Manual No: 577013-756

Revision: J

Veeder-Root TLS2 Console

Gilbarco EMC2 Console

Site Prep Manual

loading

Related Manuals for Veeder-Root TLS2

Summary of Contents for Veeder-Root TLS2

  • Page 1
    Manual No: 577013-756 ● Revision: J Veeder-Root TLS2 Console Gilbarco EMC2 Console Site Prep Manual…
  • Page 2
    Customer Service will work with production facility to have the replacement product shipped as soon as possible. If “lost” equipment is delivered at a later date and is not needed, Veeder-Root will allow a Return to Stock without a restocking fee.
  • Page 3: Table Of Contents

    Table of Contents Introduction Contractor Certification Requirements …………….1 Related Manuals …………………..1 Safety Symbols …………………….2 Control Drawing …………………..3 National Electrical Code Compliance …………….4 Probe-to-Console Wiring ………………4 Power Wiring ………………….4 Probe Junction Boxes………………..4 Probe Wiring Safety Issues ………………..5 Console Installation Selecting a Console Location ……………….6 Accessing the Console’s Mounting Holes …………..6 Console Dimensions ………………….7 Mounting the Console …………………..8…

  • Page 4
    DB-9 Connector Pin-Outs ………………..37 Comm Port 2 Pin-Outs ………………..37 Figures Figure 1. Control Drawing — Example TLS2/EMC2 System Site Layout ….3 Figure 2. Console Dimensions and Designated Wiring Entry Knockouts ….7 Figure 3. Recommended Mounting of Console — International Installations …..8 Figure 4.
  • Page 5: Contractor Certification Requirements

    Setup and Operation manual. Contractor Certification Requirements Veeder-Root requires the following minimum training certifications for contractors who will install and setup the equipment discussed in this manual: Installer (Level 1) Certification: Contractors holding valid Installer Certification are approved to perform wiring and conduit routing;…

  • Page 6: Safety Symbols

    Introduction Safety Symbols Safety Symbols The following safety symbols are used in this manual to alert you to important safety hazards and precautions. EXPLOSIVE FLAMMABLE Fuels and their vapors are extremely Fuels and their vapors are extremely explosive if ignited. flammable.

  • Page 7: Control Drawing

    Circuitry within the console barrier forms an intrinsically safe, energy-limited system. This system makes console probes safe for use in a Class I, Group D hazardous locations. Console probe wiring is intrinsically safe only when connected to Veeder-Root/Gilbarco Consoles. Reference Console Form Number 8560 and Probe Form Numbers 8462, 8463, 8468, and 8473.

  • Page 8: National Electrical Code Compliance

    1000 feet (304 m). Wire runs must be less than 1000 feet to meet intrinsic safety requirements. Splices Veeder-Root recommends that no splices be made in the wire run between a probe junction box and the console. Each splice degrades signal strength and could result in poor system performance. Wire Gauges — Color coded Shielded cable must be used in all installations.

  • Page 9: Probe Wiring Safety Issues

    If the TLS2/EMC2 System is being retrofitted into a paved site, you run direct burial cable to the probes, and then seal over the cable grooves. Before trenching, you should diagram all conduit runs between the console’s intended location and its deployed probes.

  • Page 10: Console Installation

    Console Installation Selecting a Console Location WARNING Explosive vapors or flammable liquids could be present near locations where fuels are stored or being dispensed. The console is not explosion proof. An explosion or fire resulting in serious injury or death, property loss and equipment damage could occur if the console is installed in a volatile, combustible or explosive atmosphere (Class I, Division 1 or 2).

  • Page 11: Console Dimensions

    (51 mm) 0.93» 0.93» 1.25» (24 mm) (24 mm) (32 mm) 0.4» tls2dimen.eps (10 mm) 3.75″ 1.18» (95mm) (30 mm) Legend for numbered boxes Console mounting holes — 4 places. 1/2-inch I.P.S. & 0.56 inch (22 and 14 mm) — Power wiring only conduit knockouts (4 places).

  • Page 12: Mounting The Console

    Mounting the Console Install 1/2-inch I.P.S. (14 mm) metal conduit between the console and the power panel as shown in Figure 3 for international installations or Figure 4 for U.S. installations. consolestls2mnt.eps Legend for numbered boxes 2A neon spur To an external alarm (i.e., forecourt alarm) 1000 mm, maximum Communication cable.

  • Page 13: Figure 4. Recommended Mounting Of Console — Alternate Installations

    Console Installation Mounting the Console consolestls2mntUS.eps Legend for numbered boxes To an optional overfill alarm Communication cable. A dedicated circuit breaker rated for 15 amperes, 120 Vac or 240 Vac. NOTE, circuit breaker must be marked as the power disconnect for the console. Run three 14 AWG standard color coded wires; live, neutral, and earth, to the console. Run one 12 AWG wire, color coded green, from the earth bus bar at the distribution panel direct to the console location.

  • Page 14: Wiring The Console

    Console Installation Wiring the Console Wiring the Console WARNING The console contains voltages which can be lethal. It is connected to devices that must be intrinsically safe. Connecting power wires to a live circuit can cause electrical shock that may result in serious injury or death.

  • Page 15: Figure 5. Wiring Ac Power To The Console

    C24/C27 or the metal bands on chokes L2/L4. consoles/tls2/pcon.eps Legend for numbered boxes Attach neutral wire (N) to top terminal (J5). Attach hot wire (L) to bottom terminal (J5). Attach chassis ground wire to ground lug.

  • Page 16: Cpu Board Component Locations

    Figure 6 shows important component locations on the CPU board. 2 3 4 OPEN LED2 CONTRAST PGM1 consoles/tls2/display.eps 11 12 Legend for numbered boxes Console features ibutton (under display) Door (reference) Liquid crystal touch screen display Filtered probe data indicator…

  • Page 17: Determining Mag Probe Length

    2. Measure the distance from the bottom of the probe riser pipe to the top of the probe riser pipe (B). 3. Subtract (B) from (A) to determine the correct tank diameter (C). Round tank diameter (C) up to next highest inch and order this length probe. consoles/tls2/figure6.eps Legend for numbered boxes Tank 24”…

  • Page 18: Special Mag Probe Installation Kits

    3/8” Adaptor nut 329972-002 3/8” Straight liquidtite connectors and related parts 576008-295 Cord Grip Group 331028-001 tls2/astkit.eps Legend for numbered boxes Cord grip Flexible conduit 5 ft (1.5 m) Liquidtight connector assembly (at riser cap) Liquidtight connector assembly (at J-box)

  • Page 19: Riser Cap Kit For Mag Probe Installations

    Part Number Plastic Riser Cap 331106-001 Gasket 331140-001 Bushing — Cord Grip 330787-001 Nut — Cord Grip 330594-001 tls2risercap.eps Legend for numbered boxes Cord grip nut Cord grip bushing Riser cap and gasket Figure 9. Cap and Cord Grip Kit…

  • Page 20: Metal Cap And Ring Kit

    Special Mag Probe Installation Kits Riser Cap Kit for Mag Probe Installations METAL CAP AND RING KIT This riser cap kit contains a metal ring which screws onto the 4-inch NPT riser and a quick-release metal cap which clamps onto the ring (Table 3). The cap comes drilled and tapped with a cord grip (Figure 10). Table 3.

  • Page 21: Modifying An Existing Metal Cap

    Special Mag Probe Installation Kits Riser Cap Kit for Mag Probe Installations MODIFYING AN EXISTING METAL CAP In order to ensure that the riser cap seals properly to the probe cable and riser, we recommend that you purchase one of the kits available for this purpose. Riser Caps from other manufacturers may require modification. If you use your own metal riser cap, you must drill and tap it for a cord grip fitting (V-R P/N 331028-001) as follows: 1.

  • Page 22: Mag Probe Assembly

    Mag Probe Assembly The following assembly instructions are for Global Mag Plus and Mag Plus probes. For other probe types follow assembly instructions included with probe. Attaching Probe Canister Spacer Rings Open the probe shipping carton so that you have access to the probe. Also open the installation kit. For 3- and 4-inch risers After adjusting the spacers for a 3- or 4-inch riser, install the two spacer rings as shown in Figure 12.

  • Page 23: Figure 12. Installing Probe Canister Spacer Rings For 3- & 4-Inch Risers

    Mag Probe Assembly Attaching Cable Connector to Probe Canister tls2/figure12.eps Legend for numbered boxes After setting arms (see insert) install top spacer ring. Orient locking tabs as shown, and then slide ring over top of canister until tabs snap into groove in canister.

  • Page 24: Figure 13. Installing Insulating Sleeves For 2-Inch Risers

    Mag Probe Assembly Attaching Cable Connector to Probe Canister probessleeveinst2.eps Legend for numbered boxes Canister connector up Sleeve tabs up (snap into canister groove) Canister insulator sleeves (2). Probe shaft Sleeve tabs down (snap into canister groove) Probe canister Figure 13. Installing Insulating Sleeves for 2-inch Risers…

  • Page 25: Figure 14. Probe Float/Boot Installation

    Mag Probe Assembly Attaching Cable Connector to Probe Canister tls2/figure13.eps Legend for numbered boxes Bottom of probe shaft 4-Inch Float set Product float — slide on probe shaft first Optional Water float OR (6) Water/Density float — slide on probe shaft second.

  • Page 26: Mag Probe Installation

    At sites that require installation of a riser adaptor (Phil-Tite M/F 4X4 or equivalent) at the top of the riser, do so following the manufacturer’s instructions. Next screw the adapter ring from the Veeder-Root kit (P/N 312020- 952) onto the riser adaptor by hand until the gasket contacts the sealing surface. Then use a torque wrench attached to an appropriate strap wrench (K-D Specialty tools nylon strap oil filter wrench, or equivalent) and tighten the ring to 35 — 45 ft-lbs.

  • Page 27: Figure 15. Probe Installation Example — Underground Storage Tank

    Mag Probe Installation UST/AST Tank — Dedicated Riser Adaptor Nut on one end and the J-box on the other. Tighten the fittings until snug. Splice and seal the wires in the J-box (see Probe Field Wiring on page 28). probespinst.eps Legend for numbered boxes Riser cap and cord grip 14-inch diameter or larger manhole…

  • Page 28: Figure 16. U.s. Probe Installation Example — Above Ground Storage Tank

    Mag Probe Installation UST/AST Tank — Dedicated Riser probesapins.eps Legend for numbered boxes Riser cap and cord grip Use bushing and body of grip fitting supplied with probe and adaptor nut supplied with AST kit (V-R P/N 312020-984 Liquidtight fittings from AST kit Flexible metal conduit supplied with AST kit Weatherproof junction box with 1/2”…

  • Page 29: Probe Conduit Installation

    Mag Probe Installation Probe Conduit Installation probesriserdapttls2.eps Legend for numbered boxes Metal cap from kit Adaptor ring from kit Riser adaptor (Phil-Tite M/F4X4, or equivalent) Tank Figure 17. Installing the Riser Adaptor Probe Conduit Installation WARNING Probes operate in areas where flammable liquids and explosive vapors may be present.

  • Page 30: Rigid Conduit

    Also, if the intrinsically safe wires enter the building in a wiring trough, only intrinsically safe wires (from TLS2 probes) can be in the trough. Keep all low power (intrinsically safe) wiring physically isolated from high power wires in all wiring troughs per the NEC.

  • Page 31: Direct Burial

    Prior to installing direct burial cable with epoxy splices, consult with the local authority having jurisdiction. Use of direct burial cable is only allowed in locations where local codes permit the use of buried cable. If you decide to use the direct burial method, you should order the Veeder-Root Direct Burial Cable Preparation Kit, P/N 848100-500.

  • Page 32: Probe Field Wiring

    Mag Probe Installation Probe Field Wiring Probe Field Wiring Figure 20 diagrams a typical probe field wiring connection in the junction box. consoles/tls2/pw.eps Legend for numbered boxes To console Seal off Do not ground drain wire in junction box Black wire (-) from probe…

  • Page 33: Direct Burial Cable

    Contains: epoxy resin and Cycloaliphatic epoxycarboxylate. Precautions: Wear suitable protective clothing, gloves, eye, and face protection. Use only in well ventilated areas. Wash thoroughly before eating, drinking, or smoking. consoles/tls2/epxy.eps Legend for numbered boxes NOTE: When temperature is below 50°F (10°C), keep resin in a warm place prior to mixing (e.g., in an inside pocket next to body).Remove guard bag, using caution not to damage inner bag.

  • Page 34: Connecting Probes To The Console

    Mag Probe Installation Connecting Probes to the Console Connecting Probes to the Console WARNING The equipment is used in location where lethal voltages and explosive vapors or flammable fuels may be present. Care must be taken when installing, servicing or replacing parts in the system or serious injury or death from explosion, fire or shock may occur.

  • Page 35: Figure 22. Connecting Probe Wiring To Console

    PROBE 1 AVERTISSEMENT LA SUBSTITUTION DE COMPOSANTS PEUT COMPROMETTRE LA SECURITE INTRINSEQUE. consoles/tls2/pbwr.eps Legend for numbered boxes Circuit Directory label Black wire from probe 1 connects to (-) terminal White wire from probe 1 connects to (+) terminal Attach probe 1 cable shield and /or drain wire to ground lug Intrinsically safe wiring cover (shown swung open to left) Figure 22.

  • Page 36: Overfill Alarm Relay

    C24/C27 or the metal bands on chokes L2/L4. consoles/tls2/rcon.eps Legend for numbered boxes Connect one wire from relay to top terminal of J6 (no polarity) Connect second wire from relay to lower terminal of J6 (no polarity)

  • Page 37: Applying Power To System

    Pins (jumper on pins 2&3) (jumper on pins 1&2) consoles/tls2/ram.eps Figure 24. RAM Clear Jumper Positions 2. Move the jumper down to the RAM Clear position (pins 1&2). Turn the power to the console ‘On’ and wait until the console completely boots up.

  • Page 38: Warm Boot

    Applying Power to System Warm Boot NO TANKS CONFIGURED Figure 25. Cold boot ‘No Tanks Configured’ message Warm Boot After the system has been setup, and power to the console is switched ‘Off’ and ‘On’ , the software will run a self- diagnostic warm boot program and display the test results: Test Passed Message Test Failed Message…

  • Page 39: Communications

    TO A DEVICE LESS THAN 50 FEET (15 METRES) FROM THE CONSOLE Veeder-Root recommends that you use a null-modem cable no longer than 50 feet for direct connections between the console and a remote device. Cable runs longer than 50 feet can result in data errors, component damage, or both.

  • Page 40: Figure 26. Example Of Console Connected To A Remote Device Via Mde800A Short-Haul Modems

    Communications Surge Protection for Communication Devices 12 11 10 9 19 18 17 16 consolestls2shm.eps Legend for numbered boxes DB9 connector or (2) DB25 connector — depends on availability Personal Computer Twisted pair 24 or 26 AWG (0.2 mm ) cable…

  • Page 41: Db-9 Connector Pin-Outs

    Pin layout to connect the console’s Serial Interface DB-9 connector to a 25-pin computer terminal connector are shown in Table 1 below. These connections are standard for “AT” style modem cables. Table 4. TLS2/EMC2 DB-9 Pin-Outs Console (DB-9) Computer (DB-25)

  • Page 42
    For technical support, sales or other assistance, please visit: www.veeder.com…

  • Contents

  • Table of Contents

  • Bookmarks

Quick Links

VEEDER — ROOT

SERIAL INTERFACE MANUAL

for

TLS2

UST Monitoring Systems

through Software Version 7

Manual Number 577013-767

Revision H

loading

Related Manuals for Veeder-Root TLS2

Summary of Contents for Veeder-Root TLS2

  • Page 1
    VEEDER — ROOT SERIAL INTERFACE MANUAL TLS2 UST Monitoring Systems through Software Version 7 Manual Number 577013-767 Revision H…
  • Page 2
    NOTICE Veeder-Root makes no warranty of any kind with regard to this publication, including but not limited to, the implied warranties of merchantability and fitness for a particular purpose. Veeder-Root shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance, or use of this publication.
  • Page 3: Table Of Contents

    Serial Interface Manual • TLS2 Monitoring Systems TABLE OF CONTENTS INTRODUCTION ……………………..1 HARDWARE CONNECTIONS ………………….1 RS-232 ……………………… 1 EIA RS-232 INTERFACE ………………..2 CHARACTER FORMAT AND BAUD RATE ………………. 2 SECURITY CODE SETTINGS ………………….2 COMMAND MESSAGE FORMAT ………………..3 RESPONSE MESSAGE FORMAT …………………

  • Page 4: Introduction

    Serial Interface Manual • TLS2 Monitoring Systems INTRODUCTION The serial RS-232 interface is used to connect the system to a controlling computer, a display terminal (CRT), or a printing terminal. A modem can be connected directly to the system to provide telephone line access.

  • Page 5: Eia Rs-232 Interface

    Serial Interface Manual • TLS2 Monitoring Systems EIA RS-232 INTERFACE The EIA RS-232 interface is designed to connect to modems for transmission of data over telephone lines. It can be used for direct local attachment of terminals if the cable run is no more than 50 feet. In practice, cable runs longer than 50 feet have performed satisfactorily;…

  • Page 6: Command Message Format

    Serial Interface Manual • TLS2 Monitoring Systems COMMAND MESSAGE FORMAT All command and response messages are configured in a format which includes a surrounding envelope of control characters and a function code and data field message. The control characters are described in this section, while the function codes and data field messages are described in subsequent sections.

  • Page 7: Response Message Format

    Serial Interface Manual • TLS2 Monitoring Systems RESPONSE MESSAGE FORMAT There are two types of response message formats: computer (or packed data format) and display format. Each format uses a different surrounding envelope of control characters. COMPUTER FORMAT The computer format is a stream of data without any formatting characters; i.e., carriage return, line feed, spaces, labels, etc.

  • Page 8: Ascii Floating Point Format

    Serial Interface Manual • TLS2 Monitoring Systems ASCII FLOATING POINT FORMAT 6.3.1 NOTES 6.3.1.1 HHHHHHHH (H = 0-9 or A-F) indicates the 8 «nibble» ASCII-Hexadecimal representation of a 4-Byte Floating Point number. Many data parameters are transmitted in this format.

  • Page 9: Examples

    Serial Interface Manual • TLS2 Monitoring Systems 6.3.2 EXAMPLES 6.3.2.1 3F800000 hex = 0011 1111 1000 0000 0000 0000 0000 0000 bin S = 0 = + (positive) E = 011 1111 1 bin = 7F hex = 127 dec…

  • Page 10: Function Codes And Response Messages

    Serial Interface Manual • TLS2 Monitoring Systems FUNCTION CODES AND RESPONSE MESSAGES The function codes and data fields of the message formats are described in this section. Most response messages can be requested for either a single device (tank, etc.) or all devices. A «TT» in the function code signifies single device number 01 through 16.

  • Page 11: Control Functions

    Serial Interface Manual • TLS2 Monitoring Systems CONTROL FUNCTIONS Function Code: Version 1 Function Type: System Reset Command Format: Display: <SOH>S00100 Computer: <SOH>s00100 Typical Response Message, Display Format: <SOH> S00100 22-05-01 14:51 <ETX> Typical Response Message, Computer Format: <SOH>s00100YYMMDDHHmm&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time &&…

  • Page 12
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Remote Alarm Reset Command Format: Display: <SOH>S00300 Computer: <SOH>s00300 Typical Response Message, Display Format: <SOH> S00300 22-05-01 14:54 <ETX> Typical Response Message, Computer Format: <SOH>s00300YYMMDDHHmm&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time &&…
  • Page 13
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Computer Mode Autodial Hang-up Command Format: Display: <SOH>S01000 Computer: <SOH>s01000 Typical Response Message, Display Format: <SOH> S01000 22-05-01 14:54 <ETX> Typical Response Message, Computer Format: <SOH>s01000YYMMDDHHmm&&CCCC<ETX> Notes:…
  • Page 14
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Start In-Tank Leak Detect Test Command Format: Display: <SOH>S052TT Computer: <SOH>s052TT Typical Response Message, Display Format: <SOH> S05201 22-05-01 14:55 TANK PRODUCT LABEL REGULAR UNLEADED LEAK TEST START TEST BY EXTERN INTERFACE <ETX>…
  • Page 15
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Stop In-Tank Leak Detect Test Command Format: Display: <SOH>S053TT Computer: <SOH>s053TT Typical Response Message, Display Format: <SOH> S05301 22-05-01 14:55 TANK PRODUCT LABEL REGULAR UNLEADED LEAK TEST STOP <ETX>…
  • Page 16
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Setup Password Log In Command Format: Display: <SOH>S09E00PPPPPPPPPPPPPPPP Computer: <SOH>s09E00PPPPPPPPPPPPPPPP Notes: P — Setup Password (6 to 16 ASCII characters [20h-7Eh]) Typical Response Message, Display Format: <SOH>…
  • Page 17
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Setup Password Log Out Command Format: Display: <SOH>S09F00149 Computer: <SOH>s09F00149 Notes: 149 — code must be sent to confirm the command Typical Response Message, Display Format: <SOH>…
  • Page 18: Operational Reports

    Serial Interface Manual • TLS2 Monitoring Systems OPERATIONAL REPORTS 7.2.1 SYSTEM REPORTS Function Code: Version 1 Function Type: System Status Report Command Format: Display: <SOH>I10100 Computer: <SOH>i10100 Notes: This command will report all active OR unacknowledged alarms and warnings up to the limit of 25 alarms in display format,…

  • Page 19
    Serial Interface Manual • TLS2 Monitoring Systems Function Code 101 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i10100YYMMDDHHmmAANNTT… AANNTT&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time AA — Alarm/Warning Category: 00 — All Functions Normal 02 — Tank Alarm 14 — Auto-Dial Fax Alarm…
  • Page 20
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: System Identification Report Command Format: Display: <SOH>I10300 Computer: <SOH>i10300 Typical Response Message, Display Format: <SOH> I10300 22-05-08 14:58 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 21
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Priority Alarm History Report Command Format: Display: <SOH>I11100 Computer: <SOH>i11100 Typical Response Message, Display Format: <SOH> I11100 22-05-01 14:55 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 22
    Serial Interface Manual • TLS2 Monitoring Systems Function Code 111 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i11100YYMMDDHHmmAAccNNTTSSYYMMDDHHmm… AAccNNTTSSYYMMDDHHmm&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time AA — Alarm/Warning Category: 00 — All Functions Normal 02 — Tank Alarm 14 — Auto-Dial Alarm…
  • Page 23
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Non-Priority Alarm History Report Command Format: Display: <SOH>I11200 Computer: <SOH>i11200 Typical Response Message, Display Format: <SOH> I11200 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 24
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Active Alarm Report Command Format: Display: <SOH>I11300 Computer: <SOH>i11300 Notes: This command will report ALL active alarms and warnings regardless of their acknowledgement state. If there are…
  • Page 25
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Cleared Alarm Report Command Format: Display: <SOH>I11400 Computer: <SOH>i11400 Typical Response Message, Display Format: <SOH> I11400 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 26
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Priority Alarm History Report II Command Format: Display: <SOH>I11700 Computer: <SOH>i11700 Typical Response Message, Display Format: <SOH> I11700 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 27
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Non-Priority Alarm History Report II Command Format: Display: <SOH>I11800 Computer: <SOH>i11800 Typical Response Message, Display Format: <SOH> I11800 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 28: In-Tank Reports

    Serial Interface Manual • TLS2 Monitoring Systems 7.2.2 IN-TANK REPORTS Function Code: Version 1 Function Type: In-Tank Inventory Report Command Format: Display: <SOH>I201TT Computer: <SOH>i201TT Typical Response Message, Display Format: <SOH> I20101 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..

  • Page 29
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Delivery Report Command Format: Display: <SOH>I202TT Computer: <SOH>i202TT Typical Response Message, Display Format: <SOH> I20201 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 30
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Detect Report Command Format: Display: <SOH>I203TT Computer: <SOH>i203TT Typical Response Message, Display Format: <SOH> I20301 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 31
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Shift Inventory Report Command Format: Display: <SOH>I204TT Computer: <SOH>i204TT Typical Response Message, Display Format: <SOH> I20401 22-05-01 14:56 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 32
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Status Report Command Format: Display: <SOH>I205TT Computer: <SOH>i205TT Typical Response Message, Display Format: <SOH> I20501 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 33
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Alarm History Report Command Format: Display: <SOH>I206TT Computer: <SOH>i206TT Typical Response Message, Display Format: <SOH> I20601 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 34
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Test History Report Command Format: Display: <SOH>I207TT Computer: <SOH>i207TT Typical Response Message, Display Format: <SOH> I20701 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 35
    Serial Interface Manual • TLS2 Monitoring Systems Function Code 207 Notes: (Continued) Typical Response Message, Computer Format: <SOH>i207TTYYMMDDHHmmTTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp… TTNNRRnnttYYMMDDHHmmhhhhhhhhVVVVVVVVpppppppp…&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time TT — Tank Number (Decimal, 00 = all) NN — Number of Leak History Reports to Follow (Hex)
  • Page 36
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Leak Test Results Report Command Format: Display: <SOH>I208TT Computer: <SOH>i208TT Typical Response Message, Display Format: <SOH> I20801 22-05-01 14:57 PREVIOUS IN TANK LEAK TEST RESULTS TANK 1…
  • Page 37
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Enhanced Leak Detect Report Command Format: Display: <SOH>I209TT Computer: <SOH>i209TT Typical Response Message, Display Format: <SOH> I20901 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 38
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Most Recent Delivery Report Command Format: Display: <SOH>I20CTT Computer: <SOH>i20CTT Typical Response Message, Display Format: <SOH> I20C01 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 39
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: In-Tank Stick Height Report Command Format: Display: <SOH>I20DTT Computer: <SOH>i20DTT Notes: This command will respond only if stick height is enabled. Tank stick height is fuel height (without tilt) + stick offset.
  • Page 40
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Mass/Density Inventory Report Command Format: Display: <SOH>I214TT Computer: <SOH>i214TT Typical Response Message, Display Format: <SOH> I214TT 04-30-09 2:18 PM STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 41
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Mass/Density Delivery Report Command Format: Display: <SOH>I215TT Computer: <SOH>i215TT Typical Response Message, Display Format: <SOH> I215TT 04-30-09 2:46 PM T 1:PRODUCT 1 INCREASE DATE / TIME…
  • Page 42
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Power Outage Delivery Report Command Format: Display: <SOH>I21CTT Computer: <SOH>i21CTT Typical Response Message, Display Format: <SOH> I21CTT 29-07-08 14:58 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 43
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Inventory Snapshot Volume Command Format: Display: <SOH>I21ETTyymmddhhmm Computer: <SOH>i21ETTyymmddhhmm Notes: yymmddhhmm — Request for Inventory records starting with this date to the most recent. If no yymmddhhmm, return the most recent…
  • Page 44
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Manual Shift Inventory Snapshot Report Command Format: Display: <SOH>I21Fssdd Computer: <SOH>i21Fssdd Notes: ss — number 00=all, 01, 02, 03, 04 shift number (Decimal) dd — number Day of Shift…
  • Page 45
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Full Inventory Report Command Format: Display: <SOH>I231TT Computer: <SOH>I231TT Typical Response Message, Display Format: <SOH> I23100 16-06-11 07:35 STATION HEADER 1..STATION HEADER 2..STATION HEADER 3..
  • Page 46
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 6 Function Type: Density Offset History Report Command Format: Display: <SOH>I233TT Computer: <SOH>I233TT Typical Response Message, Display Format: <SOH> I23300 16-06-11 07:35 DENSITY OFFSET HISTORY REPORT T 1:REGULAR UNLEADED DATE / TIME…
  • Page 47
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Mass/Density Inventory Report 2 Command Format: Display: <SOH>I234TT Computer: <SOH>I234TT Typical Response Message, Display Format: <SOH> I234TT 04-30-09 2:18 PM STATION HEADER 1..STATION HEADER 2..
  • Page 48
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: In-Tank Mass/Density Delivery Report 2 Command Format: Display: <SOH>I235TT Computer: <SOH>I235TT Typical Response Message, Display Format: <SOH> I235TT 04-30-09 2:46 PM T 1:PRODUCT 1 INCREASE DATE / TIME…
  • Page 49: I/O Device Reports

    Serial Interface Manual • TLS2 Monitoring Systems 7.2.3 I/O DEVICE REPORTS Function Code: Version 1 Function Type: Relay Status Report Command Format: Display: <SOH>I406RR Computer: <SOH>i406RR Typical Response Message, Display Format: <SOH> I40600 22-05-01 14:57 STATION HEADER 1..STATION HEADER 2..

  • Page 50: Setup Functions & Reports

    Serial Interface Manual • TLS2 Monitoring Systems SETUP FUNCTIONS & REPORTS 7.3.1 SYSTEM SETUP Function Code: Version 1 Function Type: Set Time of day Command Format: Inquire: Display: <SOH>S50100YYMMDDHHmm <SOH>I50100 Computer: <SOH>s50100YYMMDDHHmm <SOH>i50100 Typical Response Message, Display Format: <SOH> I50100…

  • Page 51
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Shift Start Time 1, 2, 3, 4 Command Format: Inquire: Display: <SOH>S502SSHHmm <SOH>I502SS Computer: <SOH>s502SSHHmm <SOH>i502SS Notes: SS — Shift Start time (01, 02, 03, 04) Typical Response Message, Display Format: <SOH>…
  • Page 52
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Print Header Line 1, 2, 3, 4 Command Format: Inquire: Display: <SOH>S503LLaaaaaaaaaaaaaaaaaaaa <SOH>I503LL Computer: <SOH>s503LLaaaaaaaaaaaaaaaaaaaa <SOH>i503LL Typical Response Message, Display Format: <SOH> I50301 22-05-01 14:58 1:STATION HEADER 1..
  • Page 53
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set System RS-232 Security Code Command Format: Inquire: Display: <SOH>S50400aaaaaa <SOH>I50400 Computer: <SOH>s50400aaaaaa <SOH>i50400 Typical Response Message, Display Format: <SOH> I50400 22-05-01 14:58 232 SECURITY CODE PORT…
  • Page 54
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Printer Page Eject Flag Command Format: Inquire: Display: <SOH>S50C00f <SOH>I50C00 Computer: <SOH>s50C00f <SOH>i50C00 Typical Response Message, Display Format: <SOH> I50C00 22-05-01 14:58 PAGE EJECT : NO <ETX>…
  • Page 55
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Print Temperature Compensation Flag Command Format: Inquire: Display: <SOH>S50D00f <SOH>I50D00 Computer: <SOH>s50D00f <SOH>i50D00 Typical Response Message, Display Format: <SOH> I50D00 22-05-01 14:59 PRINT TC VOLUMES DISABLED <ETX>…
  • Page 56
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Temperature Compensation Value Command Format: Inquire: Display: <SOH>S50E00DDD.hh <SOH>I50E00 Computer: <SOH>s50E00FFFFFFFF <SOH>i50E00 Notes: DDD.hh — Compensation Temperature, Degrees and hundredths (Decimal) FFFFFFFF — Compensation Temperature, Degrees (ASCII Hex IEEE float) Typical Response Message, Display Format: <SOH>…
  • Page 57
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set System Date/Time Display Format Command Format: Inquire: Display: <SOH>S50F00xx <SOH>I50F00 Computer: <SOH>s50F00xx <SOH>i50F00 Typical Response Message, Display Format: <SOH> I50F00 22-05-01 14:59 DD-MM-YY HH:MM:SS <ETX> Typical Response Message, Computer Format: <SOH>i50F00YYMMDDHHMMxx&&CCCC<ETX>…
  • Page 58
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set H-Protocol Height/Volume format Command Format: Inquire: Display: <SOH>S51400f <SOH>I51400 Computer: <SOH>s51400f <SOH>i51400 Typical Response Message, Display Format: <SOH> I51400 22-05-01 14:59 H-PROTOCOL DATA FORMAT HEIGHT <ETX>…
  • Page 59
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set System Type & Language Flags Command Format: Inquire: Display: <SOH>S51700ULL <SOH>I51700 Computer: <SOH>s51700ULL <SOH>i51700 Typical Response Message, Display Format: <SOH> I51700 22-05-01 14:59 SYSTEM TYPE AND LANGUAGE FLAG…
  • Page 60
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Auto Daylight Saving Time Command Format: Inquire: Display: <SOH>S51A00f <SOH>I51A00 Computer: <SOH>s51A00f <SOH>i51A00 Typical Response Message, Display Format: <SOH> I51A00 22-05-01 14:59 DAYLIGHT SAVING TIME DISABLED <ETX>…
  • Page 61
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Start/End Daylight Saving Date and Time Command Format: Inquire: Display: <SOH>S51BttMMWDHHmm <SOH>I51Btt Computer: <SOH>s51BttMMWDHHmm <SOH>i51Btt Notes: YYMMDDHHmm — Current Date and Time tt — Start or End Time Indicator 01=Start Date &…
  • Page 62
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Euro Protocol Prefix Command Format: Inquire: Display: <SOH>S51F00e <SOH>I51F00 Computer: <SOH>s51F00e <SOH>i51F00 Typical Response Message, Display Format: <SOH> I51F00 22-05-01 15:02 EURO PROTOCOL PREFIX <ETX> Typical Response Message, Computer Format: <SOH>i51F00YYMMDDHHmme&&CCCC<ETX>…
  • Page 63: Communications Setup

    Serial Interface Manual • TLS2 Monitoring Systems 7.3.2 COMMUNICATIONS SETUP Function Code: Version 1 Function Type: Set Receiver Telephone Number Command Format: Inquire: Display: <SOH>S523RRaaaaaaaaaaaaaaaaaaaa <SOH>I523RR Computer: <SOH>s523RRaaaaaaaaaaaaaaaaaaaa <SOH>i523RR Typical Response Message, Display Format: <SOH> I52301 22-05-01 15:02 RECEIVER PHONE NUMBER…

  • Page 64
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Receiver Retry Number Command Format: Inquire: Display: <SOH>S526RRnn <SOH>I526RR Computer: <SOH>s526RRnn <SOH>i526RR Typical Response Message, Display Format: <SOH> I52601 22-05-01 15:02 RETRY NUMBER RCVR RETRY NUMBER <ETX>…
  • Page 65
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Receiver Retry Delay Time Command Format: Inquire: Display: <SOH>S527RRnn <SOH>I527RR Computer: <SOH>s527RRnn <SOH>i527RR Typical Response Message, Display Format: <SOH> I52701 22-05-01 15:03 RETRY DELAY TIME RCVR RETRY DELAY <ETX>…
  • Page 66
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Receiver Auto Dial On Alarms Command Format: Inquire: Display: <SOH>S52CRRAANNTTSS <SOH>I52CRR Computer: <SOH>s52CRRAANNTTSS <SOH>i52CRR Typical Response Message, Display Format: <SOH> I52C01 22-05-01 15:06 RECEIVER SETUP REPORT…
  • Page 67
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Hangup Method Command Format: Inquire: Display: <SOH>S53500MM <SOH>I535MM Computer: <SOH>s53500MM <SOH>i535MM Typical Response Message, Display Format: <SOH> I53501 22-05-01 15:06 AUTO COMPUTER MODE HANGUP RCVR…
  • Page 68
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set RS-232 Security Code per Port Command Format: Inquire: Display: <SOH>S536PPsaaaaaa <SOH>I536PP Computer: <SOH>s536PPsaaaaaa <SOH>i536PP Notes: PP — Port number (Decimal, 01-02; 99=this port) s — Enable or Disable Status (if disabled no password is…
  • Page 69
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Receiver Auto Dial On Events Command Format: Inquire: Display: <SOH>S539RRAANNTTSS <SOH>I539RR Computer: <SOH>s539RRAANNTTSS <SOH>i539RR Typical Response Message, Display Format: <SOH> I53901 22-05-01 15:06 RECEIVER EVENTS SETUP REPORT…
  • Page 70
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set TC Density Enable Command Format: Inquire: Display: <SOH>S54500f <SOH>I54500 Computer: <SOH>s54500f <SOH>i54500 Typical Response Message, Display Format: <SOH> I54500 04-30-09 9:11 AM TC DENSITY ENABLED <ETX>…
  • Page 71
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set IS03166 3 Character Country Code Command Format: Inquire: Display: <SOH>S54D00aaa <SOH>I54D00 Computer: <SOH>s54D00aaa <SOH>i54D00 Typical Response Message, Display Format: <SOH> I54D00 APR 10, 2007 10:15 AM ISO3166 COUNTRY CODE: ESP <ETX>…
  • Page 72: I/O Device Setup

    Serial Interface Manual • TLS2 Monitoring Systems 7.3.3 I/O DEVICE SETUP Function Code: Version 1 Function Type: Set Relay Alarm Assignment Command Format: Inquire: Display: <SOH>S55C00M <SOH>I55C00 Computer: <SOH>s55C00M <SOH>i55C00 Typical Response Message, Display Format: <SOH> I55C01 22-05-01 15:06 ALARM RELAY : NONE <ETX>…

  • Page 73
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Autodial Confirmation Flag Command Format: Inquire: Display: <SOH>S56BRRf <SOH>I56BRR Computer: <SOH>s56BRRf <SOH>i56BRR Typical Response Message, Display Format: <SOH> I56B01 22-05-01 15:03 AUTODIAL CONFIRMATION RCVR AUTODIAL CONFIRMATION DISABLED <ETX>…
  • Page 74
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Shift Close Method Command Format: Inquire: Display: <SOH>S56D00M <SOH>I56D00 Computer: <SOH>s56D00M <SOH>i56D00 Typical Response Message, Display Format: <SOH> I56D00 22-05-08 15:02 SHIFT CLOSE METHOD : SNAPSHOT <ETX>…
  • Page 75
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Manual Close Timeout Command Format: Inquire: Display: <SOH>S56E00NN <SOH>I56E00 Computer: <SOH>s56E00NN <SOH>i56E00 Typical Response Message, Display Format: <SOH> I56E00 22-05-08 15:02 MANUAL CLOSE TIMEOUT <ETX> Typical Response Message, Computer Format: <SOH>i56D00YYMMDDHHmmNN&&CCCC<ETX>…
  • Page 76
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Dial Type Command Format: Inquire: Display: <SOH>S571RRTT <SOH>I571RR Computer: <SOH>s571RRTT <SOH>i571RR Typical Response Message, Display Format: <SOH> I57100 JAN 31, 2008 9:02 AM DIAL TYPE RCVR…
  • Page 77
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Push Site ID Enable Command Format: Inquire: Display: <SOH>S574RRF <SOH>I574RR Computer: <SOH>s574RRF <SOH>i574RR Typical Response Message, Display Format: <SOH> I57400 JUL 8, 2009 9:02 AM PUSH SITE ID ENABLE…
  • Page 78
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Dial Type Command Format: Inquire: Display: <SOH>S571RRDDDDDD <SOH>I571RR Computer: <SOH>s571RRHHHHHHHH <SOH>i571RR Notes: DDDDDD — Site ID (Decimal) Typical Response Message, Display Format: <SOH> I57500 8, 2009…
  • Page 79
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Inventory Start Time Command Format: Inquire: Display: <SOH>S57700hhmm <SOH>I57700 Computer: <SOH>s57700hhmm <SOH>i57700 Typical Response Message, Display Format: <SOH> I577D00 22-05-08 15:02 INVENTORY LOG TIME : 12:00 <ETX>…
  • Page 80
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Inventory Repeat Interval Command Format: Inquire: Display: <SOH>S57800rr <SOH>I57800 Computer: <SOH>s57800rr <SOH>i57800 Typical Response Message, Display Format: <SOH> I57800 22-05-08 15:02 INVENTORY LOG INTERVAL : 1 Hour <ETX>…
  • Page 81
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Idle Delivery Enabled Command Format: Inquire: Display: <SOH>S57900f <SOH>I57900 Computer: <SOH>s57900f <SOH>i57900 Typical Response Message, Display Format: <SOH> I57900 22-05-08 15:02 TANK IDLE DELIVERY ENABLED <ETX>…
  • Page 82: In-Tank Setup

    Serial Interface Manual • TLS2 Monitoring Systems 7.3.4 IN-TANK SETUP Function Code: Version 1 Function Type: Set Tank Configuration Command Format: Inquire: Display: <SOH>S601TTf <SOH>I601TT Computer: <SOH>s601TTf <SOH>i601TT Typical Response Message, Display Format: <SOH> I60101 22-05-01 15:07 TANK CONFIGURATION DEVICE…

  • Page 83
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Product Label Command Format: Inquire: Display: <SOH>S602TTaaaaaaaaaaaaaaaaaaaa <SOH>I602TT Computer: <SOH>s602TTaaaaaaaaaaaaaaaaaaaa <SOH>i602TT Typical Response Message, Display Format: <SOH> I60201 22-05-01 15:07 TANK PRODUCT LABEL TANK PRODUCT LABEL REGULAR UNLEADED <ETX>…
  • Page 84
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 1 Point Full Height Volume Command Format: Inquire: Display: <SOH>S604TTGGGGGG <SOH>I604TT Computer: <SOH>s604TTFFFFFFFF <SOH>i604TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Full Height Volume, Gallons (Decimal)
  • Page 85
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 4 Point Full, 3/4, 1/2, 1/4 Volumes Command Format: Inquire: Display: <SOH>S605TTGGGGGGggggggGGGGGGgggggg <SOH>I605TT or: <SOH>S605TTGGGG,gggg,GGGG,ggg Computer: <SOH>s605TTFFFFFFFFffffffffFFFFFFFFffffffff <SOH>i605TT Notes: TT — Tank Number (Decimal, 00 = all)
  • Page 86
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank 20 Point Full, 95%, 90%,…Volumes Command Format: Inquire: Display: <SOH>S606TTGGGGGGgggggg… <SOH>I606TT or: <SOH>S606TTGGGG,gggg,GGGG,… Computer: <SOH>s606TTFFFFFFFF… <SOH>i606TT Notes: TT — Tank Number (Decimal, 00 = all)
  • Page 87
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Diameter Command Format: Inquire: Display: <SOH>S607TTIII.hh <SOH>I607TT Computer: <SOH>s607TTFFFFFFFF <SOH>i607TT Notes: TT — Tank Number (Decimal, 00 = all) III.hh — Tank Diameter, Inches and hundredths (Decimal)
  • Page 88
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Tilt Command Format: Inquire: Display: <SOH>S608TTIII.hh <SOH>I608TT Computer: <SOH>s608TTFFFFFFFF <SOH>i608TT Notes: TT — Tank Number (Decimal, 00 = all) III.hh — Tank Tilt, Inches and hundredths (Decimal)
  • Page 89
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Thermal Expansion Coefficient Command Format: Inquire: Display: <SOH>S609TTc.cccccc <SOH>I609TT Computer: <SOH>s609TTFFFFFFFF <SOH>i609TT Notes: TT — Tank Number (Decimal, 00 = all) c.cccccc — Thermal Expansion Coefficient (decimal)
  • Page 90
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Linear Calculated Full Volume Command Format: Inquire: Display: <SOH>S60ATTGGGGGG <SOH>I60ATT Computer: <SOH>s60ATTFFFFFFFF <SOH>i60ATT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Full Height Volume, Gallons (Decimal)
  • Page 91
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Stick Height Function Enable Command Format: Inquire: Display: <SOH>S60B00f <SOH>I60B00 Computer: <SOH>s60B00f <SOH>i60B00 Typical Response Message, Display Format: <SOH> I60B01 22-05-01 15:08 STICK HEIGHT OFFSET ENABLE STATUS ENABLED <ETX>…
  • Page 92
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Stick Height Offset Command Format: Inquire: Display: <SOH>S60CTTIII.hh <SOH>I60CTT Computer: <SOH>s60CTTFFFFFFFF <SOH>i60CTT Notes: TT — Tank Number (Decimal, 00 = all) III.hh — Stick Height Offset, Inches and hundredths (Decimal) FFFFFFFF — Stick Height Offset, Inches (ASCII Hex IEEE float).
  • Page 93
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Chinese Fixed Product Label Command Format: Inquire: Display: <SOH>S60DTTLL <SOH>I60DTT Computer: <SOH>s60DTTLL <SOH>i60DTT Typical Response Message, Display Format: <SOH> I60D01 22-05-01 15:08 CHINESE PRODUCT LABEL TANK 1 <ETX>…
  • Page 94
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Delivery Delay Command Format: Inquire: Display: <SOH>S610TTdd <SOH>I610TT Computer: <SOH>s610TTdd <SOH>i610TT Typical Response Message, Display Format: <SOH> I61001 22-05-01 15:08 TANK DELIVERY DELAY TANK PRODUCT LABEL REGULAR UNLEADED <ETX>…
  • Page 95
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Leak Test Type & Start Time Command Format: Inquire: Display: <SOH>S611TTDDRMYYMMDDHHmm<CR> (if M = 1) <SOH>I611TT MMWDHHmm<CR> (if M = 2) WDHHmm<CR> (if M = 3) DHHmm<CR>…
  • Page 96
    Serial Interface Manual • TLS2 Monitoring Systems Function Code 611 Notes: (Continued) M — Leak test Method: 1 = On Date 2 = Annually 3 = Monthly 4 = Weekly 5 = Daily — If M = 1 ON DATE, YYMMDDHHmm:…
  • Page 97
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Manifolded Partners Command Format: Inquire: Display: <SOH>S612TTttTTtt…<CR> <SOH>I612TT Computer: <SOH>s612TTttTTtt…<CR> <SOH>i612TT Typical Response Message, Display Format: <SOH> I61201 22-05-01 15:09 TANK MANIFOLDED PARTNERS TANK PRODUCT LABEL…
  • Page 98
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set In-Tank Leak Test Early Stop Command Format: Inquire: Display: <SOH>S61ATTf <SOH>I61ATT Computer: <SOH>s61ATTf <SOH>i61ATT Typical Response Message, Display Format: <SOH> I61A01 22-05-01 15:09 IN-TANK LEAK TEST EARLY STOP…
  • Page 99
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Low Level Limit Command Format: Inquire: Display: <SOH>S621TTGGGGGG <SOH>I621TT Computer: <SOH>s621TTFFFFFFFF <SOH>i621TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Low Level Limit, Gallons (Decimal)
  • Page 100
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Overfill Level Limit Command Format: Inquire: Display: <SOH>S623TTGGGGGG <SOH>I623TT Computer: <SOH>s623TTFFFFFFFF <SOH>i623TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Overfill Level Limit, Gallons (Decimal)
  • Page 101
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank High Water Level Limit Command Format: Inquire: Display: <SOH>S624TTII.t <SOH>I624TT Computer: <SOH>s624TTFFFFFFFF <SOH>i624TT Notes: TT — Tank Number (Decimal, 00 = all) II.t — High Water Level Limit, Inches and tenths (Decimal, Max=05.0)
  • Page 102
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Maximum Volume Limit Command Format: Inquire: Display: <SOH>S628TTGGGGGG <SOH>I628TT Computer: <SOH>s628TTFFFFFFFF <SOH>i628TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Maximum Volume Limit, Gallons (Decimal)
  • Page 103
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Delivery Required Limit Command Format: Inquire: Display: <SOH>S629TTGGGGGG <SOH>I629TT Computer: <SOH>s629TTFFFFFFFF <SOH>i629TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Delivery Required Limit, Gallons (Decimal)
  • Page 104
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Annual Leak Test Minimum Volume Command Format: Inquire: Display: <SOH>S62ATTGGGGGG <SOH>I62ATT Computer: <SOH>s62ATTFFFFFFFF <SOH>i62ATT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Annual Test Minimum Volume, Gallons (Decimal)
  • Page 105
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Enable/Disable Tank Leak Test Fail Alarms Command Format: Inquire: Display: <SOH>S62DTTgpa <SOH>I62DTT Computer: <SOH>s62DTTgpa <SOH>i62DTT Typical Response Message, Display Format: <SOH> I62D01 22-05-01 15:10 TANK LEAK TEST FAIL ALARMS…
  • Page 106
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Mag Probe Float Size Command Format: Inquire: Display: <SOH>S62FTTf <SOH>I62FTT Computer: <SOH>s62FTTf <SOH>i62FTT Typical Response Message, Display Format: <SOH> I62F01 22-05-01 15:10 MAG PROBE FLOAT SIZE…
  • Page 107
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Leak Test Report Type Command Format: Inquire: Display: <SOH>S63300f <SOH>I63300 Computer: <SOH>s63300f <SOH>i63300 Typical Response Message, Display Format: <SOH> I63301 22-05-01 15:10 LEAK TEST REPORT FORMAT: NORMAL <ETX>…
  • Page 108
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Periodic Leak Test Minimum Volume Command Format: Inquire: Display: <SOH>S636TTGGGGGG <SOH>I636TT Computer: <SOH>s636TTFFFFFFFF <SOH>i636TT Notes: TT — Tank Number (Decimal, 00 = all) GGGGGG — Periodic Test Minimum Volume, Gallons (Decimal)
  • Page 109
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Tank Overfill by Percent Command Format: Inquire: Display: <SOH>S638TTppp <SOH>I638TT Computer: <SOH>s638TTppp <SOH>i638TT Typical Response Message, Display Format: <SOH> I63801 22-05-01 15:11 TANK OVERFILL LEVEL LIMIT…
  • Page 110
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Density Code Command Format: Inquire: Display: <SOH>S641TTSSSSSSSSSSSSSS <SOH>I641TT Computer: <SOH>s641TTSSSSSSSSSSSSSS <SOH>i641TT Notes: 1. SSSSSSSSSSSSSS — Density Code (This entry should either be exactly 14 characters or empty)) — The density code should always start with either ‘A’…
  • Page 111
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 6 Function Type: Set Tank Density Float Serial Number Command Format: Inquire: Display: <SOH>S644TTSSSSSSSS <SOH>I644TT Computer: <SOH>s644TTSSSSSSSS <SOH>i644TT Typical Response Message, Display Format: <SOH> I644TT AUG 15, 2011 3:11 PM…
  • Page 112
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 6 Function Type: Set Tank GOST Volume Correction Enable Command Format: Inquire: Display: <SOH>S645TTf <SOH>I645TT Computer: <SOH>s645TTf <SOH>i645TT Typical Response Message, Display Format: <SOH> I645TT AUG 15, 2011 3:11 PM…
  • Page 113
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 6 Function Type: Set Tank Multipoint Chart Profile Command Format: Inquire: Display: <SOH>S647TTf <SOH>I647TT Computer: <SOH>s647TTf <SOH>i647TT Notes: TT — Tank Number (Decimal, 00 all) Enable = ‘1’. To disable change profile to 1,4,20 points or linear.
  • Page 114
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Density High Limit Command Format: Inquire: Display: <SOH>S671TTdd.ddd <SOH>I671TT Computer: <SOH>s671TTFFFFFFFF <SOH>i671TT Notes: TT — Tank Number (Decimal, 00=all) dd.ddd — Density High Limit (Decimal)
  • Page 115
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Set Tank Density Low Limit Command Format: Inquire: Display: <SOH>S672TTdd.ddd <SOH>I672TT Computer: <SOH>s672TTFFFFFFFF <SOH>i672TT Notes: TT — Tank Number (Decimal, 00=all) dd.ddd — Density Low Limit (Decimal)
  • Page 116: Miscellaneous Setup

    Serial Interface Manual • TLS2 Monitoring Systems 7.3.5 MISCELLANEOUS SETUP Function Code: Version 1 Function Type: Set Immediate Non-volatile RAM Store Command Format: Inquire: Display: <SOH>S85400ss149 <SOH>I85400 Computer: <SOH>s85400ss149 <SOH>i85400 Notes: ss — Save set up data Flag (see below)

  • Page 117
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Communication Port Data Command Format: Inquire: Display: <SOH>S881PPBBBBBPSDTAA <SOH>I881PP Computer: <SOH>s881PPBBBBBPSDTAA <SOH>i881PP Notes: PP — Communication Port Number (Decimal 01-05). Inquiry commands work for all 5 ports (Decimal 01-05). Set commands only work for the first 3 ports (Decimal 01-03).
  • Page 118
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Initialize Communication Port Data Command Format: Inquire: Display: <SOH>S882PP149 <SOH>I882PP Computer: <SOH>s882PP149 <SOH>i882PP Notes: PP — Communication Port Number (Decimal 01-05). Inquiry and set commands work for all 5 ports (Decimal 01-05).
  • Page 119
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Serial Communication Language Command Format: Inquire: Display: <SOH>S88300LL <SOH>I88300 Computer: <SOH>s88300LL <SOH>i88300 Typical Response Message, Display Format: <SOH> I88301 22-05-01 15:11 SERIAL LANGUAGE LANG : ENGLISH <ETX>…
  • Page 120
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Serial Handshaking Method Command Format: Inquire: Display: <SOH>S88400f <SOH>I88400 Computer: <SOH>s88400f <SOH>i88400 Notes: Inquiry and Set commands work for the first 3 ports (Decimal 01-03). The ports can be set to the following values: Port 1: 0 = None, 1 = XON/XOFF, 2 = Hardware Port 2 &…
  • Page 121
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Type Command Format: Inquire: Display: <SOH>S885PPMM <SOH>I885PP Computer: <SOH>s885PPMM <SOH>i885PP Notes: PP — Communication Port Number (Decimal 01 — 02) Typical Response Message, Display Format: <SOH>…
  • Page 122
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Dial-In Setup String Command Format: Inquire: Display: <SOH>S886PPaaaaaaaaaaaaaaaaaaaa <SOH>I886PP Computer: <SOH>s886PPaaaaaaaaaaaaaaaaaaaa <SOH>i886PP Notes: PP — Communication Port Number (Decimal 01 only) Typical Response Message, Display Format: <SOH>…
  • Page 123
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Communications Port Type Command Format: Inquire: Display: <SOH>S88APPt <SOH>I88APP Computer: <SOH>s88APPt <SOH>i88APP Notes: PP — Communication Port Number (Decimal 01-03) Inquiry and Set commands work for the first 3 ports (Decimal 01-03).
  • Page 124
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Printer Language Command Format: Inquire: Display: <SOH>S88BPPll <SOH>I88BPP Computer: <SOH>s88BPPll <SOH>i88BPP Notes: PP — Communication Port Number (Decimal 01 — 03) Typical Response Message, Display Format: <SOH>…
  • Page 125
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Set Modem Dial-Out Setup String Command Format: Inquire: Display: <SOH>S88CPPaaaaaaaaaaaaaaaaaaaa <SOH>I88CPP Computer: <SOH>s88CPPaaaaaaaaaaaaaaaaaaaa <SOH>i88CPP Notes: PP — Communication Port Number (Decimal 01 — 02) Typical Response Message, Display Format: <SOH>…
  • Page 126
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Acknowledge Tank Event Ready Status Command Format: Inquire: Display: <SOH>S89300149 <SOH>I89300 Computer: <SOH>s89300149 <SOH>i89300 Notes: 149 — This verification code must be sent to confirm the command Typical Response Message, Display Format: <SOH>…
  • Page 127
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: TCP/IP Parameter Inquiry Command Format: Display: <SOH>I8C000 Computer: <SOH>i8C000 Typical Response Message, Display Format: <SOH> I8C000 JAN 31, 2008 9:02 AM TCPIP SETUP PARAMETERS HOST IP ADDRESS: 10.2.1.51…
  • Page 128
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Host Address Command Format: Inquire: Display: <SOH>S8C100aaa.aaa.aaa.aaa <SOH>I8C100 Computer: <SOH>s8C100AAAAAAAA <SOH>i8C100 Notes: 1.aaa.aaa.aaa.aaa — Host IP Address (decimal) AAAAAAAA — Host IP Address (ASCII hex, two digits represent each field) Typical Response Message, Display Format: <SOH>…
  • Page 129
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Gateway IP Address Command Format: Inquire: Display: <SOH>S8C200aaa.aaa.aaa.aaa <SOH>I8C200 Computer: <SOH>s8C200AAAAAAAA <SOH>i8C200 Notes: 1.aaa.aaa.aaa.aaa — Gateway IP Address (decimal) AAAAAAAA — Gateway IP Address (ASCII hex, two digits represent each…
  • Page 130
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Subnet Mask Address Command Format: Inquire: Display: <SOH>S8C300aaa.aaa.aaa.aaa <SOH>I8C300 Computer: <SOH>s8C300AAAAAAAA <SOH>i8C300 Notes: 1.aaa.aaa.aaa.aaa — Subnet Mask Address (decimal) AAAAAAAA — Subnet Mask IP Address (ASCII hex, two digits represent each…
  • Page 131
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Host Port Number Command Format: Inquire: Display: <SOH>S8C400PPPPP <SOH>I8C400 Computer: <SOH>s8C400pppp <SOH>i8C400 Notes: PPPPP — Host Port (decimal) pppp — Host Port (ASCII Hex) Typical Response Message, Display Format: <SOH>…
  • Page 132
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Remote IP Address Command Format: Inquire: Display: <SOH>S8C500aaa.aaa.aaa.aaa <SOH>I8C500 Computer: <SOH>s8C500AAAAAAAA <SOH>i8C500 Notes: 1.aaa.aaa.aaa.aaa — Remote Address (decimal) AAAAAAAA — Remote Address (ASCII hex, two digits represent each field) Typical Response Message, Display Format: <SOH>…
  • Page 133
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set TCP/IP Remote Port Number Command Format: Inquire: Display: <SOH>S8C600PPPPP <SOH>I8C600 Computer: <SOH>s8C600pppp <SOH>i8C600 Notes: PPPPP — Remote Port (decimal) pppp — Remote Port (ASCII Hex) Typical Response Message, Display Format: <SOH>…
  • Page 134
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Email Recipient 1 Command Format: Inquire: Display: <SOH>S8C700r..r <SOH>I8C700 Computer: <SOH>s8C700r..r <SOH>i8C700 Typical Response Message, Display Format: <SOH> I8C700 JAN 31, 2008 9:02 AM TCPIP SETUP PARAMETERS EMAIL RECIPIENT 1: JOHNDOE@VEEDER.COM…
  • Page 135
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Email Recipient 2 Command Format: Inquire: Display: <SOH>S8C800r..r <SOH>I8C800 Computer: <SOH>s8C800r..r <SOH>i8C800 Typical Response Message, Display Format: <SOH> I8C800 JAN 31, 2008 9:02 AM TCPIP SETUP PARAMETERS EMAIL RECIPIENT 2: JANEDOE@VEEDER.COM…
  • Page 136
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Email From Command Format: Inquire: Display: <SOH>S8C900fffffffffffffffffffffff <SOH>I8C900 Computer: <SOH>s8C900fffffffffffffffffffffff <SOH>i8C900 Typical Response Message, Display Format: <SOH> I8C900 JAN 31, 2008 9:02 AM TCPIP SETUP PARAMETERS…
  • Page 137
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Set Email Mail Server IP Address Command Format: Inquire: Display: <SOH>S8CA00aaa.aaa.aaa.aaa <SOH>I8CA00 Computer: <SOH>s8CA00AAAAAAAA <SOH>i8CA00 Notes: 1.aaa.aaa.aaa.aaa — Email Mail Server IP Address (decimal) AAAAAAAA — Email Mail Server IP Address (ASCII hex, two digits…
  • Page 138
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: TCP/IP Save Setup Command Format: Display: <SOH>S8CB00149 Computer: <SOH>s8CB00149 Notes: 149 — code must be sent to confirm the command ??? — TCP/IP Setup not saved successfully Typical Response Message, Display Format: <SOH>…
  • Page 139: Diagnostic Reports

    Serial Interface Manual • TLS2 Monitoring Systems DIAGNOSTIC REPORTS 7.4.1 SYSTEM DIAGNOSTIC REPORTS Function Code: Version 1 Function Type: System Revision Level Report Command Format: Display: <SOH>I90200 Computer: <SOH>i90200 Typical Response Message, Display Format: <SOH> I90200 22-05-01 15:12 SOFTWARE# 349783-001-AXM CREATED — 01.05.17.15.11…

  • Page 140
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: System Revision Level Report II Command Format: Display: <SOH>I90500 Computer: <SOH>i90500 Typical Response Message, Display Format: <SOH> I90500 22-05-01 15:12 SOFTWARE# 349783-001-AXM CREATED — 01.05.17.15.11 SYSTEM FEATURES:…
  • Page 141
    Serial Interface Manual • TLS2 Monitoring Systems Function Code 905 Notes: (Continued) nn — number of 2 byte values to follow (Hex) AA — PERIODIC IN-TANK TESTS (00 = DISABLE, 01 = ENABLE) BB — ANNUAL IN-TANK TESTS (00 = DISABLE, 01 = ENABLE)
  • Page 142
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Setup Password Log In Status Command Format: Display: <SOH>I90F00 Computer: <SOH>i90F00 Typical Response Message, Display Format: <SOH> I90F00 07-12-09 09:43 SETUP PASSWORD LOG IN STATUS SETUP PASSWORD: ENABLED COMM 1: LOGGED IN <ETX>…
  • Page 143: In-Tank Diagnostic Reports

    Serial Interface Manual • TLS2 Monitoring Systems 7.4.2 IN-TANK DIAGNOSTIC REPORTS Function Code: Version 1 Function Type: Probe Type and Serial Number Command Format: Display: <SOH>IA01TT Computer: <SOH>iA01TT Typical Response Message, Display Format: <SOH> IA0101 22-05-01 15:12 TYPE CODE LENGTH SERIAL NO.

  • Page 144
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Factory Calibration Values Command Format: Display: <SOH>IA02TT Computer: <SOH>iA02TT Typical Response Message, Display Format: <SOH> IA0201 22-05-01 15:12 TANK REGULAR UNLEADED GRADIENT = 180.0000 OPT= 0x0000 <ETX>…
  • Page 145
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Last Sample Buffers Command Format: Display: <SOH>IA10TT Computer: <SOH>iA10TT Typical Response Message, Display Format: <SOH> IA1001 22-05-01 15:13 TANK REGULAR UNLEADED NUMBER OF SAMPLES = 569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000 13584.000 13585.000 13584.000 40000.000 21993.000 21993.000 21993.000 21993.000…
  • Page 146
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Fast Average Buffers Command Format: Display: <SOH>IA11TT Computer: <SOH>iA11TT Typical Response Message, Display Format: <SOH> IA1101 22-05-01 15:13 TANK REGULAR UNLEADED NUMBER OF SAMPLES = 569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000 13584.000 13585.000 13584.000 40000.000 21993.000 21993.000 21993.000 21993.000…
  • Page 147
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Standard Average Buffers Command Format: Display: <SOH>IA12TT Computer: <SOH>iA12TT Typical Response Message, Display Format: <SOH> IA1201 22-05-01 15:13 TANK REGULAR UNLEADED NUMBER OF SAMPLES = 569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000 13584.000 13585.000 13584.000 40000.000 21993.000 21993.000 21993.000 21993.000…
  • Page 148
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Long Term Average Buffers Command Format: Display: <SOH>IA13TT Computer: <SOH>iA13TT Typical Response Message, Display Format: <SOH> IA1301 22-05-01 15:13 TANK REGULAR UNLEADED NUMBER OF SAMPLES = 569.000 13584.000 13584.000 13584.000 13584.000 13585.000 13585.000 13584.000…
  • Page 149
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Mag Probe Option Table Command Format: Display: <SOH>IA14TT Computer: <SOH>iA14TT Typical Response Message, Display Format: <SOH> IA1401 22-05-01 15:13 MAG PROBE OPTIONS TABLE TEMP <ETX> Typical Response Message, Computer Format: <SOH>iA14TTYYMMDDHHmmTTNNL…
  • Page 150
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 4 Function Type: Probe Diagnostic Printout Command Format: Display: <SOH>IA18TT Computer: <SOH>iA18TT Typical Response Message, Display Format: <SOH> IA1801 22-05-01 15:13 DIAGNOSTICS SOFTWARE REVISION 349783-001-B TANK PROBE TYPE MAG1 SERIAL NUMBER…
  • Page 151
    Serial Interface Manual • TLS2 Monitoring Systems Function Code A18 Typical Response Message, Display Format: (Continued) COUNTS 15 017389 COUNTS 16 017468 COUNTS 17 017460 COUNTS 18 044370 OPTIONS CODE 0X0000 <ETX> Typical Response Message, Computer Format: <SOH>iA18TTYYMMDDHHmmTTppppsssssszzzzllllllllggggggggSSSSSSSS rrrrrrruuuuuuuuYYMMDDhhhhhhhhYYMMDDkkkkkkkk AAaaaaaaaa… aaaaaaaaBBbbbbbbbb…bbbbbbbb NNcccccccc…ccccccccKKKKKKKK…
  • Page 152
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags — Present Test Command Format: Display: <SOH>IA20TT Computer: <SOH>iA20TT Typical Response Message, Display Format: <SOH> IA2001 22-05-01 15:13 TANK REGULAR UNLEADED PRESENT LEAK TEST ANALYSIS REPORT 0.10 GAL/HR FLAGS:…
  • Page 153
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags — Stored Test Command Format: Display: <SOH>IA21TT Computer: <SOH>iA21TT Typical Response Message, Display Format: <SOH> IA2101 22-05-01 15:13 TANK REGULAR UNLEADED STORED LEAK TEST ANALYSIS REPORT 0.10 GAL/HR FLAGS:…
  • Page 154
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Probe Leak Test Flags — Gross Test Command Format: Display: <SOH>IA22TT Computer: <SOH>iA22TT Typical Response Message, Display Format: <SOH> IA2201 22-05-01 15:13 TANK REGULAR UNLEADED GROSS LEAK TEST ANALYSIS REPORT GROSS LEAK TEST FLAGS: <ETX>…
  • Page 155
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 1 Function Type: Get Tank Profile and Full Volume Command Format: Display: <SOH>IA30TT Computer: <SOH>iA30TT Typical Response Message, Display Format: <SOH> IA3001 22-05-01 15:13 TANK FULL VOLUME TANK PRODUCT LABEL…
  • Page 156
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 6 Function Type: Multipoint Tank Chart Report Command Format: Display: <SOH>IA31TT Computer: <SOH>iA31TT Typical Response Message, Display Format: <SOH> IA3101 AUG 22, 2011 3:12 PM MULTIPOINT TANK CHART TANK 1: SUPER DUPER…
  • Page 157: Miscellaneous

    Serial Interface Manual • TLS2 Monitoring Systems MISCELLANEOUS 7.5.1 MISCELLANEOUS Function Code: Version 5 Function Type: Push Site ID Command Format: Display: This command is only sent out by the TLS2P Computer: Typical Response Message, Display Format: Computer format only Typical Response Message, Computer Format: <SOH>iD0100YYMMDDHHmmDDDDDD000000&&CCCC<ETX>…

  • Page 158
    Serial Interface Manual • TLS2 Monitoring Systems Function Code: Version 5 Function Type: Server Heartbeat Command Format: Display: Computer: <SOH>iD0200cccc Typical Response Message, Display Format: Computer format only Typical Response Message, Computer Format: <SOH>iD0200YYMMDDHHmmcccc&&CCCC<ETX> Notes: YYMMDDHHmm — Current Date and Time cccc — Heartbeat Characters (ASCII characters [20h-7Eh]) &&…
  • Page 159: 8.0 Function Code Summary

    Serial Interface Manual • TLS2 Monitoring Systems 8.0 FUNCTION CODE SUMMARY CONTROL FUNCTIONS (7.1) Code Ver Function System Reset Remote Alarm Reset Computer Mode Autodial Hang-up Start In-Tank Leak Detect Test Stop In-Tank Leak Detect Test Password Log In Password Log Out OPERATIONAL REPORTS (7.2)

  • Page 160
    Serial Interface Manual • TLS2 Monitoring Systems IN-TANK REPORTS (7.2.2) (Continued) Code Ver Function Power Outage Delivery Report Inventory Snaphot Volume Manual Shift Inventory Snapshot Report In-Tank Full Inventory Report Density Offset History Report In-Tank Mass / Density Inventory Report 2 In-Tank Mass / Density Delivery Report 2 I/O DEVICE REPORTS (7.2.3)
  • Page 161
    Serial Interface Manual • TLS2 Monitoring Systems COMMUNICATIONS SETUP (7.3.2) (Continued) Code Ver Function Set RS-232 Security Code per Port Set Receiver Auto Dial On Events Set TC Density Enable Set IS03166 3 Character Country Code I/O DEVICE SETUP (7.3.3)
  • Page 162
    Serial Interface Manual • TLS2 Monitoring Systems IN-TANK SETUP (7.3.4) (Continued) Code Ver Function Set Tank High Water Level Limit Set Tank Maximum Volume Limit Set Tank Delivery Required Limit Set Tank Annual Leak Test Minimum Volume Set Enable/Disable Tank Leak Test Fail Alarms…
  • Page 163
    Serial Interface Manual • TLS2 Monitoring Systems MISCELLANEOUS SETUP (7.3.5) (Continued) Code Ver Function Set Email Recipient 2 Set Email From Set Email Mail Server IP Address TCP/IP Save Setup Part No. 577013-767, Revision H…
  • Page 164
    Serial Interface Manual • TLS2 Monitoring Systems DIAGNOSTIC REPORTS (7.4) SYSTEM DIAGNOSTIC REPORTS (7.4.1) Code Ver Function System Revision Level Report System Revision Level Report II Password Log In Status IN-TANK DIAGNOSTIC REPORTS (7.4.2) Code Ver Function Probe Type and Serial Number…
  • Page 165
    For technical support, sales or other assistance, please visit: www.veeder.com…

Veeder-Root TLS2: List of Available Documents

Note for Owners:

Guidesimo.com webproject is not a service center of Veeder-Root trademark and does not carries out works for diagnosis and repair of faulty Veeder-Root TLS2 equipment. For quality services, please contact an official service center of Veeder-Root company. On our website you can read and download documentation for your Veeder-Root TLS2 device for free and familiarize yourself with the technical specifications of device.

More Control Systems Devices:

  • Siemens SINUMERIK 840D sl

    SINUMERIKSINUMERIK 840D slMeasuring cyclesProgramming ManualValid for:Control system SINUMERIK 840D sl / 840DE sl SoftwareCNC software Version 4.8 SP2SINUMERIK Operate for PCU/PC version 4.8 SP212/20176FC5398-4BP40-6BA1PrefaceFundamental safety instructions1Description2Measuring variants3Parameter lists4Changes from cycle version SW4.4 and higherAAppendixB …

    SINUMERIK 840D sl Control Systems, 366

  • QOLSYS IQ PANEL

    IQ PANEL USER GUIDEWe hope you enjoy your new IQ Panel security and smarthome platform. It will serve as the “brain” of your home for many years to come. With it you can control your lights, locks, thermostat, security and much more. You won’t need a manual to operate your IQ Panel, but you can use this guide to learn more about the features of this amazing new device. We hope it will ad …

    IQ PANEL Security System, 23

  • Secura Key Radio Key 600

    RADIO KERADIO KERADIO KERADIO KERADIO KEYYYYY®®®®® 600600600600600QUICK-START USER GUIDEQUICK-START USER GUIDEQUICK-START USER GUIDEQUICK-START USER GUIDEQUICK-START USER GUIDEThis guide contains keypad sequences for programming your Radio Key® 600,using the built-in programming keypad.Radio Key® Transponders (Key Tags) are pre-encoded and engraved at thefactory with unique Transponder …

    Radio Key 600 Marine Radio, 4

  • EVOKO Room Manager

    Evoko Room Managerquick start guide.DE Evoko Room Manager Kurzanleitung.ES Evoko Room Manager Guía de inicio rápido.FR Guide de démarrage rapide d’Evoko Room Manager.IT Guida di avviamento rapido di Evoko Room Manager.PT Evoko Room Manager Guia de início rápido.RU Краткое руководство Evoko Room Manager. …

    Room Manager Control Systems, 6

  • Emec MAX5

    1Read Carefully !ENGLISH VersionR36-01-18OPERATING INSTRUCTIONS F O R “ MAX5” INSTRUMENTThis manual contains safety information that if ignored can endanger life or result in serious injury. They are indicated by this icon.Keep the instrument protected from sun and water. Avoid water splashes.Configuration and screenshots may be different and not including some functions. A maximum of 5 chan …

    MAX5 Control Systems, 56

Recommended Documentation:

Понравилась статья? Поделить с друзьями:
  • Оки порошок инструкция по применению отзывы цена отзывы аналоги
  • Сушильный шкаф снол руководство по эксплуатации
  • Инструкции по мытью посуды в детском саду по санпин 2020
  • Амброксол вертекс для ингаляций инструкция по применению для взрослых
  • Кнопка старт стоп xy q638 инструкция на русском