Series PM130 PLUS Powermeters
PM130P/PM130E/PM130EH
PROFIBUS DP Communications Protocol
Reference Guide
BG0444 Rev. A2
Related Manuals for Satec PM130P
Summary of Contents for Satec PM130P
-
Page 1
Series PM130 PLUS Powermeters PM130P/PM130E/PM130EH PROFIBUS DP Communications Protocol Reference Guide BG0444 Rev. A2… -
Page 2
Every effort has been made to ensure that the material herein is complete and accurate. However, the manufacturer is not responsible for any mistakes in printing or faulty instructions contained in this book. Notification of any errors or misprints will be received with appreciation. -
Page 3: Table Of Contents
Table of Contents 1 GENERAL ………………….5 2 PROFIBUS DP PROTOCOL IMPLEMENTATION ……….6 PROFIBUS ID N GSD-F ………………6 UMBER AND PROFIBUS V ………………….6 ERSION ………………………6 ATES ……………………6 DDRESS ………………..6 NPUT AND UTPUT UFFERS ………………..6 XTENDED IAGNOSTIC PROFIBUS F …………………6 AULT CTION …………………….6 US IN LINE…
-
Page 4
Setpoint Status SP1-SP16 (bitmap) ………………… 20 ………………21 INIMUM AXIMUM EGISTERS Minimum Phase Values ……………………21 Minimum Total Values…………………….. 21 Minimum Auxiliary Values ……………………21 Maximum Phase Values ……………………21 Maximum Total Values……………………. 22 Maximum Auxiliary Values ……………………22 Maximum Demands ……………………..22 …………….24 EVICE ONTROL AND… -
Page 5: General
1 General This document specifies the PM130 PROFIBUS DP messaging protocol used to transfer data between a master PROFIBUS station and the PM130. The document provides the complete information necessary to develop third-party communications software capable of communication with the Series PM130 PLUS devices. Additional information concerning communications operation, configuring the communications parameters, and communications connections is found in «Series PM130 PLUS Powermeters, Installation and Operation Manual».
-
Page 6: Profibus Dp Protocol Implementation
2 PROFIBUS DP Protocol Implementation 2.1 PROFIBUS ID Number and GSD-File The PM130 uses the certified AnyBus®-IC PROFIBUS communication module from HMS Industrial Networks AB with the registered PROFIBUS ID number 0x1810. The GSD file hms_1810.gsd is shown in Section 6 and is provided with the device on an accompanying 2.2 PROFIBUS Version The PM130 supports the basic version V0 of the PROFIBUS DP protocol.
-
Page 7: Profibus Messaging Protocol
2.8 PROFIBUS Messaging Protocol Overview Since the PM130 transfer buffers only support 32 bytes or less transfer blocks, all of the device registers cannot possibly be sent over PROFIBUS DP every scan. However, a messaging mechanism allows a master to access all the device registers by placing a command request pointing to the requested items in the output buffer and by receiving a corresponding response in the input buffer.
-
Page 8: Device Response Block
Table 2-1 Read Request Block Bytes Description Range Type Notes Command control See Table 2-3 UINT16 Start point ID 0x0000-0xFFFF UINT16 Table 2-2 Write Request Block Bytes Description Range Type Notes Command control See Table 2-3 UINT16 Start point ID 0x0000-0xFFFF UINT16 4-31…
-
Page 9: Transfer Synchronization
Byte Bits Description Range Notes 5-6 Unused 7 Synchronization bit Synchronized with the master synchronization bit when command handling is completed 0-3 Word count 0-14 Indicates the number of words in the data block 4-7 Exception code See Table 2-7 Note: Bit 0 is a least significant bit (LSB).
-
Page 10
— Raw input data in the range of RAW_LO to RAW_HI ENG_LO, — Data low and high scales in engineering units (see Section 4 for device data ENG_HI scales) RAW_LO — Low conversion scale for raw device data: RAW_LO = -32768 for a point with a negative LO scale, RAW_LO = 0 for a point with a zero or positive LO scale RAW_Hi — High conversion scale for raw device data: RAW_HI = 32767… -
Page 11
b) Assume device settings (wiring via PT): Wiring 4LN3; PT = 120; CT primary current = 200A; Voltage scale = 144V. Active Power engineering scales (see Section 4): ENG_HI = Pmax = Vmax × Imax × 3 = (144 × 120) × (200.00 × 2) × 3/1000 = 20,736kW ENG_LO = -Pmax = -20,736kW If the raw data reading is 12000 then the power reading in engineering units will be as follows: Watts reading = (12000 — (-32768)) ×… -
Page 12: Device Register Map
3 Device Register Map 3.1 Analog Registers, Binary Registers and Counters Point ID Description Type Notes Options/Range Units 0x0000 None UINT16 Special Inputs 0x0101 Phase rotation order 0=error, 1=positive (ABC), UINT16 2=negative (CBA) Counters 0x0A00 Counter #1 0-99,999 UINT32 0x0A01 Counter #2 0-99,999 UINT32 0x0A02 Counter #3…
-
Page 13: 1-Cycle Total Values
Point ID Description Type Notes Options/Range Units 0x0C1B I1 Current TDD 0-1000 ×0.1% UINT16 2-cycle value 0x0C1C I2 Current TDD 0-1000 ×0.1% UINT16 2-cycle value 0x0C1D I3 Current TDD 0-1000 ×0.1% UINT16 2-cycle value 0x0C1E V12 Voltage 0-Vmax UINT16 0x0C1F V23 Voltage 0-Vmax UINT16 0x0C20 V31 Voltage…
-
Page 14: 1-Second Phase Values
Point ID Description Type Notes Options/Range Units 1-Second Phase Values 0x1100 V1/V12 Voltage 0-Vmax UINT32 0x1101 V2/V23 Voltage 0-Vmax UINT32 0x1102 V3/V31 Voltage 0-Vmax UINT32 0x1103 I1 Current 0-Imax UINT32 0x1104 I2 Current 0-Imax UINT32 0x1105 I3 Current 0-Imax UINT32 0x1106 kW L1 -Pmax-Pmax INT32…
-
Page 15: 1-Second Auxiliary Values
Point ID Description Type Notes Options/Range Units 0x1408 Total kvar import 0-Pmax UINT32 0x1409 Total kvar export 0-Pmax UINT32 0x140A 3-phase average L-N/L-L voltage 0-Vmax UINT32 0x140B 3-phase average L-L voltage 0-Vmax UINT32 0x140C 3-phase average current 0-Imax UINT32 1-Second Auxiliary Values 0x1500 Not used UINT32 0x1501 In (neutral) Current…
-
Page 16: Total Energies E
Point ID Description Type Notes Options/Range Units 0x161F Not used UINT32 0x1620 Not used UINT32 0x1621 Not used UINT32 0x1622 In Ampere demand 0-Imax UINT32 Total Energies 0x1700 kWh import 0-999,999,999 UINT32 0x1701 kWh export 0-999,999,999 UINT32 0x1702 Not used INT32 0x1703 Not used UINT32…
-
Page 17: V2/V23 Harmonic Distortions
Point ID Description Type Notes Options/Range Units V2/V23 Harmonic Distortions 0x1A00 H01 Harmonic distortion 0-10000 0.01% UINT16 0x1A01 H02 Harmonic distortion 0-10000 0.01% UINT16 0x1A27 H40 Harmonic distortion 0-10000 0.01% UINT16 V3/V31 Harmonic Distortions 0x1B00 H01 Harmonic distortion 0-10000 0.01% UINT16 0x1B01 H02 Harmonic distortion 0-10000…
-
Page 18: Fundamental Total Values
Point ID Description Type Notes Options/Range Units 0x290F Power factor L1 -1000-1000 ×0.001 INT16 0x2910 Power factor L2 -1000-1000 ×0.001 INT16 0x2911 Power factor L3 -1000-1000 ×0.001 INT16 Fundamental Total Values 2-cycle values 0x2A00 Total fundamental kW -Pmax-Pmax INT32 0x2A01 Total fundamental kvar -Pmax-Pmax INT32 0x2A02 Total fundamental kVA…
-
Page 19: V1/V12 Harmonic Angles
Point ID Description Type Notes Options/Range Units 0x3702 V3/V31 Maximum volt demand 0-Vmax UINT32 0x3703 I1 Maximum ampere demand 0-Imax UINT32 0x3704 I2 Maximum ampere demand 0-Imax UINT32 0x3705 I3 Maximum ampere demand 0-Imax UINT32 0x3706 Not used UINT32 0x3707 Not used UINT32 0x3708 Not used UINT32…
-
Page 20: I3 Harmonic Angles
Point ID Description Type Notes Options/Range Units 0x6800 H02 Harmonic angle -1800-1800 ×0.1º INT16 0x6827 H40 Harmonic angle -1800-1800 ×0.1º INT16 I3 Harmonic Angles 0x6900 H01 Harmonic angle -1800-1800 ×0.1º INT16 0x6900 H02 Harmonic angle -1800-1800 ×0.1º INT16 0x6927 H40 Harmonic angle -1800-1800 ×0.1º…
-
Page 21: Minimum/Maximum Log Registers
3.2 Minimum/Maximum Log Registers Point ID Description Type Notes Options/Range/Format Units Minimum Phase Values 0xB000 Min. V1/V12 Voltage 0-Vmax UINT32 0xB001 Timestamp UINT32 0xB002 Min. V2/V23 Voltage 0-Vmax UINT32 0xB003 Timestamp UINT32 0xB004 Min. V3/V31 Voltage 0-Vmax UINT32 0xB005 Timestamp UINT32 0xB006 Min.
-
Page 22: Maximum Total Values
Point ID Description Type Notes Options/Range/Format Units 0xB20A Max. I3 Current 0-Imax UINT32 0xB20B Timestamp UINT32 Maximum Total Values 0xB280 Max. Total kW -Pmax-Pmax INT32 0xB281 Timestamp UINT32 0xB282 Max. Total kvar -Pmax-Pmax INT32 0xB283 Timestamp UINT32 0xB284 Max. Total kVA 0-Pmax UINT32 0xB285…
-
Page 23
Point ID Description Type Notes Options/Range/Format Units 0xB399 UINT32 0xB39A Not used UINT32 0xB39B UINT32 0xB39C Not used UINT32 0xB39D UINT32 0xB39E Maximum kW export sliding window demand 0-Pmax UINT32 0xB39F Timestamp UINT32 0xB3A0 Maximum kvar export sliding window demand 0-Pmax UINT32 0xB3A1… -
Page 24: Device Control And Status Registers
3.3 Device Control and Status Registers Point ID Description Options/Range Units Type Notes Device Reset/Clear Registers 0xA000 Clear total energy registers UINT16 Read as 0 0xA001 Clear total maximum demand registers 0 = Clear all maximum demands UINT16 1 = Clear power demands 2 = Clear volt and ampere demands 0xA004 Clear pulse counters 0 = Clear all counters…
-
Page 25: Device Setup Registers
+0 Device serial number 0-999999 UINT32 +1 Device model ID 13010=PM130P, 13011=PM130A, UINT32 13020=PM130E, 13030-13032=PM130EH 13010=PM130P, 13030=PM130EH +2-5 Device model name “PM130P”, “PM130A”, “PM130E”, UINT32 Null-terminated string “PM130EH” +6 Device options (bitmap) UINT32 Not used +7-9 Reserved UINT32 +10 Device firmware version number…
-
Page 26: Basic Setup
Address Description Options/Range Units Type Notes +3 Baud rate COM1: 1=300 bps, 2=600 bps, UINT16 COM2 baud rate does not concern the 3=1200 bps, 4=2400 bps, 5=4800 PROFIBUS baud rate bps, 6=9600 bps, 7=19200 bps, 8=38400 bps, 9=57600 bps, 10=115200 bps COM2: 9=57600 bps +4 Data format COM1: 0=7 bits/even parity,…
-
Page 27: Clock Setup
Address Description Options/Range Units Type Notes +2 Phase energy calculation mode 0=disabled, 1=enabled UINT16 +3-9 Reserved UINT16 Read as 65535 +10 Energy LED test mode 0=disabled, 1=Wh test, 2=varh test UINT16 LED pulse rate is 10,000 pulses/kWh +11 Starting voltage, percent of FS voltage 15-50 ×0.1% UINT16…
-
Page 28: Data Scales And Units
4 Data Scales and Units Code Condition Value/Range Notes Data Scales Vmax Voltage scale × PT Ratio, V Imax Current scale × CT Ratio, A 1, 3 Pmax Wiring 4LN3, 3LN3, 3BLN3 Vmax × Imax × 3, W Wiring 4LL3, 3LL3, 3BLL3, Vmax ×…
-
Page 29: Data Formats
5 Data Formats Format Code Value Description Notes Timestamp Local time in a UNIX-style format. Represents the number 946684800 to of seconds since midnight (00:00:00), January 1, 1970. 2145916799 The time is valid after January 1, 2000. allowed Wiring Mode 3OP2 — 3-wire open delta using 2 CTs (2 element) 4LN3 — 4-wire WYE using 3 PTs (3 element), line-to- neutral voltage readings…
-
Page 30: Device Gsd File
6 Device GSD File ;============================================================ ; Profibus Device Database of HMS Industrial Networks AB ; Model : ANYBUS-IC PDP ; Description : ANYBUS-IC Profibus DP slave ; Language : English ; Date : 30 September 2003 ; Author : HMS Industrial Networks AB ;…
-
Page 31
Implementation_Type = «SPC3» ; Supported DP features Freeze_Mode_supp ; supported Sync_Mode_supp ; supported Auto_Baud_supp ; supported Set_Slave_Add_supp ; supported ; Maximum polling frequency Min_Slave_Intervall ; 100 us ; Maximum supported sizes Modular_Station ; modular Max_Module = 24 Max_Input_Len = 48 Max_Output_Len = 48 Max_Data_Len… -
Page 32
Module = «OUTPUT: 4 Byte ( 2 word)» 0x61 EndModule Module = «OUTPUT: 8 Byte ( 4 word)» 0x63 EndModule Module = «OUTPUT: 16 Byte ( 8 word)» 0x67 EndModule Module = «OUTPUT: 32 Byte (16 word)» 0x6F EndModule…
Приборы для измерений показателей качества и учета электрической энергии PM130P Plus, PM130E Plus, PM130EH Plus
Изделие зарегистрировано в Госреестре под номером 36128-07
НАЗНАЧЕНИЕ И ОБЛАСТЬ ПРИМЕНЕНИЯ
Приборы для измерений показателей качества и учета электрической энергии РМ130Р Plus, РМ130ЕН Plus (далее — измерители) предназначены для измерения и регистрации основных параметров электрической энергии в однофазных двухпроводных, трехфазных трёх- и четырёхпроводных электрических сетях с номинальной частотой 50 Гц и 60 Гц (специальные версии для частоты 25 и 400 Гц). Область применения -предприятия электрических сетей, электростанции, генераторы, насосные установки электрические подстанции, промышленные предприятия, метрологические службы, измерительные и испытательные лаборатории, офисные здания и торговые центры.
Измерители предназначены для эксплуатации внзггри закрытых помещений, в том числе и в неотапливаемых, шкафов или щитов при отсутсвии конденсата.
ОПИСАНИЕ
Принцип действия измерителей основан на одновременном измерении мгновенных значений токов и напряжений в каждой из фаз сети. Измерения производятся с помощью быстрого аналого-цифрового преобразователя и производятся с частотой, в 32 или 64 раза превосходящей сетевую частоту. Информация о мгновенных значениях величин поступает в микропроцессор, где вьиисляются различные параметры электроэнергии. Запись выбранных для регистрации параметров производится во внутреннюю память прибора, информация из которой может быть выведена через цифровой интерфейс для дальнейшей обработки или хранения. Выбор регистрируемых параметров, режимов измерений и прочие настройки прибора могут производиться дистанционно, через цифровой интерфейс, а также с помощью кнопок управления. Измерители имеют порты коммуникации RS-485, протоколы ASCII, Modbus и DNP3.0. Возможна установка дополнительного коммутационного порта Ethernet; протоколы Modbus TCP и DNP3 TCP. Приборы оснащены 3-х оконным светодиодным индикатором (дисплеем). Модель РМ130Р Plus является базовой, у модели РМ130ЕН Plus расширены измерительные возможности.
В таблице 1 указаны величины, измеряемые различными моделями.
Таблица 1. Величины, измеряемые различными моделями измерителей серии PM130PIus:
Таблица 1. Величины, измеряемые различными моделями измерителей серии PM130PIus:
величина |
РМ130Р Plus |
РМ130Е Plus |
РМ130ЕН Plus |
Ток |
+ |
+ |
+ |
Напряжение |
+ |
+ |
+ |
Частота |
+ |
+ |
+ |
Коэф.мощности |
+ |
+ |
+ |
Активная мощность |
+ |
+ |
+ |
Реактивная мощность |
+ |
+ |
+ |
Полная мощность |
+ |
+ |
+ |
Активная энергия |
+ |
+ |
|
Реактивная энергия |
+ |
+ |
|
Полная энергия |
+ |
+ |
|
Коэффициент искажения синусоидальности тока и напряжения |
+ |
||
Коэффициенты гармонических состовляющих тока и напряжения |
+ |
||
Сдвиг фаз |
+ |
Все модели могут быть оснащены одним из 4-х дополнительных модулей:
1. Модуль коммутационного порта Ethernet.
2. Модуль аналоговых выходов: 4 оптически изолированных аналоговых выхода с внутренним источником питания (0-20 мА, 4-20 мА, 0-1 мА, ±1 мА).
3. Модуль 4-х цифровых входов и 2-х релейных выходов.
4. Модуль 4-х цифровых входов и батареи, обеспечивающей автономное питание часов (до 5 лет) при перерывах в электропитании. Без этого модуля показания часов при отключении электропитания сохраняются в течение 30 сек. Заказ и использование многотарифной системы учета возможно только при наличии данного модуля.
ОСНОВНЫЕ ТЕХНИЧЕСКИЕ ХАРАКТЕРИСТИКИ
Условия окружающей среды
Рабочая температура: -20°С до 60°С Температура хранения: -25°С до 80°С Влажность: О до 95 % без конденсата
Габаритные размеры: длина 114мм, ширина 114 мм, глубина 109 мм; масса — 0,7 кг.
Гарантийный срок — 3 года со дня изготовления. Время наработки на отказ — 92000 часов.
Таблица 2 — Основные метрологические характеристики
Таблица 2 — Основные метрологические характеристики
Величины |
Предельное значение |
Номинальные значения |
Пределы допускаемой основной относительной погрешности |
Линейное напряжение, В |
3*800 или 3*144 |
3*690 или 3*120 |
0,2 % |
Ток, А |
6 или 15 |
1 или 5 |
0,2 % |
Частота, Гц |
15-480 |
50 или 60; спец. версии — 25 или 400 |
0,02 % |
Коэффициент мощности при токе 5-200 % и напряжении 10-120 % от номинальных значений |
От-1 до+1 |
±0,2 % для диапазонов от 0,5 до 1,0 и от-1 до -0,5 |
|
Активная мощность |
Класс 0.5S 0,5 S по ГОСТ Р 523232005 (ШС 62053- 22:2003) |
±0,2 % |
|
реактивная мощность |
±0,3 % |
||
полная мощность |
±0,2 % |
||
Активная энергия |
±0,2 % |
||
реактивная энергия |
±0,3 % |
||
Полная энергия |
±0,2 % |
||
Коэффициент искажения синуса (КИС) (только РМ130ЕН) |
0-100 % |
100% |
±1,5% |
Погрешности измерений для напряжения, тока, мощности и энергии даны для температурного интервала (+20 — +26) °С. За пределами этого интервала дополнительная погрешность измерения тока и напряжения составляет 0,01 % /К, мощности и энергии -0,02 %/К.
ЗНАК УТВЕРЖДЕНИЯ ТИНА
Знак утверждения типа наносится наклейкой на первую страницу руководства по эксплуатации.
КОМПЛЕКТНОСТЬ
В комплект поставки входят:
измеритель — 1 шт.;
комплект монтажных частей — 1 шт.;
руководство по установке и эксплуатации (на CD-диске) — 1 экз.;
CD с программным обеспечением и документацией — 1 шт.;
паспорт — 1 экз.;
протокол заводских испытаний — 1 шт.;
-методика поверки (на CD-диске) — 1 экз.
ПОВЕРКА
Поверка осуществляется в соответствии с документом «Приборы для измерений показателей качества и учета электрической энергии РМ130Р Plus, РМ130ЕН Plus. Методика поверки», утверждённым ФГУП «ВНИИМС» в 2007 году.
Основное оборудование, необходимое для поверки: калибратор переменного напряжения и тока многофункциональный с погрешностью не хуже 0,08 %.
Межповерочный интервал 8 лет.
НОРМАТИВНЫЕ ДОКУМЕНТЫ
ГОСТ 22261-94 «Средства измерений электрических и магнитных величин. Обпдие технические условия»;
ГОСТ 14014-91 «Приборы и измерительные преобразователи цифровые напряжения, тока, сопротивления. Общие технические условия и методы испытаний»;
ГОСТ Р 52323-2005 «Аппаратура для измерения электрической энергии переменного тока. Частные требования. Статические счетчики активной энергии классов точности 0,2S и 0,58»;
Документация фирмы-изготовителя.
ЗАКЛЮЧЕНИЕ
Тип приборов для измерений показателей качества и учета электрической энергии РМ130Р Plus, РМ130ЕН Plus утвержден с техническими и метрологическими характеристиками, приведенными в настоящем описании типа, метрологически обеспечен при выпуске из производства и в эксплуатации.
PM130 PLUS — трехфазный прибор, предназначенный для измерения основных параметров электрической сети. Серия представляет 3 модели, выполняющих измерения 80 электрических параметров локально, а также до 100 электрических параметров через интерфейс RS485. В приборе предусмотрена уникальная возможность установки одного дополнительного внешнего модуля. Прибор имеет базовые функции контроля качества электроэнергии, а также функции защиты, сигнализации и управления.
PM130P PLUS — базовая модель, измеряющая напряжение, ток, частоту, мощность и cosφ.
PM130 PLUS Powermeter Series
PM130P/PM130E/PM130EH
Installation and Operation Manual
BG0425 Rev. A15
C hapter 6 Device
C O N T R O L
Figure 6 -6: Device Control Dialog Box – Remote Relay Control Tab
114
A N D
U P G R A D I N G
Upgrading
D E V I C E
To send a remote command to a relay:
1.
Select a desired command in the Relay Command box for a relay:
2.
OPERATE – to operate a relay
3.
RELEASE – to remove your remote command, or to release a latched
relay
4.
Click Send.
Your meter has upgradeable firmware. If you need to upgrade your
device, download a new firmware file to the meter through PAS.
Firmware can be downloaded via the Modbus RTU or Modbus/TCP protocol
through any communication port.
To download a new firmware file to your device:
1.
Ensure that the communication port you are connected through to
the meter operates in Modbus mode.
2.
If you are connected to the meter through a serial interface, it is
recommended to set the port baud rate to 115,200 bps. See
Up Serial Communication Ports
protocol and baud rate in your meter.
3.
Ensure that the On-line button on the PAS toolbar is checked, and
then select Flash Downloader from the Monitor menu and confirm
downloading.
4.
Point to the firmware upgrade file for your meter, click Open, and
then confirm upgrading the meter.
F I R M W A R E
on how to remotely change the
PM130 PLUS Powermeter Series
Setting