equipment Directive and degree of protection Permitted ambient temperature (T Document number of safety-related supplementary documentation… -
Page 15: Promass 100 Safety Barrier Nameplate
Proline Promass E 100 Modbus RS485 Incoming acceptance and product identification 4.2.3 Promass 100 safety barrier nameplate Safe area NON intrinsically safe circuit (grey terminals) Promass 100 Safety Barrier Intrinsically safe circuits (blue terminals) HAZARDOUS area A0017854 5 Example of a Promass 100 safety barrier nameplate Non-hazardous area or Zone 2/Div.
-
Page 16: Storage And Transport
Storage and transport Proline Promass E 100 Modbus RS485 Storage and transport Storage conditions Observe the following notes for storage: ‣ Store in the original packaging to ensure protection from shock. ‣ Do not remove protective covers or protective caps installed on process connections.
-
Page 17: Measuring Devices With Lifting Lugs
Proline Promass E 100 Modbus RS485 Storage and transport 5.2.2 Measuring devices with lifting lugs CAUTION Special transportation instructions for devices with lifting lugs ‣ Only use the lifting lugs fitted on the device or flanges to transport the device.
-
Page 18: Installation
Installation Proline Promass E 100 Modbus RS485 Installation Installation conditions 6.1.1 Mounting position Mounting location A0028772 To prevent measuring errors arising from accumulation of gas bubbles in the measuring tube, avoid the following mounting locations in the pipe: • Highest point of a pipeline.
-
Page 19
Proline Promass E 100 Modbus RS485 Installation Ø orifice plate, pipe restriction [mm] [in] [mm] [in] ³⁄₈ 0.24 ½ 0.40 0.55 1½ 0.87 1.10 1.97 Orientation The direction of the arrow on the sensor nameplate helps you to install the sensor according to the flow direction (direction of medium flow through the piping). -
Page 20: Environmental And Process Requirements
Installation Proline Promass E 100 Modbus RS485 Inlet and outlet runs No special precautions need to be taken for fittings which create turbulence, such as valves, elbows or T-pieces, as long as no cavitation occurs → 20. A0029322 A0029323 Installation dimensions For the dimensions and installation lengths of the device, see the «Technical…
-
Page 21: Special Mounting Instructions
Proline Promass E 100 Modbus RS485 Installation NOTICE Electronics overheating on account of thermal insulation! ‣ Recommended orientation: horizontal orientation, transmitter housing pointing downwards. ‣ Do not insulate the transmitter housing . ‣ Maximum permissible temperature at the lower end of the transmitter housing: 80 °C (176 °F)
-
Page 22: Mounting The Measuring Device
Installation Proline Promass E 100 Modbus RS485 Sanitary compatibility When installing in hygienic applications, please refer to the information in the «Certificates and approvals/hygienic compatibility» section → 99 Rupture disk Information that is relevant to the process: → 93.
-
Page 23: Preparing The Measuring Device
Proline Promass E 100 Modbus RS485 Installation 6.2.2 Preparing the measuring device 1. Remove all remaining transport packaging. 2. Remove any protective covers or protective caps present from the sensor. 3. If present, remove transport protection of the rupture disk.
-
Page 24: Electrical Connection
Electrical connection Proline Promass E 100 Modbus RS485 Electrical connection NOTICE The measuring device does not have an internal circuit breaker. ‣ For this reason, assign the measuring device a switch or power-circuit breaker so that the power supply line can be easily disconnected from the mains.
-
Page 25: Terminal Assignment
Proline Promass E 100 Modbus RS485 Electrical connection Connecting cable between Safety Barrier Promass 100 and measuring device Cable type Shielded twisted-pair cable with 2×2 wires. When grounding the cable shield, observe the grounding concept of the plant. Maximum cable resistance 2.5 Ω, one side Comply with the maximum cable resistance specifications to ensure the operational reliability of the measuring device.
-
Page 26
Electrical connection Proline Promass E 100 Modbus RS485 Connection methods available Order code Possible options for order code Power «Housing» «Electrical connection» Output supply Options Device plugs Device plugs Option Q: 2 x plug M12x1 A, B, C → 28 →… -
Page 27
Proline Promass E 100 Modbus RS485 Electrical connection 72 A A0030219 10 Modbus RS485 terminal assignment, connection version for use in intrinsically safe areas (connection via Safety Barrier Promass 100) Intrinsically safe power supply Modbus RS485 Order code 10 (L+) -
Page 28: Pin Assignment, Device Plug
Electrical connection Proline Promass E 100 Modbus RS485 7.2.4 Pin assignment, device plug Supply voltage Promass 100 Device plug for signal transmission with supply voltage (device side), MODBUS RS485 (intrinsically safe) Assignment Supply voltage, intrinsically safe Modbus RS485 intrinsically safe…
-
Page 29: Shielding And Grounding
Proline Promass E 100 Modbus RS485 Electrical connection 7.2.5 Shielding and grounding Shielding and grounding concept 1. Maintain electromagnetic compatibility (EMC). 2. Take explosion protection into consideration. 3. Pay attention to the protection of persons. 4. Comply with national installation regulations and guidelines.
-
Page 30: Connecting The Transmitter
Electrical connection Proline Promass E 100 Modbus RS485 7.3.1 Connecting the transmitter The connection of the transmitter depends on the following order codes: • Housing version: compact or ultra-compact • Connection version: device plug or terminals A0016924 12 Housing versions and connection versions…
-
Page 31: Connecting The Safety Barrier Promass 100
Proline Promass E 100 Modbus RS485 Electrical connection For device version with device plug: follow step 6 only. 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. 2. Depending on the housing version, unscrew or open the housing cover.
-
Page 32: Ensuring Potential Equalization
Electrical connection Proline Promass E 100 Modbus RS485 7.3.3 Ensuring potential equalization Requirements No special measures for potential equalization are required. For devices intended for use in hazardous locations, please observe the guidelines in the Ex documentation (XA). Special connection instructions 7.4.1…
-
Page 33: Hardware Settings
Proline Promass E 100 Modbus RS485 Electrical connection Modbus RS485 intrinsically safe L- L+ A0028766 16 Connection example for Modbus RS485 intrinsically safe Control system (e.g. PLC) Cable shield provided at one end. Observe cable specifications Safety Barrier Promass 100…
-
Page 34: Ensuring The Degree Of Protection
Electrical connection Proline Promass E 100 Modbus RS485 If the transmitter is used in the intrinsically safe area 220 Ω A0030217 18 Terminating resistor can be enabled via DIP switch in the Safety Barrier Promass 100 Ensuring the degree of protection The measuring device fulfills all the requirements for degree of protection IP66/67, Type 4X enclosure.
-
Page 35
Proline Promass E 100 Modbus RS485 Electrical connection Depending on the device version: are all the device plugs firmly tightened → 30? • Does the supply voltage match the specifications on the transmitter nameplate → 86? • For device version with Modbus RS485 intrinsically safe: does the supply voltage match the … -
Page 36: Operation Options
Operation options Proline Promass E 100 Modbus RS485 Operation options Overview of operating options A0017760 Computer with «FieldCare» or «DeviceCare» operating tool via Commubox FXA291 and service interface Control system (e.g. PLC) Endress+Hauser…
-
Page 37: Structure And Function Of The Operating Menu
Proline Promass E 100 Modbus RS485 Operation options Structure and function of the operating menu 8.2.1 Structure of the operating menu For an overview of the operating menu for experts: «Description of Device Parameters» document supplied with the device→ 101…
-
Page 38: Operating Philosophy
Operation options Proline Promass E 100 Modbus RS485 8.2.2 Operating philosophy The individual parts of the operating menu are assigned to certain user roles (operator, maintenance etc.). Each user role contains typical tasks within the device lifecycle. Menu/parameter User role and tasks…
-
Page 39
Proline Promass E 100 Modbus RS485 Operation options X X X X X X X 1120.50 kg/h A0037831 Operational display Device tag→ 57 Status area Display area for measured values (4-line) Status area The following symbols appear in the status area of the operational display at the top right: •… -
Page 40: User Roles And Related Access Authorization
Operation options Proline Promass E 100 Modbus RS485 Totalizer The measurement channel number indicates which of the three totalizers is displayed. Output Measurement channel numbers Symbol Meaning Measurement channel 1 to 4 The measurement channel number is displayed only if more than one channel is present for the same measured variable type (e.g.
-
Page 41: Access To The Operating Menu Via The Operating Tool
Computer with «FieldCare» operating tool with «CDI Communication FXA291» COM DTM Via service interface (CDI) A0014019 Service interface (CDI = Endress+Hauser Common Data Interface) of the measuring device Commubox FXA291 Computer with FieldCare operating tool with COM DTM CDI Communication FXA291 8.4.2…
-
Page 42
Operation options Proline Promass E 100 Modbus RS485 Access is via: CDI service interface → 41 Typical functions: • Configuring parameters of transmitters • Loading and saving device data (upload/download) • Documentation of the measuring point • Visualization of the measured value memory (line recorder) and event logbook… -
Page 43: Devicecare
DeviceCare Function scope Tool to connect and configure Endress+Hauser field devices. The fastest way to configure Endress+Hauser field devices is with the dedicated «DeviceCare» tool. Together with the device type managers (DTMs) it presents a convenient, comprehensive solution. For details, see Innovation Brochure IN01047S Source for device description files See information →…
-
Page 44: System Integration
System integration Proline Promass E 100 Modbus RS485 System integration Overview of device description files 9.1.1 Current version data for the device Firmware version 01.03.zz • On the title page of the Operating Instructions • On the transmitter nameplate • Firmware version Diagnostics →…
-
Page 45: Register Information
Proline Promass E 100 Modbus RS485 System integration Code Name Description Application Write single Master writes a new value to one Write only 1 device parameter registers Modbus register of the measuring Example: reset totalizer device. Use function code 16 to write multiple registers with just 1 telegram.
-
Page 46: Byte Transmission Sequence
System integration Proline Promass E 100 Modbus RS485 INTEGER Data length = 2 bytes (1 register) Byte 1 Byte 0 Most significant byte (MSB) Least significant byte (LSB) STRING Data length = depends on the device parameter, e.g. presentation of a device parameter with a data length = 18…
-
Page 47: Modbus Data Map
Proline Promass E 100 Modbus RS485 System integration 0 – 1 – 2 – 3 Byte 16 Byte 17 Byte 0 Byte 1 2 – 3 – 0 – 1 (MSB) (LSB) * = factory setting, MSB = most significant byte, LSB = least significant byte 9.2.6…
-
Page 48
System integration Proline Promass E 100 Modbus RS485 Configuring the scan list via Modbus RS485 Carried out using register addresses 5001 — 5016 Scan list Modbus RS485 register Data type Configuration register 5001 Integer Scan list register 0 Integer 5016… -
Page 49: Commissioning
Proline Promass E 100 Modbus RS485 Commissioning Commissioning 10.1 Function check Before commissioning the device, make sure that the post-installation and post- connection checks have been performed. • «Post-mounting check» checklist → 23 • «Post-connection check» checklist → 34 10.2…
-
Page 50
Commissioning Proline Promass E 100 Modbus RS485 Temperature unit Pressure unit Parameter overview with brief description Parameter Description Selection/ Factory setting User entry Mass flow unit Select the unit for mass flow. Unit choose list Country-dependent: • kg/h Result • lb/min The selected unit applies for: •… -
Page 51
Proline Promass E 100 Modbus RS485 Commissioning Parameter Description Selection/ Factory setting User entry Temperature unit Select the unit for temperature. Unit choose list Country-dependent: • °C (Celsius) Result • °F (Fahrenheit) The selected unit applies for: • Output • Reference temperature •… -
Page 52: Selecting And Setting The Medium
Commissioning Proline Promass E 100 Modbus RS485 10.3.2 Selecting and setting the medium The Medium selection submenu contains parameters that have to be configured for selecting and setting the medium. Navigation path «Setup» menu → Medium selection Structure of the submenu Medium selection →…
-
Page 53: Interface
Proline Promass E 100 Modbus RS485 Commissioning 10.3.3 Configuring communication interface The Communication submenu guides you systematically through all parameters that must be configured for selecting and setting the communication interface. Navigation path «Setup» menu → Communication Structure of the submenu Communication →…
-
Page 54
Commissioning Proline Promass E 100 Modbus RS485 Selection/ Parameter Description Factory setting User entry Assign diagnostic Select diagnostic behavior • Off Alarm behavior for MODBUS • Alarm or warning communication. • Warning • Alarm Failure mode Select measured value • NaN value… -
Page 55: Configuring The Low Flow Cut Off
Proline Promass E 100 Modbus RS485 Commissioning 10.3.4 Configuring the low flow cut off The Low flow cut off submenu contains parameters that have to be set for configuring the low flow cut off. Navigation path «Setup» menu → Low flow cut off…
-
Page 56: Configuring The Partial Filled Pipe
Commissioning Proline Promass E 100 Modbus RS485 10.3.5 Configuring the partial filled pipe detection The Partially filled pipe detection submenu contains parameters that have to be set for configuring empty pipe detection. Navigation path «Setup» menu → Partial filled pipe detection…
-
Page 57: Advanced Settings
Proline Promass E 100 Modbus RS485 Commissioning 10.4 Advanced settings The Advanced setup menu with its submenus contains all parameters needed for specific settings. Navigation path «Setup» menu → Advanced setup Overview of the parameters and submenus in the «Advanced setup» menu taking the…
-
Page 58: Carrying Out A Sensor Adjustment
Commissioning Proline Promass E 100 Modbus RS485 Linear expansion coefficient Square expansion coefficient Parameter overview with brief description Parameter Prerequisites Description Selection/input Factory settings Corrected – Select the reference Calculated • Fixed reference volume flow density for calculating the reference density…
-
Page 59: Configuring The Totalizer
Proline Promass E 100 Modbus RS485 Commissioning Progress Parameter overview with brief description Parameter Description Selection/ Factory setting User entry Installation direction Change the sign of the direction • Flow in arrow direction Flow in arrow of flow of the fluid.
-
Page 60: Simulation
Commissioning Proline Promass E 100 Modbus RS485 Selection/ Parameter Prerequisite Description Factory setting User entry Volume unit The following option Select the unit for Unit choose list Country-dependent is selected in the volume. • l Assign process • gal (us)
-
Page 61: Parameter Overview With Brief
Proline Promass E 100 Modbus RS485 Commissioning 10.5.1 Parameter overview with brief description Selection/ Parameter Prerequisite Description Factory setting User entry Assign simulation Select a process • Off process variable variable for the • Mass flow simulation process • Volume flow that is activated.
-
Page 62
Commissioning Proline Promass E 100 Modbus RS485 4 — Bus termination 3 — Not used 2 — Not used 1 — Write protection A0017954 1. Depending on the housing version, loosen the securing clamp or fixing screw of the housing cover. -
Page 63: Operation
Proline Promass E 100 Modbus RS485 Operation Operation 11.1 Read device locking status The write protection types that are currently active can be determined using the Locking status parameter. Navigation path «Display/operation» menu → Locking status Function scope of «Locking status» parameter…
-
Page 64: Totalizer
Operation Proline Promass E 100 Modbus RS485 Parameter overview with brief description Parameter overview with brief description Parameter Prerequisite Description Display Mass flow – Displays the mass flow currently Floating-point number with measured sign Volume flow – Displays the volume flow currently…
-
Page 65: Adapting The Measuring Device To The Process
Proline Promass E 100 Modbus RS485 Operation Parameter overview with brief description Parameter Prerequisite Description Display Totalizer value 1-3 One of the following Displays the current Floating point number options is selected in the totalizer counter value. with sign Assign process variable…
-
Page 66
Operation Proline Promass E 100 Modbus RS485 «Operation» submenu Operation → Control totalizer 1 Preset value 1 Control totalizer 2 Preset value 2 Control totalizer 3 Preset value 3 Reset all totalizers Parameter overview with brief description Selection/ Parameter Prerequisite… -
Page 67: Diagnostics And Troubleshooting
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Diagnostics and troubleshooting 12.1 General troubleshooting For output signals Problem Possible causes Remedy Green power LED on the main Supply voltage does not match that Apply the correct supply voltage electronics module of the specified on the nameplate.
-
Page 68: Safety Barrier Promass 100
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 Alarm Device status is ok. Flashing red A device error of diagnostic behavior «Warning» has occurred. • A device error of diagnostic behavior «Alarm» has occurred. • Boot loader is active.
-
Page 69: Calling Up Remedy Information
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Status signals The status signals provide information on the state and reliability of the device by categorizing the cause of the diagnostic information (diagnostic event). Symbol Meaning Failure A device error has occurred. The measured value is no longer valid.
-
Page 70: Configuring Error Response Mode
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 • Via register address 6821 (data type = string): diagnosis code, e.g. F270 • Via register address 6859 (data type = integer): diagnosis number, e.g. 270 For an overview of diagnostic events with diagnosis number and diagnosis code →…
-
Page 71: Overview Of Diagnostic Information
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting 12.6 Overview of diagnostic information The amount of diagnostic information increases if the measuring device has one or more application packages. Diagnostics for the sensor Status Diagnostic Diagnosti signal Short text…
-
Page 72
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 Diagnostics for the configuration Status Diagnostic Diagnosti signal Short text Remedial measures behavior c number from the from the factory factory Data transfer 1. Check connection. Alarm 2. Retry data transfer. -
Page 73: Pending Diagnostic Events
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Status Diagnostic Diagnosti signal Short text Remedial measures behavior c number from the from the factory factory Inhomogeneous Oscillation amplitude limit! Alarm* The fluid properties do not allow a precise measurement.
-
Page 74: Event Logbook
Diagnostics and troubleshooting Proline Promass E 100 Modbus RS485 12.9 Event logbook 12.9.1 Event history A chronological overview of the event messages that have occurred is provided in the events list which contains a maximum of 20 message entries. This list can be displayed via FieldCare if necessary.
-
Page 75: 12.10 Resetting The Measuring Device
Proline Promass E 100 Modbus RS485 Diagnostics and troubleshooting Information event Event text I1151 History reset I1209 Density adjustment OK I1221 Zero point adjust failure I1222 Zero point adjustment OK 12.10 Resetting the measuring device Using the Device reset parameter it is possible to reset the entire device configuration or some of the configuration to a defined state.
-
Page 76: 12.12 Firmware History
«Manufacturer’ s information» document. The manufacturer’ s information is available: • In the Download Area of the Endress+Hauser Internet site: www.endress.com → Download • Specify the following details: •…
-
Page 77: Maintenance
→ 92. 13.2 Measuring and test equipment Endress+Hauser offers a wide variety of measuring and test equipment, such as W@M or device tests. Your Endress+Hauser Sales Center can provide detailed information on the services. List of some of the measuring and testing equipment: → 80→ 81 13.3…
-
Page 78: Repair
• The measuring devices have a modular design. • Spare parts are grouped into logical kits with the associated Installation Instructions. • Repairs are carried out by Endress+Hauser Service or by appropriately trained customers. • Certified devices can only be converted to other certified devices by Endress+Hauser Service or at the factory.
-
Page 79: Disposal
(WEEE), the product is marked with the depicted symbol in order to minimize the disposal of WEEE as unsorted municipal waste. Do not dispose of products bearing this marking as unsorted municipal waste. Instead, return them to Endress+Hauser for disposal under the applicable conditions.
-
Page 80: Accessories
Various accessories, which can be ordered with the device or subsequently from Endress +Hauser, are available for the device. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 81: Service-Specific Accessories
Tool to connect and configure Endress+Hauser field devices. Innovation brochure IN01047S Commubox FXA291 Connects Endress+Hauser field devices with a CDI interface (= Endress +Hauser Common Data Interface) and the USB port of a computer or laptop. Technical Information TI00405C 15.4…
-
Page 82: Technical Data
Technical data Proline Promass E 100 Modbus RS485 Technical data 16.1 Application The measuring device is intended only for the flow measurement of liquids and gases. Depending on the version ordered, the measuring device can also measure potentially explosive, flammable, poisonous and oxidizing media.
-
Page 83: Input
Proline Promass E 100 Modbus RS485 Technical data 16.3 Input Measured variable Direct measured variables • Mass flow • Density • Temperature Calculated measured variables • Volume flow • Corrected volume flow • Reference density Measuring range Measuring ranges for liquids Measuring range full scale values …
-
Page 84: Output
• Operating pressure to increase accuracy (Endress+Hauser recommends the use of a pressure measuring device for absolute pressure, e.g. Cerabar M or Cerabar S) •…
-
Page 85
Proline Promass E 100 Modbus RS485 Technical data Interface/protocol • Via digital communication: Modbus RS485 • Via service interface CDI-RJ45 service interface Plain text display With information on cause and remedial measures Light emitting diodes (LED) Status information Status indicated by various light emitting diodes The following information is displayed depending on the device version: •… -
Page 86: Power Supply
Technical data Proline Promass E 100 Modbus RS485 16.5 Power supply Terminal assignment • → 26 • → 25 Pin assignment, device plug → 28 Supply voltage The power unit must be tested to ensure it meets safety requirements (e.g. PELV, SELV).
-
Page 87: Performance Characteristics
Proline Promass E 100 Modbus RS485 Technical data Power supply failure • Totalizers stop at the last value measured. • Depending on the device version, the configuration is retained in the device memoryor in the pluggable data memory (HistoROM DAT).
-
Page 88
Technical data Proline Promass E 100 Modbus RS485 Temperature ±0.5 °C ± 0.005 · T °C (±0.9 °F ± 0.003 · (T – 32) °F) Zero point stability Zero point stability [mm] [in] [kg/h] [lb/min] ³⁄₈ 0.20 0.007 ½ 0.65 0.024… -
Page 89
Proline Promass E 100 Modbus RS485 Technical data Base repeatability Design fundamentals → 90 Mass flow and volume flow (liquids) ±0.075 % o.r. ±0.05 % o.r. (calibration option, for mass flow) Mass flow (gases) ±0.35 % o.r. Density (liquids) ±0.00025 g/cm… -
Page 90
Technical data Proline Promass E 100 Modbus RS485 o.r. = of reading It is possible to compensate for the effect by: • Reading in the current pressure measured value via the current input. • Specifying a fixed value for the pressure in the device parameters. -
Page 91: Installation
Proline Promass E 100 Modbus RS485 Technical data Example for maximum measured error E [%] 95 100 Q [%] A0030289 Maximum measured error in % o.r. (example) Flow rate in % of maximum full scale value 16.7 Installation Installation conditions →…
-
Page 92: Process
Technical data Proline Promass E 100 Modbus RS485 Shock resistance Shock, half-sine according to IEC 60068-2-27 6 ms 30 g Shock resistance Shock due to rough handling following IEC 60068-2-31 Interior cleaning • SIP cleaning • CIP cleaning Electromagnetic • As per IEC/EN 61326 and NAMUR Recommendation 21 (NE 21) compatibility (EMC) •…
-
Page 93
Proline Promass E 100 Modbus RS485 Technical data Sensor housing The sensor housing is filled with dry nitrogen gas and protects the electronics and mechanics inside. If a measuring tube fails (e.g. due to process characteristics like corrosive or abrasive fluids), the fluid will initially be contained by the sensor housing. -
Page 94
Technical data Proline Promass E 100 Modbus RS485 • The minimum recommended full scale value is approx. 1/20 of the maximum full scale value • In most applications, 20 to 50 % of the maximum full scale value can be considered ideal •… -
Page 95: 16.10 Mechanical Construction
Proline Promass E 100 Modbus RS485 Technical data 16.10 Mechanical construction Design, dimensions For the dimensions and installation lengths of the device, see the «Technical Information» document, «Mechanical construction» section. Weight All values (weight exclusive of packaging material) refer to devices with EN/DIN PN 40 flanges.
-
Page 96
Technical data Proline Promass E 100 Modbus RS485 Cable entries/cable glands A0020640 22 Possible cable entries/cable glands Female thread M20 × 1.5 Cable gland M20 × 1.5 Adapter for cable entry with female thread G ½» or NPT ½»… -
Page 97: 16.11 Human Interface
Proline Promass E 100 Modbus RS485 Technical data Process connections • Flanges according to EN 1092-1 (DIN2501) / according to ASME B 16.5 / as per JIS B2220: Stainless steel, 1.4404 (F316/F316L) • All other process connections: Stainless steel, 1.4404 (316/316L) Available process connections→…
-
Page 98: 16.12 Certificates And Approvals
The device meets the legal requirements of the applicable EU Directives. These are listed in the corresponding EU Declaration of Conformity along with the standards applied. Endress+Hauser confirms successful testing of the device by affixing to it the CE mark. RCM-tick symbol The measuring system meets the EMC requirements of the «Australian Communications…
-
Page 99
• With the identification PED/G1/x (x = category) on the sensor nameplate, Directive Endress+Hauser confirms conformity with the «Essential Safety Requirements» specified in Appendix I of the Pressure Equipment Directive 2014/68/EU. • Devices not bearing this marking (PED) are designed and manufactured according to good engineering practice. -
Page 100: 16.13 Application Packages
The application packages can be ordered with the device or subsequently from Endress+Hauser. Detailed information on the order code in question is available from your local Endress+Hauser sales center or on the product page of the Endress+Hauser website: www.endress.com.
-
Page 101: 16.14 Accessories
For an overview of the scope of the associated Technical Documentation, refer to the following: • W@M Device Viewer (www.endress.com/deviceviewer): Enter the serial number from nameplate • Endress+Hauser Operations App: Enter the serial number from the nameplate or scan the 2D matrix code (QR code) on the nameplate Standard documentation Brief Operating Instructions…
-
Page 102
Technical data Proline Promass E 100 Modbus RS485 Supplementary device- Safety Instructions dependent documentation Content Documentation code ATEX/IECEx Ex i XA00159D ATEX/IECEx Ex nA XA01029D cCSAus IS XA00160D INMETRO Ex i XA01219D INMETRO Ex nA XA01220D Special Documentation Content Documentation code… -
Page 103: Index
Proline Promass E 100 Modbus RS485 Index Index 0 … 9 Design Measuring device ……11 3-A approval .
-
Page 104
Index Proline Promass E 100 Modbus RS485 Enabling write protection ….. 61 Installation conditions Endress+Hauser services Down pipe ……18 Maintenance . -
Page 105
Proline Promass E 100 Modbus RS485 Index Read access ……44 Pressure-temperature ratings ….92 Reading out data . -
Page 106
Index Proline Promass E 100 Modbus RS485 Spare parts ……. . 78 Special connection instructions . -
Page 108
*71506065* 71506065 www.addresses.endress.com…
Цена по запросу
Promass E 100 кориолисовый(массовый) расходомер, компактное и экономичное решение, прекрасная альтернатива объемным расходомерам, быстрая окупаемость за счёт высокой точности ±0,15 %
DN 8…80
- Описание
- Тех.характеристики
- Документация
Описание
Promass E 100
Promass E 100 – надежный кориолисовый (массовый) расходомер, зарекомендовал себя как самый компактный и экономичный из большинства представленных сегодня массовых расходомеров, прибор имеет высокую точность измерения расхода ±0,15 %(для жидкости).Преобразователь в сверхкомпакнтым и прочном корпусе, Promass E 100 — полная функциональность при небольших габаритах. Быстрая настройка и локальное управление без дополнительного программного и аппаратного обеспечения – встроенный веб-сервер.
Основные преимущества Promass E 100:
• Экономичность и долговечность – многоцелевое устройство; прекрасная альтернатива объемным расходомерам
• Кориолисовый принцип измерения расхода не зависит от таких физических свойств жидкости, как вязкость и плотность.
• Возможность измерения: Массового расхода, плотности, температуры, объемного расхода, приведенного объемного расхода, референсной плотности, концентрации
• Меньше точек измерения в процессе – многопараметрическое измерение (расход, плотность, температура)
• Простая установка – не требуются прямые участки до и после расходомера
• Быстрая настройка без дополнительного программного и аппаратного обеспечения – встроенный веб-сервер
• Встроенная функция для самоповерки и диагностики – технология Heartbeat Technology**
**Heartbeat Technology в измерительных приборах обеспечивает получение четких, стандартизованных диагностических сообщений о действиях, которые необходимо выполнить для эффективного обслуживания вашего завода. Таким образом, данная технология позволяет проводить упреждающее техническое обслуживание и обеспечивает ощутимые преимущества в надежности и безопасности процессов при эксплуатации оборудования. Так как устройства сами проводят собственную диагностику, интервал проведения контрольных испытаний может быть увеличен до максимальных значений.
Преимущества
-
Тестирование и документирование каждой измерительной точки на месте без прерывания процесса
-
Постоянная самодиагностика позволяет увеличивать интервалы между проведением контрольных испытаний
-
Диагностические сообщения обеспечивают точные инструкции для технического обслуживания
-
Четкие и документируемые результаты тестов, простая процедура тестирования
-
Автоматически генерируемый протокол тестирования обеспечивает соответствие документации нормативным требованиям
-
Данные процесса и устройства отражают тренды для упреждающего обслуживания
-
Сочетание параметров процесса и устройства упрощают анализ для оптимизации процесса
Простой и удобный контроль измерительных точек
С технологией Heartbeat вы всегда держите свои измерения под контролем. Вы сможете с легкостью проверить функционирование измерительной точки не прерывая процесс. Так как устройства сами проводят собственную диагностику, интервал проведения контрольных испытаний может быть увеличен до максимальных значений. Автоматически генерируемые отчеты без остановки процесса помогают вам вести документооборот. Мониторинг параметров приборов позволяет осуществлять упреждающее техническое обслуживание и использовать данные для оптимизации процесса в будущем.
Источник www.endress.com
Детали
Основные характерситики |
• Условный диаметр: DN 8…80 • Массовый/Объемный расход (жидкость): ±0,15 % • Массовый расход (газ): ±0,75 % • Плотность (жидкость): ±0,0005 г/см³ • материал корпуса сенсора: 1.4301 (304) коррозионно стойкий материал • Входной сигнал : нет •Выходные сигналы 4‐20 мА HART (активный)-Импульсный/частотный/дискретный (пассивный) • Цифровая связь: HART, Modbus RS485, EtherNet/IP, PROFIBUS DP, PROFINET • Макс. рабочее давление: PN 100, класс 600 • Рабочая температура среды: стандарт -40…+140 °C • Диапазон окружающей температуры: –40 (-50 опция)…+60 °C • Материал корпуса преобразователя: Компактное исполнение: AlSi10Mg, с покрытием /сверхкомпактное исполнение: 1.4301 (304) • Степень защиты: IP66/67, опционально IP69 • Сертификаты на взрывозащиту: ATEX, IECEx, cCSAus, INMETRO, NEPSI, EAC •Морские сертификаты и нормативы ABS (American Bureau of Shipping), BV (Bureau Veritas), LR (Lloyds Register) |
---|---|
Бренд |
Endress+Hauser |
Страна-производитель |
Германия |
Promass E 100 описание функций прибора на русском языке
Promass E 100 руководство по эксплуатации на русском языке (протокол передачи данных HART )
*другая техническая информация по запросу
Detail Specifications: 1302/1302206-proline_promass_e_100.pdf file (15 Feb 2023) |
Accompanying Data:
Endress+Hauser Proline Promass E 100 Measuring Instruments PDF Manual (Updated: Wednesday 15th of February 2023 02:58:32 PM)
Rating: 4.6 (rated by 6 users)
Compatible devices: Cerabar M, Liquiline CM44P, Proline Promass 84, Proline Promass O 100HART, PROline promag 23, SpectraSensors SS2100i-1, Liquiline System CA80AL, FOUNDATION Fieldbus Micropilot FMR50.
Recommended Documentation:
Text Version of Manual
(Ocr-Read Summary of Contents, UPD: 15 February 2023)
-
51, Endress+Hauser Proline Promass E 100 Proline Promass E 100 Endress+Hauser 51 Flange JIS B2220 300 [°F]350250200150100500-50 [°C]200150100500-50 400 0 10 20 30 40 50 70 60 [bar][psi] 200 400 600 800 0 1000 63K 10K 40K 20K A0029834-EN 27 With flange material 1.4404 (F316/F316L) Flange DIN 11864-2 Form A DN8…40 ≥ DN 50 -80 0 80 160 240 320 400 0 10 20 30 40 0 200 400 600 [°C] [°F] [bar][psi] 20015010050…
-
43, Proline Promass E 100 Endress+Hauser 43 Accuracy Max. ±50 ppm o.r. (over the entire ambient temperature range) Repeatability o.r. = of reading; 1 g/cm 3 = 1 kg/l; T = medium temperature Base repeatability Design fundamentals → 44 Mass flow and volume flow (liquids) ±0.075 % o.r. ±0.05 % o.r. (calibration option, for mass flow) Mass flow (gases) ±0.35 % o.r. Density (liquids) �…
-
35, Endress+Hauser Proline Promass E 100 Proline Promass E 100 Endress+Hauser 35 2 3 4…20 mA 41 5 A0028762 10 Connection example for 4 to 20 mA HART current output (passive) 1 Automation system with current input (e.g. PLC) 2 Power supply 3 Cable shield: the cable shield must be grounded at both ends to comply with EMC requirements; observe cable specifications → 39 4 Analog display unit: observe maxim…
-
5, Proline Promass E 100 Endress+Hauser 5 Function and system design Measuring principle The measuring principle is based on the controlled generation of Coriolis forces. These forces are always present in a system when both translational and rotational movements are superimposed. F c = 2 · ∆m (ν · ω) F c = Coriolis force ∆ m = moving mass ω = rotational velo…
-
90, Endress+Hauser Proline Promass E 100 Proline Promass E 100 90 Endress+Hauser Content Documentation code Concentration measurement SD01152D Concentration measurement SD01503D Heartbeat Technology SD01153D Heartbeat Technology SD01493D Web server SD01820D Web server SD01821D Web server SD01822D Web server SD01823D Installation Instructions Contents Comment Installation instructions for spare part sets and acc…
-
47, Proline Promass E 100 Endress+Hauser 47 If a sensor is installed horizontally with a curved measuring tube, match the position of the sensor to the fluid properties. 1 2 A0028774 22 Orientation of sensor with curved measuring tube 1 Avoid this orientation for fluids with entrained solids: Risk of solids accumulating. 2 Avoid this orientation for outgassing fluids: Risk of gas accumulating. …
-
71, Proline Promass E 100 Endress+Hauser 71 Flange connections Fixed flange ASME B16.5 C D A B E L A0015621 Length tolerance for dimension L in inch: +0.06 / –0.08 Flange according to ASME B16.5, Cl 150 1.4404 (F316/F316L) Order code for «Process connection», option AAS DN [in] A [in] B [in] C [in] D [in] E [in] L [in] ³⁄₈ 1) 3.54 2.37 4 × Ø0.62 0.44 0.62 9.13 ½…
-
59, Proline Promass E 100 Endress+Hauser 59 Flange according to EN 1092-1 (DIN 2501 / DIN 2512N), PN 63 1.4404 (F316/F316L): order code for «Process connection», option D3S Flange with groove according to EN 1092-1 Form D (DIN 2512N), PN 63 1.4404 (F316/F316L): order code for «Process connection», option D7S DN [mm] A [mm] B [mm] C [mm] D [mm] E [mm] L [mm] 50 180 135…
-
25, Proline Promass E 100 Endress+Hauser 25 PROFIBUS DP connection version For use in the non-hazardous area and Zone 2/Div. 2 Order code for «Output», option L Depending on the housing version, the transmitters can be ordered with terminals or device plugs. Order code «Housing» Connection methods available Possible options for order code «Electrical connection» Output P…
-
21, Proline Promass E 100 Endress+Hauser 21 Input/output value Process variable Category Slot Oscillation frequency 1 Oscillation amplitude 0 Oscillation amplitude 1 Frequency fluctuation 1 Tube damping fluctuation 1 Exciter current 1 Input value External density Process monitoring 18 External temperature 19 External reference density 20 Flow override 21 Zero point…
Recommended Instructions:
MZ-100, bluTrend, Standard 3030x, D406DZ, 917.375501
-
VIZIT-M42 CVIZIT-M42 C88 PAL VIZITOPERATING INSTRUCTION- is a colour monitor intended for use as a subscriber device within video doorphones.123105678941. Handset.2. ..3.4.(.5. :—- ()—6.7.8. 12 / 509.10. 2.7” TFT LCD.11. .12.Ring volume switch (left position for a quiet call, right position for a loud call) The switch position alsoinfluences intercom volumeLock release b …
VIZIT-M428C 11
-
40-6676 Self-Leveling 360° Laser with Plumb Line Operator’s ManualDownload this manual at www.johnsonlevel.com/manuals 40-6676 Thank you for purchasing this Johnson Self-Leveling 360° Laser with Plumb Line featuring GreenBrite® technology. This laser includes a 360° plane of laser light as well as a vertical beam for plumb work.This tool comes with a Li-Ion battery and …
40-6676 2
-
The A-464 mounting kit provides a flush mounting solution forMagnehelic®Gage installations in applications such as cleanrooms and mechanical equipment rooms. The A-464 can alsobe used as an alternative means to flush mount Magnehelic®Gages on control panel enclosures. Utilizing the A-464 for Magnehelic®Gages installations reducesinstallation time while al …
A-464 2