INTERFACE

TRIO-UPS/1AC/24DC/5

Data sheet

1Description

The TRIO-UPS/1AC/24DC/5 provides an uninterruptible

24 V DC voltage at a maximum load current of up to 5 A in

both an error-free AC power supply network and in the event

of power failure.

It is designed specifically for supplying industrial PCs (IPC).

The power supply unit and the electronic switch-over unit are

housed in the same housing.

In the event of supply voltage failure, buffer mode is

activated without interruption. In this operating mode, the

output voltage is directly dependent on the battery voltage.

In the event of a voltage dip, the IPC continues operating

without interruption, thus increasing system availability.

Uncontrolled shutdown is avoided.

The TRIO-UPS/1AC/24DC/5 can be parameterized using a

service PC and the UPS-CONF configuration and

management software via an IFS-USB-PROG-ADAPTER.

For convenient parameter transfer between various TRIO-

UPS devices, the IFS-CONFSTICK configuration stick is

available as an option.

Features

–Spacesaving

The TRIO-UPS combines a power supply unit and

electronic switch-over unit in the same housing

– Flexible

Rechargeable battery module with 1.3, 3.4, 7.2 or 12 Ah

– Autonomous

In the event of AC mains failure, the industrial PC

continues operating without interruption

–Timesaving

When the supply voltage is reapplied, the industrial PC

starts automatically

– Parameterizable

Can be parameterized with the PC or configuration stick

DANGER

Never carry out work when voltage is present.

The device contains dangerous live elements and high levels of stored energy.

Depending on the ambient temperature and load, the housing can become very hot.

Make sure you always use the latest documentation.

It can be downloaded at www.phoenixcontact.net/download.

This data sheet is valid for all products listed under «Ordering data» on page 3.

Uninterruptible power supply with integrated power

supply unit

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 2

2Table of contents

1 Description…………………………………………………………………………………………………….………… 1

2 Table of contents ………………………………………………………………….…………………………………….. 2

3 Ordering data…………………………………………………………………………………………………..…………. 3

4 Technical data ……………………………………………………………………………….…………………………… 3

4.1 I/O data…..………..………..…………..…………………..…………..………..………..…………....……………………..…………. 3

4.2 Battery management…………………..…………..………..……………………..………..…………..…….…….…………..……. 4

4.3 Signaling and switching outputs ……………………..………..…………..………..…………..…………..………..…………. 5

4.4 Ambient conditions…………………………..…………..………..…………..………..…………..……….….……………………... 5

4.5 Standards/approvals .………..…………..………..…………..………..…………..……………………..………..………..……. 6

5 Safety regulations ………………….……………………………………………..…………………………………….. 7

6 Connection, operating, and indication elements …………………………………………..………………….. 8

6.1 Connection terminal blocks …………….…………..………..…………..…………..………..…………..….………….…………. 8

6.2 Block diagram …………..…………..………..…………..………..…………..………..…………..……..……………..……………. 9

6.3 Input …………………..…………..………..………..…………..……………………..………..…………..………..………..…………. 9

6.4 Output ………………..………..………..…………..……………………..………..…………..………..………..………..……….. 10

6.5 LED indicators..……………………..………..………..…………..………..…………..………..……….…….………..………….. 10

7 Installation …………………………………………………………………………..……………………….……………11

7.1 Narrow mounting position…………………….………..…………..………..…………..………..…………..…………..……….. 11

7.2 Flat mounting position ………………………………………….………..…………..……………………....………………………. 11

8 Rechargeable battery module……………………………………………………………………………..………..12

9 Method of operation……………………………………………………………………………………………..……..13

9.1 Output voltage…………..………..…………..…………………….………..…………..………………………………….…………. 13

9.2 Remote shutdown ………….…………..…………………….……………………..………..…………..…………………………… 13

9.3 Buffer time setting ……………….………..…………..………..…………..………..…………..………..…………………………. 13

9.4 PC mode …………….…………..…………………….…………………….……………………..………..………………..…………. 13

9.5 PC idle time………………..…………..……………………..………..………..…………..………..…..…………………..……….. 14

9.6 Battery management…………………..…………..…………………….……………………..…………………………………….. 15

10 Interfaces………………………………………………………….……………………………………………………….15

10.1 Config.-Port …………………..…………..………..…………..……………………..………..……………………….…………..….. 15

10.2 IFS-USB-PROG-ADAPTER .…………………….…………..………..…………..……………………..………...………….….. 15

10.3 IFS-CONFSTICK………………………..………..…………..……………………..………..…………..…..………………..…….. 15

11 UPS-CONF configuration and management software ………………………….…………………………..16

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 3

3Ordering data

4 Technical data

4.1 I/O data

UPS system

Description Type Order No. Pcs./Pkt.

Uninterruptible power supply with integrated power supply unit TRIO-UPS/1AC/24DC/5 2866611 1

The TRIO-UPS/1AC/24DC/5 is supplied without a rechargeable battery module. The rechargeable battery module must be ordered

separately (see accessories).

Accessories

Description Type Order No. Pcs./Pkt.

Rechargeable battery module, 24 V DC, 1.3 Ah MINI-BAT/24DC/1.3AH 2866417 1

Rechargeable battery module, 24 V DC, 3.4 Ah QUINT-BAT/24DC/3.4AH 2866349 1

Rechargeable battery module, 24 V DC, 7.2 Ah QUINT-BAT/24DC/7.2AH 2866352 1

Rechargeable battery module, 24 V DC, 12 Ah QUINT-BAT/24DC/12AH 2866365 1

Configuration and management software UPS-CONF 2320403 1

USB data link cable between the UPS and IPC IFS-USB-PROG-ADAPTER 2811271 1

Configuration stick for parameter transfer between various

TRIO-UPS/1AC/24DC/5 devices

IFS-CONFSTICK 2986122 1

Input data

Nominal input voltage (wide-range input) 100 … 240 V AC

Input voltage range (nominal load) 85 … 264 V AC (< 90 V AC derating: 2.5%/V)

100 … 350 V DC (UL508: 100 … 250 V)

Frequency 45 … 65 Hz

Approximate current consumption (mains operation and battery charging/

maximum)

At 230 V AC

At 120 V AC

0.95 A/1.1 A

1.7 A/1.8 A

Inrush current limiting / I²t at 25°C typical < 44 A / < 1.3 A²s

Switch-on time after applying the mains voltage

At 230 V AC

At 120 V AC

150 ms

200 ms

Transient surge protection Varistor

Internal input fuse T 6.3 A

Recommended backup fuse

Circuit breaker 6 A/10 A/16 A (B characteristic)

Discharge current to PE 0.8 mA

Output data

Rise time < 100 ms

Residual ripple < 10 mVPP

Switching peaks < 25 mVPP

Parallel connection to increase the buffer time Yes, 2

Surge protection against internal surge voltages Yes, < 35 V DC

Maximum resistance to return supply 35 V DC

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 4

4.2 Battery management

Output data in mains operation (AC input voltage present)

Nominal output voltage UN24 V DC

Output voltage (adjustable) 22.5 … 29.5 V DC

Nominal output current, > 24 V DC constant capacity (-25°C to +70°C) 5 A

Derating (above 55°C) 2.5%/K

Current limit 6 A, approximately

Connection of capacitive loads Yes, unlimited

Control deviation < 1% (static load change 10 … 90%)

Approximate efficiency (mains operation and battery charging)

At 230 V AC

At 120 V AC

88%

86%

Approximate power dissipation (mains operation and battery charging)

At 230 V AC

At 120 V AC

16 W

20 W

Output data in battery operation (AC input voltage not present)

Nominal output voltage UN24 V DC

Output voltage (UOUT = UBAT — 0.5 V ) 27.9 … 19.2 V DC — 0.5 V

Nominal output current (-25°C to +70°C) 5 A

Derating (above 55°C) 2.5%/K

Current limit 6 A, approximately

Connection of capacitive loads Yes, 3300 µF

Efficiency > 86%

Power dissipation

Maximum no load

Maximum nominal load

2 W

4 W

Maximum buffer time (adjustable per minutes) 0.5; 1; 2; 3; 5; 10; 15; 20; PC mode

Overload fuse (electronic) Yes

Remote shutdown Yes

Battery management

Charging characteristic curve I/U

Charging current 1 (preset/minimum/maximum) 1.0 A/0.2 A/1.5 A

End-of-charge voltage 1 (preset/minimum/maximum) 27,6 V DC / 25 V DC / 30 V DC

Temperature compensation 1 (preset/minimum/maximum) 42 mV/K / 0 mV/K / 200 mV/K

Battery presence check/time interval 60 s

Battery quality check 1 (preset/minimum/maximum) 12 h/4 h/200 h

Protection against total discharge 1 (preset/minimum/maximum) 19.2 V DC / 18 V DC / 21 V DC

«Battery almost flat» alarm signaling threshold 1 (preset/minimum/maximum) 20.4 V DC / 18 V DC / 30 V DC

1Can be adjusted via UPS-CONF software

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 5

4.3 Signaling and switching outputs

4.4 Ambient conditions

Status indicators

Mains voltage OK (Power in OK) Green LED, static ON

Alarm

LED indicator

Switching output

Current limit (internal)

Red LED, static ON

24 V DC, active high

200 mA

Battery operation (Battery Mode)

LED indicator

Switching output

Current limit (internal)

Signal options 1

1Can be adjusted via UPS-CONF software

Yellow LED, static ON

24 V DC, active high

200 mA

Bat.-Mode, Bat.-Mode Delayed

Battery charging (Battery Charge)

LED indicator

Switching output

Current limit (internal)

Signal options 1

Yellow LED, flashing

24 V DC, active high

200 mA

Bat.-Charge, Bat.-Mode, Bat.-Mode Delayed, battery almost flat

Climatic requirements

Ambient temperature

Operation (> 55°C derating)

Storage/transport

-25°C … +70°C

-40°C … +80°C

Humidity at +25°C, no condensation 95%

Pollution degree according to EN 50178 2

Climatic class 3K3

Mechanical requirements

Vibration (operation) < 15 Hz, amplitude ±2.5 mm according to IEC 60068-2-6

15 Hz … 150 Hz, 2.3g, 90 min.

Shock according to IEC 60068-2-27 30g in each direction

General data

Insulation voltage I/O (type/routine test) 4 kV AC/2 kV AC

Input/PE (type/routine test) 2 kV AC/2 kV AC

Output/PE (routine test) 500 V DC

Mounting position according to EN 60715

Degree of protection IP20

Protection class (with PE connection) I

MTBF according to IEC 61709 (SN 29500) > 500,000 h

Material Aluminum (AlMg3)/zinc-plated sheet steel

Dimensions (W/H/D) 60 mm x 130 mm x 118 mm

Weight 1.1 kg

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 6

4.5 Standards/approvals

Standards/approvals

Electrical equipment of machines

(surge voltage category III)

EN 60204

Safety transformers for switched-mode power supply units IEC 61558-2-17

Electrical safety

(of information technology equipment)

EN 60950/VDE 0805

UL/C-UL Recognized UL 60950

Industrial control equipment UL/C-UL Listed UL 508

Electronic equipment for use in

power installations

EN 50178 (VDE 0160)

PELV/SELV PELV (EN 60204)/SELV (IEC 60950)

Safe isolation VDE 0100-410

Protection against electric shock DIN 57100-410

Protection against electric shock, basic requirements for safe isolation in

electrical equipment

DIN VDE 0106-101

Limitation of mains harmonic currents EN 61000-3-2

u

U

Conformance with EMC Directive 2004/108/EC, noise immunity according to 2006/95/EC

(electromagnetic compatibility)

Noise immunity according to EN 61000-6-2

Electrostatic discharge according to EN 61000-4-2 Housing

Contact discharge

Air discharge

Remark

Level 3

6 kV

8 kV

Criterion B

Electromagnetic HF field according to EN 61000-4-3 Housing

Frequency range

Field strength

Remark

Level 3

80 MHz … 2 GHz

10 V/m

Criterion A

Fast transients (burst) according to EN 61000-4-4 Input

Output

Signal

Remark

4 kV (Level 4 — asymmetrical: Cable to ground)

2 kV (Level 4 — asymmetrical: Cable to ground)

1 kV (Level 4 — asymmetrical: Cable to ground)

Criterion B

Surge current loads (surge) according to EN 61000-4-5 Input

Output

Signal

Remark

4 kV (Level 4 — asymmetrical: Cable to ground)

2 kV (Level 4 — asymmetrical: Cable to cable)

2 kV (Level 3 — asymmetrical)

1 kV (Level 3 — symmetrical)

2 kV (Level 3 — asymmetrical)

Criterion B

Conducted interference according to EN 61000-4-6 Input/output/signal

Frequency range

Voltage

Remark

Level 3

10 kHz … 80 MHz

10 kV

Criterion A

Noise emission according to EN 61000-6-3 Radio interference voltage according

to EN 55011

EN 55011 (EN 55022) Class B, industrial and residential

applications

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 7

5Safety regulations

Installation notes

Connection notes

NOTE:

–The device must only be installed, operated,

and maintained by qualified personnel.

Follow the installation instructions.

When installing and operating the device, the

applicable safety directives (including

national safety directives), accident

prevention regulations, as well as general

technical regulations, must be observed.

For the safety data, please refer to the

package slip and certificates (conformity

assessment, other approvals, if necessary).

Do not repair the device yourself, replace it

with an equivalent device.

Repairs may only be carried out by the

manufacturer. The manufacturer is not liable

for damage resulting from violation.

The IP20 degree of protection (IEC 60529/

EN 60529) of the device is intended for use in

a clean and dry environment.

The device must not be subject to

mechanical strain and/or thermal loads,

which exceed the limits described.

NOTE: Electrostatic discharge

The device contains components that can be

damaged or destroyed by electrostatic discharge.

When handling the device, observe the

necessary safety precautions against

electrostatic discharge (ESD) according to

EN 61340-5-1 and EN 61340-5-2.

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 8

6Connection, operating, and indication

elements

Figure 1 TRIO-UPS/1AC/24DC/5 structure

6.1 Connection terminal blocks

Use a screwdriver with the correct blade width for wiring. For

reliable and safe-to-touch connections, strip 8 mm off the

cable ends.

The following cable cross-sections can be connected:

No. Description

1100 … 240 V AC input

224 V rechargeable battery module connection

324 V DC output, buffered

422.5 … 29.5 V DC potentiometer

5Active switching output: Alarm

6Active switching output: Bat.-Mode

7Active switching output: Bat.-Charge

8Red LED indicator: Alarm

9Yellow LED indicator: Bat.-Mode/Bat.-Charge

0Green LED indicator: Power in OK/Overload

!Remote shutdown (R1, R2)

«Buffer time setting

0.5 … 20 minutes, PC mode, unlimited

§Config.-Port

$«Confirm» button

Bat.- Mode

Bat.- Charge

Remote R1

Alarm

Battery

3

5

10

15

20

PC-Mode

12

8

+

+

+

OFF

ON

Remote R2

TRIO DC-UPS

t

max

min

L

N

Alarm

Adjust

Output DC

24V 5A

Input AC

100-240 V

22.5-29.5 V

Bat.-Mode

Bat.-Charge

Power in OK

Overload

Config.-Port

(Default 0.5)

Custom

UPSSTICK

DATA

1. Press Button and

2. Insert STICK within 4sec

STICK UPS

DATA

1. Insert STICK

2. Press Button > 6sec

(+)

(-)

1

13

14

4

3

5

6

7

11

2

12

8

9

10

Terminal

block

Rigid Stranded AWG Tightening

torque

No. [mm²] [mm²] [Nm] [lb in]

13,

57,

!

0.2 — 2.5 0.2 — 2.5 24 — 12 0.5 — 0.6 3.5 — 4.5

In order to comply with UL approval, use copper

cables that are designed for operating

temperatures >75°C.

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 9

6.2 Block diagram

Figure 2 Block diagram for the TRIO-UPS/1AC/24DC/5

6.3 Input

The 100 240 V AC connection is made using the L (+) and

N (-) screw connections.

Device installation must be carried out according to the

regulations of EN 60950. It must be possible to switch off the

device using a suitable disconnecting device outside the

power supply.

An internal fuse is provided for device protection. Additional

device protection is not required.

Network type

The device can be connected to single-phase AC networks

or to two of the phase conductors of three-phase systems

(TN, TT or IT networks according to VDE 0100-300/IEC

60364-3) with nominal voltages of 100 V AC … 240 V AC.

Figure 3 Single-phase network systems

t…[min]

JJ

Output DC

24V5A

Remote

On/Off

2x 12V

Battery

PS

Alarm

Bat.-Charge

Bat.-Mode

IFS Config.-Port

Confirm

L (+)

N (-)

R1

R2

For example, primary side line protection could

be used.

If an internal fuse is blown, this is due to a device

fault. In this case, send the device to Phoenix

Contact for inspection.

For operation using two phase conductors of a

three-phase system, an all-pole disconnecting

device must be provided.

TN-S

L

N

PE

+

LN

TT

+

LN

L

N

TN-C

L

PEN

+

LN

iT

+-

LN

L1

L2

L3

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 10

6.4 Output

The 24 V DC connection is made using the «OUT DC 24 V,

+, -» screw connections. The output voltage set upon

delivery is 24 V DC. The output voltage can be set from

22.5 V DC to 29.5 V DC on the potentiometer.

Figure 4 Connection

6.5 LED indicators

Figure 5 LED indicators

The signal outputs are connected via the «Alarm», «Bat.-

Mode», and «Bat.-Charge» terminal blocks. There are three

LED status indicators and three active switching outputs for

function monitoring.

No. Description

1100 … 240 V AC input

324 V DC output, buffered

422.5 … 29.5 V DC potentiometer

No. Description

8Red LED indicator: Alarm

9Yellow LED indicator: Bat.-Mode/Bat.-Charge

0Green LED indicator: Power in OK/Overload

Bat.- Mode

Bat.- Charge

Remote R1

Alarm

Battery

3

5

10

15

20

PC-Mode

12

8

+

+

+

OFF

ON

Remote R2

TRIO DC-UPS

t

max

min

L

N

Alarm

Adjust

Output DC

24V 5A

Input AC

100-240 V

22.5-29.5 V

Bat.-Mode

Bat.-Charge

Power in OK

Overload

Config.-Port

(Default0.5)

Custom

UPS STICK

DATA

1. Press Button and

2. Insert STICK within 4sec

STICK UPS

DATA

1. Insert STICK

2. Press Button > 6sec

(+)

(-)

4

1

3

8

9

10

Status

Green

Yellow

Red

Description

1

The UPS is switched off or the UPS

is operating in mains mode, battery

mode is deactivated (remote),

battery management is still active

2

The UPS is starting mains

operation, for the LED test all LEDs

are switched on and off again once

before the current operating state is

indicated

3

The UPS is operating in mains

mode, the battery is OK and

charged

4

The UPS is operating in mains

mode, the battery is OK and is

charging (charge < 85% of nominal

capacity)

5

The UPS is operating in battery

mode, the battery voltage UBAT

is > 20.4 V

6

The UPS is operating in battery

mode, the battery is almost flat

(battery voltage UBAT is < 20.4 V)

7

UPS protection against total

discharge has terminated battery

mode

(battery voltage UBAT = 19.2 V) and

continues indication for a maximum

of 10 hours

8The UPS is operating in mains

mode, the battery is faulty

9

The UPS has been overloaded in

mains mode, the battery is OK and

charged

10 The UPS has been overloaded in

mains mode, the battery is faulty

Key

LED OFF

LED ON

LED flashing

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 11

7 Installation

A minimum spacing between other devices does not have to

be observed in order to ensure correct device function.

7.1 Narrow mounting position

The power supply unit can be snapped onto all DIN rails

according to EN 60715 and must be mounted horizontally

(connection terminal blocks facing upwards and

downwards).

Mounting

Position the module with the DIN rail guideway on the top

edge of the DIN rail and then snap it downwards.

Figure 6 Mounting the TRIO-UPS/1AC/24DC/5

Removal

Release the snap-on catch using a screwdriver and then

detach the module from the bottom edge of the DIN rail.

Figure 7 Removing the TRIO-UPS/1AC/24DC/5

7.2 Flat mounting position

A flat mounting position can be achieved by mounting the

module onto the DIN rail at a 90° angle. Mount the DIN rail

adapter (UTA 107) as shown in the figure. The screws that

were previously used to secure the UTA must be used: Torx

T10 (0.8 Nm … 0.9 Nm tightening torque).

Figure 8 Modification for flat mounting position

B

A

A

B

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 12

8 Rechargeable battery module

The rechargeable battery module is connected to the power

supply unit via the «Battery +» and «Battery -» terminal blocks

2.

The following rechargeable battery modules are

recommended:

Figure 9 Characteristic curves for the rechargeable

battery modules

Battery mode can be exited after a predefined time has

elapsed or by means of external shutdown. If the device is

to be shut down after a specific time has elapsed, the time

can be set via the selector switch «on the front of the

device. When the supply voltage is reapplied, the device

can switch to battery mode again.

NOTE: Risk of short circuit

The fuse for the rechargeable battery module

must be removed when installing or replacing the

module.

Rechargeable battery

module

Fuse Recom-

mended

charging

current

1MINI-BAT/24DC/1.3Ah 15 A 0.8 A 2

2QUINT-BAT/24DC/3.4Ah 1

1Connection via plug connector, 14 mm

25 A 1.0 A 2

2Can be adjusted via UPS-CONF software

3QUINT-BAT/24DC/7.2Ah12×25A 1.5A

2

4QUINT-BAT/24DC/12Ah12×25A 1.5A

2

t [min]

t [h]

I[A]

0 0.5 2 4

1

10

11 1.5 2.5 3 3.5 4.5 5

60

10

30

1

2

3

4

= 1.3Ah

= 3.4Ah

= 7.2Ah

= 12Ah

4

13

2

The batteries are sealed, maintenance-free

lead AGM batteries, which are intended for

operating temperatures of 0°C … 40°C.

They have a service life of six to nine years at an

ambient temperature of 20°C.

In order to ensure immediate availability, all

batteries are supplied fully charged. Startup

should be carried out at the latest after nine

months at 20°C … 30°C, or after six months at

30°C … 40°C.

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 13

9 Method of operation

9.1 Output voltage

In mains operation (AC input voltage present) the output

voltage of the TRIO-UPS corresponds to the setting at the

potentiometer 4. In the event of supply voltage failure,

battery mode is activated without interruption. The output

voltage is now directly dependent on the battery voltage and

is UBAT — 0.5 V.

9.2 Remote shutdown

If the connected load cannot be supplied from the power

storage device in the event that the AC voltage fails, the

UPS can be disabled via R1/R2. This shutdown can be

performed during mains operation or while battery mode is

active.

UPS active, remote shutdown deactivated, default upon

delivery:

Terminal points «R1» and «R2» are short circuited (with

plug-in bridges by default upon delivery) OR 24 V DC is

present at terminal point «R2».

If the supply voltage fails, the TRIO-UPS switches to

battery mode. UPS not active, remote shutdown

activated:

Terminal points «R1» and «R2» are not short circuited

AND 0 V DC is present at terminal point «R2».

All LEDs are OFF.

If the supply voltage fails, the TRIO-UPS does not

switch to battery mode, the device shuts down.

The connected loads are supplied and the

rechargeable battery module is charged as long as the

supply voltage is present.

9.3 Buffer time setting

The time after which battery mode is exited is set via the «

selector switch on the front of the device:

0.5 to 20 minutes

Parameterizable time via software

(«CUSTOM» switch position, default: 0.5 minutes)

Unlimited (buffering with the total stored energy)

PC mode (see Section 9.4 «PC mode» )

9.4 PC mode

In «PC mode», the UPS function follows a chronological

sequence that can be parameterized via the software and

individually optimized for the relevant IPC solution.

Requirements: IFS-USB-PROG-ADAPTER data cable

(Order No. 2811271) and UPS-CONF software

(Order No. 2320403).

To set the parameters, an Interface interface (IFS) is used

for data exchange between the TRIO-UPS and a suitable

user interface on the IPC. The user is supported by help

texts and graphics for the individual parameters.

As an option, parameterization can be carried out using an

IFS-CONFSTICK. Here, a parameter record is transferred

from the TRIO-UPS to the IFS-CONFSTICK. This

parameter record can then be written to any other

TRIO-UPS.

In «PC mode», the UPS function follows a parameterizable

chronological sequence of delay time, IPC shutdown, and

IPC idle time.

Delay time:

If the mains voltage is not applied again within the first 60

seconds of battery mode, for example, «Bat.-Mode» is

indicated in order to shut down an IPC with a delay.

IPC shutdown:

Shutdown is performed via a data cable to the IPC. The IPC

must be connected to the UPS via a USB data cable.

The IPC is supplied by the TRIO-UPS for a parameterizable

period of time, e.g., 2 minutes.

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 14

9.5 PC idle time

Once the «PC shutdown» time has elapsed, the output voltage is switched off, e.g., for 30 seconds (also when the mains

voltage is applied again).

Figure 10 Time diagrams

120/230V

0V

24V

0V

24V

0V

ON

OFF

ON

OFF

ON

OFF

1

3

6

10

9

AC input

DC output

LED green

POWER IN OK

LED gelb

Bat.-Mode

PC response

Delay time PC shutdown

Bat. mode delayed:

Active switching output

(can be parameterized)

Power comes back on during set delay time

1

3

6

10

9

AC input

DC output

LED green

POWER IN OK

LED yellow

Bat. mode

PC response

Bat. mode delayed:

Active switching output

(can be parameterized)

PC shutdown PC

idle time

Power comes back on during set time PC shutdown

Delay time

120/230V

0V

24V

0V

24V

0V

ON

OFF

ON

OFF

ON

OFF

1

3

6

10

9

TRIO-UPS/1AC/24DC/5

104103_en_00 PHOENIX CONTACT 15

9.6 Battery management

Battery management of the TRIO-UPS is divided into two

checks that are performed cyclically during normal

operation.

Battery presence check

The battery presence check is used to detect a correctly

installed battery. If this is not the case, the check is failed

and the green 0 and red 8 LED indicators are controlled

statically.

Battery quality check

The battery quality check is a lifecycle test. It enables

conclusions to be drawn, e.g., regarding the maximum

lifecycle of the battery if the maximum charging time has

been exceeded. In this case, the green 0 and red 8 LED

indicators are controlled statically.

10 Interfaces

10.1 Config.-Port

The TRIO-UPS is connected to the USB connection on the

service PC via the «Config.-Port» using the IFS-USB-PROG-

ADAPTER data cable.

10.2 IFS-USB-PROG-ADAPTER

The programming adapter (Order No. 2811271) represents

the interface between the service PC and the TRIO-UPS

and is required in order to parameterize the TRIO-UPS.

Figure 11 Programming adapter

10.3 IFS-CONFSTICK

The IFS-CONFSTICK is a multi-functional memory block for

easy storage and back up of configuration and parameter

data.

Transferring parameters to the IFS-CONFSTICK

To transfer parameters, proceed as follows:

1. Press and hold down the «Confirm» button.

2. You now have four seconds to carefully insert the

IFS-CONFSTICK in the «Config.-Port» on the

TRIO-UPS, taking care to observe the connection

direction.

3. Parameter transfer is started and indicated by the cyclic

control of the three LED indicators. Sequence: Red —

Yellow — Green

a) Error-free transfer:

Green LED indicator ON

b) Transfer error:

Red LED indicator ON

Transferring parameters to the TRIO-UPS

To transfer parameters, proceed as follows:

1. Carefully insert the IFS-CONFSTICK in the «Config.-

Port» on the TRIO-UPS, taking care to observe the

connection direction.

1. Press and hold down the «Confirm» button for at least

six seconds.

2. Parameter transfer is started and indicated by the cyclic

control of the three LED indicators. Sequence: Green —

Yellow — Red

a) Error-free transfer:

Green LED indicator ON

b) Transfer error:

Red LED indicator ON

The following can be parameterized:

–Times

Switching outputs

Battery management

SerialNo.XXXXXXXXXX

www.interface.phoenixcontact.com

IFS-USB-PROG-ADAPTER

Ord.-No.: 2811 271

32825Blomberg,Germany

USB-ProgrammingAdapter

USB

TRIO-UPS/1AC/24DC/5

104103_en_00 16

PHOENIX CONTACT GmbH & Co. KG • 32823 Blomberg • Germany • Phone: +49 — 52 35 — 30 0

PHOENIX CONTACT • P.O.Box 4100 • Harrisburg • PA 17111-0100 • USA • Phone: +717-944-1300

www.phoenixcontact.com

11 UPS-CONF configuration and

management software

The Windows-based UPS-CONF configuration and

management software (Order No. 2320403) is used to

parameterize the TRIO-UPS.

Various dialog boxes are available for parameterization.

The current operating status of the TRIO-UPS is always

displayed at the bottom of the dialog box.

Figure 12 Example, TRIO-UPS status display

A distinction is made between the following states:

The UPS-CONF configuration and management

software can be downloaded free of charge at

www.phoenixcontact.net/download.

Status Meaning

Operation mode Preset operating mode at the

selector switch «

Power Source Power source that is currently

active

Battery Condition Current battery charging state

Device Status Current state of the TRIO-UPS

Connection to UPS Connection status between service

PC and TRIO-UPS

If an alarm is detected or an existing online

connection between the IPC and TRIO-UPS is

interrupted, the UPS-CONF dialog box is

automatically displayed on screen.

The status is queried cyclically.

Ваш город: Москва

Ваш или ближайший к вам город: Москва

Часы работы 9:00-18:00


  • Описание

  • Характеристики

Источник бесперебойного питания (ИБП) постоянного тока ИБП TRIO-UPS/1AC/24DC/5 серии TRIO POWER обеспечит ваше оборудование с потребляемым током до 5 А бесперебойным питанием электроэнергией высокого качества напряжением 24 В. Основная сфера применения – промышленная автоматизация.

ИБП TRIO-UPS/1AC/24DC/5 выполнен в виде настенного блока для крепления на DIN-рейку. ИБП обеспечивает автоматическое переключение нагрузки на работу от внешней аккумуляторной батареи (АКБ) при пропадании входного напряжения и обратно, заряд АКБ и ее защиту от глубокого разряда, стабилизацию выходного напряжения при работе от сети, локальную и дистанционную сигнализацию состояния, дистанционную настройку параметров ИБП.

Функциональные и конструктивные особенности ИБП TRIO-UPS/1AC/24DC/5

  • топология off-line;
  • металлический корпус для крепления на DIN-рейку с помощью адаптера UTA 107 (поставляется в комплекте с ИБП), возможно крепление на вертикальную плоскую поверхность с помощью адаптера UWA 182/52 (опция) или монтажную рейку S7-300 с помощью адаптера QUINT-PS-ADAPTERS7/2 (опция);
  • возможность крепления как к задней, так и к боковой панели;
  • возможность работы от сети как переменного, так и постоянного тока;
  • электронная защита от перегрузки, короткого замыкания и аварийно высокого выходного напряжения (>35 В);
  • внешние аккумуляторные модули емкостью 1,3-12 А*ч (опция);
  • стабилизация выходного напряжения при работе от сети;
  • естественное охлаждение;
  • входной плавкий предохранитель;
  • заряд АКБ с термокомпенсацией;
  • защита АКБ от глубокого разряда;
  • светодиодные индикаторы состояния ИБП и АКБ;
  • возможность ограничения времени автономной работы с помощью регулятора на передней панели;
  • возможность дистанционного мониторинга через выходные переключающие контакты и дистанционного мониторинга/настройки параметров ИБП через компьютерный интерфейс с помощью адаптера IFS-USB-PROG-ADAPTER (опция) и свободно распространяемого ПО Phoenix Contact;
  • клеммные колодки с винтовым креплением для сечений провода 0,2-2,5 мм².

Для приобретения ИБП TRIO-UPS/1AC/24DC/5 воспользуйтесь инструкцией «Как купить продукцию».

Тип корпуса

для крепления на DIN-рейку

Вид охлаждения

естественное

Функционал

бесперебойное электроснабжение

Номинальное входное напряжение, В

100-240 AC/DC

Диапазон входного напряжения, В

85-264 AC/100-350 DC

Номинальная частота, Гц

50/60

Диапазон частоты, Гц

45-65

Максимальный входной ток, А

1,1 (при Uвх=230 В AC); 1,8 (при Uвх=120 В AC)

Номинальное выходное напряжение, В

24 DC

Возможность параллельной работы

есть

Действующее значение пульсаций выходного напряжения, мВ

<=25

Номинальный выходной ток, А

5

Максимальный зарядный ток, А

1,5

Допустимый диапазон изменения нагрузки, %

0-100

Электрическая прочность между входом и выходом, кВ

4

Электрическая прочность между входом и корпусом, кВ

2

Электрическая прочность между выходом и корпусом, кВ

0,5

Защита от перегрузки и КЗ

электронная

Диапазон температуры окружающей среды, °С

-25…+70 (>+55 — ухудшение параметров)

Диапазон температуры окружающей среды при транспортировке и хранении, °С

-40…+80

Относительная влажность воздуха, %

0…95

Наработка на отказ (MTBF), ч

500 000

Габаритные размеры (ШхВхГ), мм

60 x 130 x 118

Ваш или ближайший к вам город

Москва

Да, все верно

Выбрать другой

Внутренний код:
PC-2866611

Phoenix contact

Если Вы готовы рассматривать аналоги, просьба сообщить об этом при запросе.
Возможные производители: KLEMSAN

Срок поставки 14-16 недель

Рассчитать доставку

  • Описание
  • Оплата
  • Доставка
  • Отзывы

Источники бесперебойного питания со встроенным блоком питания, 5 А, вместе с компонентами MINI-BAT/24/DC/1.3 AH, QUINT-BAT/24DC 3,4AH, 7,2AH или 12 AH

Описание изделия

Модуль БП TRIO со встроенным источником питания особенно компактен: модуль БП и блок питания в одном корпусе. Для формирования полноценной системы бесперебойного питания требуется всего один энергоаккумулятор.
Энергоаккумуляторы со свинцовой технологией AGM имеют время автономной работы до двух часов при токовой нагрузке 5 А.

Преимущества для Вас

  • Независимость — в случае исчезновения напряжения в сети перем. тока промышленные ПК продолжат работу без перерыва
  • Экономия времени — при возобновлении подачи электроснабжения запуск промышленного ПК произойдет автоматически

Коммерческие данные

Код заказа 2866611
Упаковочная единица 1 stk
Страница каталога Стр. 300 (C-4-2017)
GTIN 4046356311809
Вес/шт. (без упаковки) 1 147,000 GRM

Размеры

Ширина 60 мм
Высота 130 мм
Глубина 118 мм

Окружающие условия

Степень защиты IP20
Температура окружающей среды (при эксплуатации) -25 °C … 70 °C (> 55 °C — ухудшение характеристик: 2,5%/K)
Температура окружающей среды (хранение/транспорт) -40 °C … 80 °C
Макс. допустимая отн. влажность воздуха (при эксплуатации) 95 % (При 25 °C, без выпадения конденсата)
Климатический класс 3K3 (согласно EN 60721)
Степень загрязнения 2

Входные данные

Диапазон номинальных напряжений на входе 100 В AC … 240 В AC
Диапазон входных напряжений переменного тока 85 В AC … 264 В AC (Ухудшение характеристик при напряжении
Диапазон входных напряжений постоянного тока 100 В DC … 350 В DC (UL508: 100 … 250 В)
Время автономной работы настраивается: 0,5 мин; 1 мин; 2 мин; 3 мин; 5 мин; 10 мин; 15 мин; 20 мин; режим PC
Потребляемый ток 1,1 A (макс. 230 В AC)
1,8 A (макс. 120 В AC)
Ограничение пускового тока/I²t 2c
Время автономной работы см. диаграмму
Время включения, типовое 150 мс (230 В AC)
200 мс (120 В AC)
Коэффициент мощности (cos phi) около 0,5
Защитная схема Защита от перенапряжений при переходных процессах Варистор
Входной предохранитель, встроенный 6,3 A (инертного типа, внутренний)

Выходные данные

Номин. напряжение на выходе 24 В DC
Диапазон настройки выходного напряжения (USet) 22,5 В DC … 29,5 В DC (Работа от сети; буферный режим работы в зависимости от напряжения аккумулятора 27,9 В DC … 19,2 В DC)
Номинальный ток на выходе (IN) 5 A (-25 °C … 55 °C)
Изменение хар-к 55 °C … 70 °C (2,5 % / K)
Ограничение тока на выходе макс. 6 A (Питание от сети)
Рассогласование
КПД > 88 % (230 В B AC, работа от сети)
> 86 % (120 В B AC, работа от сети)
> 86 % (Питание от аккумулятора)
Остаточная пульсация (ДА)
Коммутационные пики, номинальная нагрузка (ДА)
Возможность параллельного подключения да, 2
Защита от внутреннего перенапряжения
Устойчивость к обратной связи 35 В DC

Общие сведения

Технология IQ нет
Вес нетто 1,1 кг
Носитель информации внешний, аккумулятор 1,3 Aч / 3,4 Aч / 7,2 Aч / 12 Aч
Режим работы
Напряжения изоляции на входе / выходе 4 кВ (Типовое исп.)
2 кВ (Выборочное исп.)
Степень защиты I
MTBF (IEC 61709, SN 29500)
> 596000 ч (40 °C)
Монтажное положение горизонтальная DIN-рейка NS 35, EN 60715
Указания по монтажу присоединяемый: горизонтально 0 мм, вертикально 50 мм

Характеристики клемм, вход

Тип подключения Винтовые зажимы
Сечение жесткого проводника мин. 0,2 мм²
Сечение жесткого проводника макс. 2,5 мм²
Сечение гибкого проводника мин. 0,2 мм²
Сечение гибкого проводника макс. 2,5 мм²
Сечение проводника AWG, мин. 24
Сечение проводника AWG, макс. 12
Резьба винтов M3

Характеристики клемм, выход

Тип подключения Винтовые зажимы
Сечение жесткого проводника мин. 0,2 мм²
Сечение жесткого проводника макс. 2,5 мм²
Сечение гибкого проводника мин. 0,2 мм²
Сечение гибкого проводника макс. 2,5 мм²
Сечение проводника AWG, мин. 24
Сечение проводника AWG, макс. 12
Длина снятия изоляции 8 мм
Резьба винтов M3

Параметры подключения сигнализации

Сечение жесткого проводника мин. 0,2 мм²
Сечение жесткого проводника макс. 2,5 мм²
Сечение гибкого проводника мин. 0,2 мм²
Сечение гибкого проводника макс. 2,5 мм²
Сечение проводника AWG, мин. 24
Сечение проводника AWG, макс. 12
Резьба винтов M3

Процесс зарядки

Зарядная характеристика Вольтамперная характеристика
Контроль наличия батареи / временной интервал 60 c
Ток зарядки 0,2 A … 1,5 A (предварительно установлено 1,0 А)
Конечное напряжение заряда 25 В DC … 30 В DC (предварительно установлено 27,6 В DC)
Температурная компенсация 0 мВ/К … 200 мВ/К (предварительно установлено: 42 мВ/К)
Проверка качества аккумулятора 4 ч … 200 ч (предварительно установлено 12 ч)
Защита от глубокого разряда 18 В DC … 21 В DC (предварительно установлено 19,2 В DC)
Порог аварийной сигнализации 18 В DC … 30 В DC (предварительно установлено 20,4 В DC)

Стандарты и предписания

Электромагнитная совместимость Соответствие директиве EMV 2014/30/EU
Излучение помех EN 55011 (EN 55022)
Помехоустойчивость EN 61000-6-2:2005
Подключение согласно стандарту CUL
Стандарты / нормативные документы EN 61000-4-2
Разряд между контактами 6 кВ
Стандарты / нормативные документы EN 61000-4-3
Диапазон частот 80 МГц … 2 ГГц
Напряженность проверочного поля 10 В/м
Стандарты / нормативные документы EN 61000-4-4
Примечания Критерий B
Стандарты / нормативные документы EN 61000-6-3
EN 61000-4-6
Диапазон частот 10 кГц … 80 МГц
Напряжение 10 В
Стандарты / нормативные документы EN 61000-4-11
Директива по низкому напряжению Соответствие Директиве по низкому напряжению 2006/95/ЕС
Стандарт — электробезопасность EN 60950-1/VDE 0805 (БСНН)
Стандарт — оснащение силового оборудования электронными средствами EN 50178/VDE 0160 (PELV)
Стандарт — безопасные малые напряжения EN 60950-1 (SELV)
EN 60204 (PELV)
Стандарт — безопасная изоляция DIN VDE 0100-410
Стандарт — защита от поражения электрическим током, основные требования к безопасной разводке и изоляции цепей EN 50178
Стандарт — требования к сетям питания (ограничение гармонических искажений) EN 61000-3-2
Разрешение на применение в судостроении DNV GL (EMC B)
Сертификация UL UL/C-UL, зарегистрированный UL 508
UL/C-UL одобренный UL 60950-1
Ударопрочность 18 мс, 30г на каждую ось (согласно МЭК 60068-2-27)
Вибрация (при эксплуатации)
15 Гц … 150 Гц, 2,3г, 90 мин.
Применение в железнодорожной отрасли EN 50121-4

Environmental Product Compliance

China RoHS Период времени для применения по назначению (EFUP): 25 лет;
Информация об опасных веществах приведена в декларации производителя во вкладке «Загрузки»

Классификация

eCl@ss

eCl@ss 4.0 27040603
eCl@ss 4.1 27040603
eCl@ss 5.0 27040603
eCl@ss 5.1 27040600
eCl@ss 6.0 27040600
eCl@ss 7.0 27040603
eCl@ss 8.0 27040603
eCl@ss 9.0 27040705

ETIM

ETIM 2.0 EC000382
ETIM 3.0 EC000382
ETIM 4.0 EC000382
ETIM 5.0 EC000382
ETIM 6.0 EC000382
ETIM 7.0 EC000382

UNSPSC

UNSPSC 6.01 30211510
UNSPSC 7.0901 39121011
UNSPSC 11 39121011
UNSPSC 12.01 39121011
UNSPSC 13.2 39121011

Банковский перевод: счет на оплату формируется после оформления заказа или отправки заявки в произвольной форме на электронную почту info@euro-avtomatika.ru. Специалист свяжется с вами для уточнения деталей.

Самовывоз с нашего склада:
По адресу: Московская область, Люберецкий район, п. Томилино, мкр. Птицефабрика, стр. лит. А, офис 109. Мы есть на Яндекс.Карты.

Доставка до двери
Осуществляется курьерской службой или транспортной компанией (на Ваш выбор).
Мы работаем с ведущими транспортными компаниями и доставляем заказы во все регионы России и Казахстана.

Доставка до терминала
Транспортной компании в Москва – БЕСПЛАТНО.

Phoenix contact

Нужна консультация?

Наши специалисты ответят на любой интересующий вопрос

Задать вопрос

Источник бесперебойного питания TRIO-UPS/1AC/24DC/5 Phoenix contact 2866611

Источники бесперебойного питания со встроенным блоком питания, 5 А, вместе с компонентами MINI-BAT/24/DC/1.3 AH, QUINT-BAT/24DC 3,4AH, 7,2AH или 12 AH

Преимущества для Вас

  • Независимость — в случае исчезновения напряжения в сети перем. тока промышленные ПК продолжат работу без перерыва
  • Экономия времени — при возобновлении подачи электроснабжения запуск промышленного ПК произойдет автоматически

Логотип

Размеры

Ширина 60 мм
Высота 130 мм
Глубина 118 мм

Окружающие условия

Степень защиты IP20
Температура окружающей среды (при эксплуатации) -25 °C … 70 °C (> 55 °C — ухудшение характеристик)
Температура окружающей среды (хранение/транспорт) -40 °C … 80 °C
Макс. допустимая отн. влажность воздуха (при эксплуатации) 95 % (При 25 °C, без выпадения конденсата)
Помехоустойчивость EN 61000-6-2:2005

Входные данные

Диапазон номинальных напряжений на входе 100 В AC … 240 В AC
Диапазон входных напряжений переменного тока 85 В AC … 264 В AC (Ухудшение характеристик при напряжении < 90 В пер. тока: 2,5% В)
Диапазон входных напряжений постоянного тока 100 В DC … 350 В DC (UL508: 100 … 250 В)
Диапазон частот AC 45 Гц … 65 Гц
Диапазон частот DC 0 Гц
Потребляемый ток
0,95 А
1,1 А (230 В AC)
1,7 А
1,8 А (120 В AC)
Потребляемый ток (при холостом ходе)
Потребляемый ток (в процессе загрузки)
Импульс пускового тока < 44 А (< 1,3 A2с)
Провалы напряжения в сети (см. диаграмму)
Время автономной работы настраивается: 0,5 мин; 1 мин; 2 мин; 3 мин; 5 мин; 10 мин; 15 мин; 20 мин; режим PC
Входной предохранитель 6,3 А (инертного типа, внутренний)
Коэффициент мощности (cos phi) около 0,5
Наименование защиты Защита от перенапряжений при переходных процессах
Защитная цепь / модуль Варистор

Выходные данные

Номинальное напряжение на выходе 24 В DC
Диапазон настройки выходного напряжения 22,5 В DC … 29,5 В DC (Работа от сети; буферный режим работы в зависимости от напряжения аккумулятора 27,9 В пост. тока … 19,2 В пост. тока)
Выходной ток 5 А (-25 … 55 °C)
Изменение хар-к 55 °C … 70 °C (2,5 %/K)
Возможность параллельного подключения да, 2
Возможность последовательного подключения Нет
Рассогласование < 1 % (статическое изменение нагрузки 10 % … 90 %)
Остаточная пульсация < 10 мB(ДА)
Коммутационные пики, номинальная нагрузка < 25 мB(ДА)

Общие сведения

Вес нетто 1,1 кг
Носитель информации внешний, аккумулятор 1,3 Aч / 3,4 Aч / 7,2 Aч / 12 Aч
Режим работы
КПД > 88 % (230 В перем. тока, работа от сети)
> 86 % (120 В перем. тока, работа от сети)
> 86 % (Питание от аккумулятора)
Напряжения изоляции на входе / выходе 4 кВ (Типовое исп.)
2 кВ (Частичное испытание)
Степень защиты IP20
MTBF (IEC 61709, SN 29500) > 596285 ч
Монтажное положение горизонтальная DIN-рейка NS 35, EN 60715
Указания по монтажу присоединяемый: горизонтально 0 мм, вертикально 50 мм
Электромагнитная совместимость Соответствует Директиве по ЭМС 2004/108/EG
Излучение помех EN 50081-2
Директива по низкому напряжению Соответствие Директиве по низкому напряжению 2006/95/ЕС
Стандарт — электрическое оснащение машин EN 60204
Стандарт — электробезопасность EN 60950-1/VDE 0805 (БСНН)
Разрешение на применение в судостроении Германский Ллойд (EMC 1)
Стандарт — оснащение силового оборудования электронными средствами EN 50178/VDE 0160 (PELV)
Стандарт — безопасные малые напряжения EN 60950-1 (SELV)
EN 60204 (PELV)
Стандарт — безопасная изоляция DIN VDE 0100-410
DIN VDE 0106-1010
Стандарт — защита от удара электрическим током DIN 57100-410
Стандарт — защита от поражения электрическим током, основные требования к безопасной разводке и изоляции цепей DIN VDE 0106-101
Стандарт — требования к сетям питания (ограничение гармонических искажений) EN 61000-3-2
Сертификация UL UL/C-UL, зарегистрированный UL 508
UL/C-UL, одобренный UL 60950

Характеристики клемм, вход

Тип подключения Винтовые зажимы
Сечение жесткого проводника мин. 0,2 мм2
Сечение жесткого проводника макс. 2,5 мм2
Сечение гибкого проводника мин. 0,2 мм2
Сечение гибкого проводника макс. 2,5 мм2
Сечение провода AWG/kcmil, мин. 24
Сечение провода AWG/kcmil, макс. 12
Резьба винтов M3

Характеристики клемм, выход

Тип подключения Винтовые зажимы
Сечение жесткого проводника мин. 0,2 мм2
Сечение жесткого проводника макс. 2,5 мм2
Сечение гибкого проводника мин. 0,2 мм2
Сечение гибкого проводника макс. 2,5 мм2
Сечение провода AWG/kcmil, мин. 24
Сечение провода AWG/kcmil, макс. 12
Длина снятия изоляции 8 мм

Сигнализация

Выходное напряжение + 24 В
Индикатор состояния LED зел.
Указание по индикации состояния Сетевое напряжение OK: светодиод зеленый, постоянно вкл.
Сечение жесткого проводника мин. 0,2 мм2
Сечение жесткого проводника макс. 2,5 мм2
Сечение гибкого проводника мин. 0,2 мм2
Сечение гибкого проводника макс. 2,5 мм2
Сечение провода AWG/kcmil, мин. 24
Сечение провода AWG/kcmil, макс. 12
Мин. момент затяжки 0,5 Нм
Момент затяжки, макс. 0,6 Нм
Резьба винтов M3
Наименование, выход Аварийный сигнал
Описание выходов Транзисторный коммутационный выход
Максимальное напряжение переключения ? 24 В
Выходное напряжение 24 В
Ток длительной нагрузки ? 200 мА
Индикатор состояния Аварийный сигнал
Указание по индикации состояния Светодиод красный, постоянно вкл.
Наименование, выход Зарядка батареи
Описание выходов Транзисторный коммутационный выход
Максимальное напряжение переключения ? 24 В
Выходное напряжение 24 В
Ток длительной нагрузки ? 200 мА
Индикатор состояния Аккумулятор заряжается (Battery Charge)
Указание по индикации состояния Желтый светодиод мигает
Наименование, выход Режим работы батареи
Описание выходов Транзисторный коммутационный выход
Тип сигнализации Светодиод, активный коммутирующий выход
Максимальное напряжение переключения ? 24 В
Выходное напряжение 24 В
Ток длительной нагрузки ? 200 мА
Индикатор состояния Режим питания от батареи
Указание по индикации состояния Светодиод, желтый, постоянно вкл.

Процесс зарядки

Зарядная характеристика Вольтамперная характеристика
Контроль наличия батареи / временной интервал 60 c
Ток зарядки 0,2 А … 1,5 А (предварительно установлено 1,0 А)
Конечное напряжение заряда 25 В DC … 30 В DC (предварительно установлено 27,6 В пост. тока)

Скачать каталоги Phoenix Contact

Описание Язык
Каталог продукции 1: [PDF, 71,7 MB]
Электротехнические клеммы (2017 / 2018)
русский
Каталог продукции 2: [PDF, 65,8 MB]
Кабели и промышленные соединители для датчиков / исполнительных элементов (2017 / 2018)
русский
Каталог продукции 3: [PDF, 45,9 MB]
маркировка, инструмент и принадлежности для монтажа (2017 / 2018)
русский
Каталог продукции 4: [PDF, 24,8 MB]
Источники питания, устройства защиты от перенапряжений и автоматические защитные выключатели (2017 / 2018)
русский
Каталог продукции 5: [PDF, 40,8 MB]
Интерфейсные технологии и коммутационные устройства (2017 / 2018)
русский
Каталог продукции 6: [PDF, 37,3 MB]
Автоматизация (2017 / 2018)
русский
Каталог продукции 7: [PDF, 14,3 MB]
Клеммы и разъемы для печатных плат (2017 / 2018)
русский

Скачать брошюры Phoenix Contact

Описание Язык
Брошюра «Новинки 2018»
Брошюра «Новинки 2018» на русском языке доступна для скачивания!
В данной брошюре Вы найдете информацию о новом оборудовании Phoenix Contact.
русский
Брошюра «Новинки 2017»
Брошюра «Новинки 2017» на русском языке доступна для скачивания!
В данной брошюре Вы найдете информацию о новом оборудовании Phoenix Contact.
русский
Брошюра «Новинки 2016»
Брошюра «Новинки 2016» на русском языке доступна для скачивания!
В данной брошюре Вы найдете информацию о новом оборудовании Phoenix Contact.
русский

Понравилась статья? Поделить с друзьями:
  • Инструкция по проведению торгов на электронной площадке
  • Самсунг ue32t5300au инструкция по эксплуатации на русском
  • Дормиплант инструкция по применению цена отзывы аналоги кому прописывают
  • Увлажнитель воздуха wellfort мини с подсветкой инструкция по применению
  • Посудомоечная машина сименс iq100 инструкция по применению на русском